IBMVN (Indirect Bit Move Not)
Applicable CPU Modules
Valid Devices
For the valid device address range, see pages 6-1 and 6-2 (Basic Vol.).
Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.
When T (timer) or C (counter) is used as S2 or D2, the timer/counter current (TC or CC) value is read out.
Make sure that the last source data determined by S1+S2 and the last destination data determined by D1+D2 are within the valid device range. If
the derived source or destination device is out of the valid device range, a user program execution error will result, turning on special internal relay
M8004 and ERR LED on the CPU module. For user program execution errors, see Chapter 4 “User Program Execution Errors” on page 4-21.
Either source device S2 or destination device D2 does not have to be designated. If S2 or D2 is not designated, the source or destination device is
determined by S1 or D1 without offset.
Examples: IBMVN
Source device S1 and destination device D1 determine the type of device. Source device S2 and destination device D2 are the offset values to
determine the source and destination devices.
As a result, when input I0 is on, the ON/OFF status of internal relay M30 is inverted and moved to output Q12.
S1 + S2 NOT
D1 + D2
When input is on, the values contained in devices designated by S1
and S2 are added to determine the source of data. The 1-bit data so
determined is inverted and moved to destination, which is
determined by the sum of values contained in devices designated by
D1 and D2.
IBMVN
S1(R)
*****
S2
*****
D1(R)
*****
REP
**
D2
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Base address to move from
X
X
X
X
—
—
X
0 or 1
1-99
S2 (Source 2)
Offset for S1
X
X
X
X
X
X
X
0-65535
—
D1 (Destination 1)
Base address to move to
—
X
X
—
—
X
—
1-99
D2 (Destination 2)
Offset for D1
X
X
X
X
X
X
X
0-65535
—
S1 –
M20
I0
IBMVN
S2
D10
SOTU
D1 –
Q0
REP
D2
C5
M20 + D10 NOT
Q0 + C5
If the value of data register D10 designated by source device S2 is 8, the
source data is determined by adding the offset to internal relay M20
designated by source device S1.
If the current value of counter C5 designated by destination device D2 is 10,
the destination is determined by adding the offset to output Q0 designated by
destination device D1.
M37
M20
M27
M30
8th from M20
Q17
Q0
Q7
Q10
10th from Q0
Q12
NOT
Содержание microsmart pentra
Страница 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Страница 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Страница 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Страница 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...