Functions
64
HR9Z-B2202 8/2020
Application Function 5
Synchronization:
Wiring of the inputs for coded magnetic switches
Characteristic
Value/Description
Typical applications
Monitoring of guards as per ISO 14119/14120
with electrical switches
Monitoring of guards as per ISO 14119/14120
with coded magnetic switches
Monitoring of proximity switches
Type of outputs of sensor/device providing the input signal
for application function
Normally open, normally closed and/or changeover
outputs
S## terminals to be connected
S11-S12 and S11-S13 for sensor/device A
S21-S22 and S21-S23 for sensor/device B
Dynamization
Yes
Signal interlock monitoring
No
Synchronized terminals
Synchronization time
S12 synchronized with S13
S12 and S13 have to be activated within 0.5 s.
S22 synchronized with S23
S22 and S23 have to be activated within 0.5 s.