®  Communication Module User’s Manual

2-1

2.  Mounting and wiring the L

ON

W

ORKS

®

Communication Module

2.1 General 

guidelines

The following guidelines should be observed when mounting
wiring your L

ON

W

ORKS

®  Communication Module:

When wiring the L

ON

W

ORKS

®  Communication Module,

make certain that you follow all of the applicable and
legally binding standards. Observe all of the relevant
national and regional regulations when installing and
operating the device. Check with the local authorities
regarding the standards and regulations that must be
observed in your special case.

Make certain that the device is de-energized.

Use only approved bus cables.

Make certain that the specified cable lengths are used and
that the correct terminating resistors are installed properly.

The L

ON

W

ORKS

®  Communication Module must always

be installed as the last module on the right of the IDEC
SmartRelay, since you may not install other expansion
modules onto the L

ON

W

ORKS

®  Communication Module.

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

Содержание LONWORKS

Страница 1: ...LONWORKS Communication Module User s Manual FL9Y B695 ...

Страница 2: ... the corresponding safety measures are not taken With the warning triangle this indicates that minor bodily injury may occur if the corresponding safety measures are not taken Without the warning triangle this indicates that material damage may occur if the corresponding safety measures are not taken This indicates that an undesirable result or condition may occur if the corresponding instructions...

Страница 3: ...tility model is registered Disclaimer of liability We have checked that the contents of this document correctly describe the associated hardware and software Nonetheless it is impossible to exclude the possibility of deviations and therefore we cannot guarantee that there are no errors in this document The information in this document is checked regularly and any necessary corrections are then mad...

Страница 4: ...nnecting the power supply 2 4 2 2 2 Connecting the LON 2 5 3 Putting the LONWORKS Communication Module into operation 3 1 3 1 Step by step 3 1 3 2 The LONWORKS Communication Module operational status3 2 3 3 Behavior in case of a fault 3 3 4 Supported functions 4 1 4 1 Virtual inputs outputs 4 1 4 2 Available network variables 4 3 4 3 LON configuration parameters 4 5 4 4 Inputs Outputs special cons...

Страница 5: ...e with other LON devices What are the capabilities of the LONWORKS Communication Module The LONWORKS Communication Module presents the current states of the LON stations to the IDEC SmartRelay which is thus able to use its logical functions and timers to join them together In the process the LON signals can also be combined with the signals of the local IDEC SmartRelay inputs and outputs The LONWO...

Страница 6: ...LONWORKS Communication Module User s Manual 1 2 1 2 The construction of the LONWORKS Communication Module Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 7: ...o the IDEC SmartRelay 3 The RUN STOP LED for IDEC SmartRelay communication 4 The SERVICE LED 5 Input LON connection 6 Expansion interface to the IDEC SmartRelay 7 Mechanical coding pin 8 Service button 7 8 1 3 4 5 6 2 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 8: ...stalling and operating the device Check with the local authorities regarding the standards and regulations that must be observed in your special case Make certain that the device is de energized Use only approved bus cables Make certain that the specified cable lengths are used and that the correct terminating resistors are installed properly The LONWORKS Communication Module must always be instal...

Страница 9: ...nted and wired by qualified personnel who know and observe the generally applicable guidelines and applicable regulations and standards Observe the assembly and disassembly instructions in the IDEC SmartRelay manual WARNING The expansion module may only inserted or removed when the power is off Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 10: ...er the installation the terminals must be covered To protect personnel against unintentional contact with the portions of the LONWORKS Communication Module that are conducting electricity the appropriate national and local standards must be observed The LONWORKS Communication Module is a double insulated switching device A protective grounding conductor is not necessary Phone 800 894 0412 Fax 888 ...

Страница 11: ...uctions that are found in the product information that was included with your equipment as well as the technical data regarding the permissible voltage tolerances main frequency and current consumption Connecting How to connect the LONWORKS Communication Module to the power DC supply AC supply Protect the LONWORKS Communication Module with a 80 mA slow action fuse if desired recommended DC24V L N ...

Страница 12: ... made using the two screw terminals A B You can start the programming by pressing the Service button NOTE Don t apply force when pressing the Service button When contact has been made the LED will light up in orange Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 13: ...the LONWORKS Communication Module s installed location The Neuron ID is also given as a bar code on the label 6 Apply power to the IDEC SmartRelay and LONWORKS Communication Module 7 If multiple LONWORKS Communication Modules have been installed repeat Steps 1 to 6 for each LONWORKS Communication Module 8 To log a LONWORKS Communication Module in on a LON network you can either press the Service b...

Страница 14: ...OP Lights In Green RUN Red STOP Orange The LONWORKS Communication Module is communicating with the device on the left The LONWORKS Communication Module is not communicating with the device on the left The LONWORKS Communication Module s initialization phase LED SERVICE Lights In Green Red Orange Green Orange Flashing Configure Service button pressed The LONWORKS Communication Module s initializati...

Страница 15: ...TOP LED will light in RED after one second IDEC SmartRelay Power returns The IDEC SmartRelay will startup and the LONWORKS Communication Module will send the parameterized status LONWORKS Communication Module Power failure All of the inputs of the LONWORKS Communication Module will be set by the IDEC SmartRelay Master to 0 LONWORKS Communication Module Power returns All of the IDEC SmartRelay Mast...

Страница 16: ...1 Virtual inputs outputs The standard LONWORKS Communication Module application fills the complete IDEC SmartRelay process image I9 I10 I11 I12 Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 A 1 A2 Q9 Q16 FL1B H12RCE FL1B M08B2R2 FL1B M08B2R2 FL1B CL1C12 FL1B H12RCE FL1B CL1C12 A1 A2 A3 A8 I9 I24 Q5 Q16 LON LON I1 I2 I3 I4 I5 I6 I7 I8 Q1 Q2 Q3 Q4 A3 A8 I13 I24 I1 I2 I3 I4 I5 I6 I7 I8 Phone 800 894 0412 Fax 888 723 4773 ...

Страница 17: ... be joined with free virtual BUS outputs Q5 Q9 to Q12 in the IDEC SmartRelay application 2 Operations basic functions BF special functions SF useable within the IDEC SmartRelay application feedback value 3 To access the IDEC SmartRelay application Q1 to Q4 Q8 directly via the bus communications these must be joined with free virtual BUS inputs I13 to I24 in the IDEC SmartRelay application Phone 80...

Страница 18: ...status Output object status LonMark Controller Object SNVT Description SNVT_switch Switch light alarm window contact free inputs outputs value 0 state 0 Þ inactive value 0 state 1 Þ active SNVT_occupancy Occupancy 0 occupiedÞ 0 1 not occupied Þ 1 2 bypass Þ 0 3 standby Þ 1 SNVT_tod_event Scheduler program Just current state 0 occupied 3 standby SNVT_temp_p Room temperature SNVT_lux Brightness ligh...

Страница 19: ...witchDI131 I13 nviSwitchDI141 I14 nviSwitchDI151 I15 nviSwitchDI161 I16 nviSwitchDI171 I17 nviSwitchDI181 I18 nviSwitchDI191 I19 nviSwitchDI201 I20 nviSwitchDI211 I21 SNVT_switch nviSwitchDI221 I22 nviOccDI231 I23 Digital inputs SNVT_occupancy nviOccDI241 I24 SNVT_temp_p nviTempAI081 AI8 SNVT_lux nviLuxAI071 AI7 nviSwitchAI011 AI1 nviSwitchAI021 AI2 nviSwitchAI031 AI3 nviSwitchAI041 AI4 nviSwitchA...

Страница 20: ...end Heartbeat cpMaxSendTDO07 Q7 0 min SCPTmaxSendTime Send Heartbeat cpMaxSendTDO08 Q8 0 min SCPTmaxSendTime Send Heartbeat cpMaxSendTDO09 Q9 0 min SCPTmaxSendTime Send Heartbeat cpMaxSendTDO10 Q10 0 min SCPTmaxSendTime Send Heartbeat cpMaxSendTDO11 Q11 0 min SCPTmaxSendTime Send Heartbeat cpMaxSendTDO12 Q12 0 min SCPTmaxSendTime Send Heartbeat cpMaxSendTDO13 Q13 0 min SCPTmaxSendTime Send Heartbe...

Страница 21: ...ions these must be joined in the IDEC SmartRelay application with free virtual BUS inputs To map the IDEC SmartRelay inputs I1 I8 as outputs on the BUS these must be joined with free virtual BUS outputs in the IDEC SmartRelay application Feedback value Feedback variables are required for status displays for a variety of applications primarily lighting applications These are not directly supported ...

Страница 22: ... mm rail wall mounting Connections IDEC SmartRelay connection Standard expansion interface For IDEC SmartRelay 12 24 V and 100 240 V LON connection TP FT 10 2 screw terminals 0 5 2 5 mm Max torque 0 5 Nm Power supply 2 screw terminals 0 5 2 5 mm Max torque 0 5 Nm Standard bus lines to use 2 x 2 x 0 8 mm Environmental Conditions Permissible operating temperature 0 C to 55 C free convection Storage ...

Страница 23: ... suppression EN 55011 Limit Value Class B Certification CE UL 508 VDE 0631 IEC 61131 2 Overvoltage protection Fuse 80 mA slow action fuse Order Data IDEC SmartRelay Expansion Module LONWORKS Communication Module FL1B CL1C12 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Страница 24: ...N STOP LED 1 3 Service button 1 3 SERVICE LED 1 3 slider 1 3 SNVT_lev_percent 4 3 4 4 SNVT_lux 4 3 SNVT_obj_request 4 3 SNVT_obj_status 4 3 SNVT_occupancy 4 3 4 4 SNVT_switch 4 3 4 4 SNVT_temp_p 4 3 4 4 SNVT_tod_event 4 3 4 4 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...

Отзывы: