![IDEAL Viscount GTS 14 Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/ideal/viscount-gts-14/viscount-gts-14_installation-and-servicing_3626405025.webp)
25
Viscount GTS -
Installation & Servicing
INSTALLATION
1
VIS5087
•
Fit the door onto the hinge
by inserting the pin (1).
2
VIS5088
29 INSTALLING THE HINGE OF THE FURNACE DOOR - Cont'd
•
Close the furnace door on the 8 studs and
fasten with 8 washers and nuts (2).
30 FITTING THE FLUEWAY DOORS
VIS5089
•
Fit the two doors of the upper flue ways (wing nuts).
•
Fit the plain flange onto the upper connection of the front
section (using four M18 nuts), with the 170 x 222 gasket in
between (first soak the gasket in warm water).
•
Fit the flange with the sludge removal hole onto the lower
connection of the front section (hole in the lower part of the
flange) using four M18 nuts, with the gasket in between
(soak in warm water first).
31 FLAME INSPECTION WINDOW
VIS5090
The flame inspection window is fitted with a 1/4" tapped hole for
ventilation (optional) :
-
if a ventilation system is used, connect the hole to the one
provided for that purpose before the burner combustion head.
INST
ALLA
TION
Содержание Viscount GTS 14
Страница 50: ...50 Viscount GTS Installation Servicing NOTES...
Страница 51: ...51 Viscount GTS Installation Servicing NOTES...