181
Kit (P/N 60460001) documentation and contact Customer Service (800–228–1161) for SAM
specific instructions/methodology. Be ready to provide the serial numbers of the valve(s) that re-
quire connection to/interface with Akroview.
5.4.
ITL-40 Calibration Procedure
The ITL-40 tank level gauges must be calibrated in order for the SAM Control Center to show ac-
curate tank level. The ITL-40 is used for Water, Foam A, and Foam B tank levels. Refer to ITL-40
manual (P/N118253).
5.4.1
Water Tank
The ITL-40 can be calibrated the traditional way using the 1, 2, or 9 point calibration (refer to
ITL-40 manual [P/N 118253]). Alternatively, the water tank level can be calibrated automatically
using the SAM Pump Controller and the following steps.
On the SAM Pump Controller, enter ITL-40 Calibration password (see Table 3, page 36.)
A.
Fill water tank.
B.
Touch check box when tank is full.
C.
Drain water tank. (Using a discharge.)
D.
Touch stop when pump starts to cavitate. (It is recommended to perform the cali-
bration while running the NFPA tank-to-pump flow-rate check/test.)
Figure 149. Water Tank Calibration Step 1
Figure 150. Water Tank Calibration Step 2
Содержание Hale Sam
Страница 2: ......
Страница 37: ...17 Figure 14 SAM Blue CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 38: ...18 Figure 15 SAM Green CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 39: ...19 Figure 16 SAM Red CAN Buss Architecture With Three SAM Control Centers Diagram...
Страница 40: ...20 Figure 17 SAM System Drain And Pneumatic Diagram...
Страница 41: ...21 Figure 18 SAM Speaks Diagram...
Страница 42: ......
Страница 58: ...38 THIS PAGE INTENTIONALLY BLANK...
Страница 62: ...42 THIS PAGE INTENTIONALLY BLANK...
Страница 192: ...172 THIS PAGE INTENTIONALLY BLANK...
Страница 206: ...186 THIS PAGE INTENTIONALLY BLANK...
Страница 220: ...200 THIS PAGE INTENTIONALLY BLANK...