Tongue Switch with Guard Locking & RFID Coding
Selector Switch
for choice
of Front or End sensing.
(See Fig 1)
Guard
Door
Status
Solenoid
Guard Lock
Status
LED1
Green
LED2
Red
11/12 21/22
Safety
Outputs
44
Guard OPEN
Signal Feed
34
Guard UNLOCKED
Signal Feed
Closed
Not Energized
Locked
Closed
Off 0V.dc
Off 0V.dc
Closed
Energized
Unlocked
Open
Off 0V.dc
On +24V.dc
Open
Energized
Unlocked
Open
On +24V.dc
On +24V.dc
Open
Not Energized
Unlocked
Open
On +24V.dc
On +24V.dc
Standards:
EN1088 EN60947-5-1 EN 60204-1
ISO 13849-1 EN62061 EN 954-1
Safety Classification and Reliability Data:
Mechanical Reliability B10d
EN 954-1
ISO 13849-1
EN 62061
Safety Data - Annual Usage
PFHd
Proof Test Interval (Life)
MTTFd
2.5 x 10
6
operations at 100mA load
up to Category 4 with Safety Relay
up to PLe depending upon system architecture
up to SIL3 depending upon system architecture
8 cycles per hour / 24 hours per day/365 days
3.44 x 10
-8
35 years
356 years
Supply Voltage
24V.dc (+/- 10%)
Power consumption:
0.5A. Supply capability 1A.required.
Safety Circuits:
2NC Positive Break and RFID coded
RFID cycle check
0.5s.
Utilization Category
AC15 A300 Maximum Current 3A.
Thermal Test Current (Ith)
3A
Rated Insulation Voltage
500VAC
Rated Impulse Withstand Volt
1000VAC
Travel for Positive Opening
10mm
Man. Actuation Frequency
2 cycle/sec
Actuator entry minimum radius
175mm
Body Case Material
KLTM-RFID: Die Cast - Painted Red
KLT-SS-RFID: Stainless Steel
Head Material
Stainless Steel 316
Mechanical Actuator Material
Stainless Steel 316
Enclosure Protection
IP67 IP69K
Operating Temperature
-25°C to 40°C
Mechanical Life Expectancy
1 x 10
6
Cycle min.
Vibration
IEC 68-2-6, 10-55Hz+1Hz,
Excursion: 0.35mm, 1 octave/min
IDEM SAFETY SWITCHES Ltd., 2 Ormside Close, Hindley Industrial Estate, Hindley Green, Wigan, WN2 4HR UK. Tel: +44 (0)1942 257070 Fax.: +44 (0)1942 257076
IDEM (USA) 4416 Technology Drive, Fremont, CA 94538 Tel:510-445-0751 Fax:1866-431-7064 email:
Web:
www.idemsafety.com
Doc: 102540
Feb. 2013
LED Normal Functions:
LED1 Green Guard Locked
LED2 Red Solenoid Energised
LED Diagnostic Functions:
LED1 Steady Yellow
Fault (See special instruction RESET)
LED1 Yellow/Green Alternate Flashing
Tag not recognised or not present.
Special Instruction: RFID actuator – RESET.
In the event that a Fault condition requires reset, follow the reset instructions
in the correct sequence:
1)
Turn off all power to the switch and open the guard.
2)
Remove the switch cover.
3)
Using a 2mm terminal screwdriver hold down the RESET button inside the switch housing and turn on the switch power (see Fig.2).
4)
Release the RESET button and the yellow LED will begin to flash, close the guard and the yellow LED will turn steady yellow.
(If yellow LED continues to flash check for mechanical fault (e.g. damaged actuator or switch head)).
5)
Turn power off and then on, the green LED will illuminate.
6)
Re-fit the switch cover.
7)
Open and close the guard ensuring all safety functions are correct – refer to any risk assessment for the particular guard application.
ENTRY SELECTOR SWITCH (inside cover):
Slide Switch Position 2:
FRONT Entry
Slide Switch Position 1:
END Entry
Fig. 1
Entry Selector
Switch
RESET button
(If required press and hold using
a 2mm terminal screw driver)
Fig. 2
Cover Removed