                                                                              Safety Interlock Switch 

 

 

IDEM SAFETY SWITCHES Ltd., 2 Ormside Close, Hindley Industrial Estate, Hindley Green, Wigan, WN2 4HR   UK.    Tel: +44 (0)1942 257070     Fax.: +44 (0)1942  257076 

IDEM (USA)  4416 Technology Drive, Fremont, CA 94538   Tel:510-445-0751  Fax:1866-431-7064  email:  

[email protected]

  Web: 

www.idemsafety.com

 

6.

 

Always ensure that when fitting electrical conductors that they are routed correctly and do not interfere with the switch cover during fitting.                                                   
Recommended conductor size is 1.5 – 2.5sq.mm, contact terminal tightening torque is 1Nm. 

7.

 

Tightening torque for the lid screw and cable glands is1Nm to maintain IP rating. 

8.

 

Check that the machine is stopped and cannot be started when the interlocked guard is open. 

9.

 

After installation apply tamper resistance paint or compound to the actuator and switch mounting bolts. 

 
 

Maintenance: 

Every Week:         Check the switch actuator and body for signs of mechanical damage and wear. Replace any switch showing damage. 
                             Check that the machine is stopped and cannot be started when the interlocked guard is open. 
Every 6 Months:   Check for mechanical damage to switch body or actuator. Replace any switch showing damage. 
                             Isolate power and remove cover. Check screw terminal tightness and check for signs of moisture ingress.  Never attempt to repair any switch.  
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 

Standards

 
EN1088, 50047, IEC 60947-5-1, EN60204-1  
ISO 13849-1, EN62061, UL508 

Safety Classification & Reliability Data: 

 Mechanical Reliability B10d  

 
2.5 x 10

operations at 100mA load 

EN 954-1  

Up to Category 4 with Safety Relay 

ISO 13849-1 

Up to PLe depending upon system architecture 

EN62061 

Up to SIL3 depending upon system architecture 

Safety Data – Annual Usage 

8 cycles per hour/24 hours per day/365 days 

PFHd 

3.4 x 10

-8

 

Proof Test Interval (Life) 

35 years 

MTTFd 

356 years 

Utilization Category 

AC15   A300   3A 

Thermal Current (lth) 

10A 

Rated Insulation/Withstand Voltages 

600VAC/2500VAC 

Actuator Travel/Force for Positive Opening 

6mm/12N 

Actuator Entry Minimum Radius 

175mm Standard    100mm Flexible 

Maximum Approach Withdrawal Speed 

600mm/s 

Body Material 

Polyester 

Enclosure Protection 

IP67 

Operating Temperature 

-25C  +80C 

Vibration 

IEC 68-2-6   10-55Hz+1Hz 
Excursion: 0.35mm, 1 octave/min 

Conduit Entry 

Various (see sales part numbers) 

Fixing 

2 x M4 

 

       R>=150mm 

       25 +/-  2mm 

         Minimum operating radius 

 Application Example: Door Interlock - Dual Channel non-monitored. 

This system shows interlock switch circuits 11-12 and 21-22 configured to allow dual circuit direct 
feeds to contactor coils K1 and K2.  
When the start button is pressed and then released, the auxiliary contacts (A) of contactors K1 and 
K2 maintain the feed to the contactor coils. 
Opening of the Interlock Switch or depressing the E Stop will isolate power to the contactor coils. 
Re-start can only occur providing the Guard is closed and the E Stop is reset. 
 
System is shown with the guards closed and the machine able to start.

 

Doc: 102503 
Jan. 2013 

Information with regard to UL 508:   

Type 1 Enclosures. 
Control Number 35NV  
Use 16 - 12AWG copper conductors rated 
90ºC minimum. 
Intended for same polarity use and 
one polymeric conduit connection. 
Electrical Rating: 
Max. Switching Current / Volt / Amp:   
120V. 6A. (720VA break)  PF 0.38 
240V. 3A. (720VA break)  PF 0.38 
Operating Temperature 40ºC 
 

                Outline fixing dimensions    mm 