background image

11

Vanguard L  - 

Installation & Servicing 

GENERAL

7  SEALED (PRESSuRISED) SySTEm

Working pressure 6 bar maximum.

Particular reference should be made to BS 6644: Section 6 and 

Guidance note PM5 "automatically controlled steam and hot 

water boilers" published by the Health and Safety Executive.

The information and guidance given below is not intended to 

override any requirements of either of the above publications 

or the requirements of the local authority, gas or water 

undertakings.

In general commercial closed pressurised systems are 

provided with either manual or automatic water make up.

In both instances it will be necessary to fit automatic controls 

intended to protect the boiler, circulating system and ancillary 

equipment by shutting down the boiler plant if a potentially 

hazardous situation should arise.

Examples of such situations are low water level and operating 

pressure or excessive pressure within the system.

Depending on circumstances, controls will need to be either 

manual or automatic reset.

In the event of a shutdown both visual and audible alarms may 

be necessary.

Expansion vessels used must comply with BS. 4814 and must 

be sized on the basis of the total system volume and initial 

charge pressure.

Initial minimum charge pressure should not be less than 0.5 

bar (7.2 psi) and must take account of the static head and 

specification of the pressurising equipment.  The maximum water 

temperatures permissible at the point of minimum pressure in the 

system are specified in Guidance Note PM5.

When make up water is not provided automatically it will be 

necessary to fit controls which shut down the plant in the event of 

the maximum system pressure approaching to within 0.5 bar (5 

psi) of the safety valve setting.

Other British Standards applicable to commercial sealed systems 

are:

BS6880: Part 2
BS 1212
BS 6281: Part 1
BS 6282: Part 1
BS 6283: Part 4

8 VENTILATIoN

Safe, efficient and trouble-free operation of conventionally 

flued gas boilers is vitally dependent on the provision of an 

adequate supply of fresh air to the room in which the appliance 

is installed.

Ventilation by grilles communicating directly with the outside 

air is required at both high and low levels.  The minimum free 

areas of these grilles must be according to the following scale 

in Table 4.

Table 4 - Ventilation Requirements

Required area (cm

2

) per kW of total rated input (net)

   

Boiler Room 

Enclosure

  Low level (inlet) 

10

  High level (outlet) 

5

Note.

Where a boiler installation is to operate in summer months 

(e.g. DHW) additional ventilation requirements are stated, if 

operating for more than 50% of time. (Refer to BS 6644)

Position ventilation grilles to avoid the risk of accidental 

obstruction by blockage or flooding.  If further guidance on 

ventilation is required then consult BS 6644.

The supply of air by mechanical means to a space housing the 

boiler should be by mechanical inlet with natural or mechanical 

extraction.  Mechanical extract ventilation with natural inlet must 

not be used.

Where a mechanical inlet and a mechanical extract system is 

applied, the design ventilation flow rates should be as in BS 6644.

Note.

For mechanical ventilation systems an automatic control should 

be provided to cause safety shutdown or lockout of the boiler(s) in 

the event of failure of air flow in either inlet or extract fans.

ImPoRTANT. 

The use of an extractor fan in the same room as 

the boiler (or in an adjacent communicating room) can, in certain 

conditions, adversely affect the safe operation of the boiler.

Where such a fan is already fitted (or if it is intended to fit an 

extractor fan after installation of the appliance) the advice of the 

gas supplier should be obtained.

Содержание Vanguard L 170

Страница 1: ...you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy o...

Страница 2: ...60 90 60 90 60 90 Safety thermostat setting C 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 High low setting C 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54 84 54...

Страница 3: ...ficiency operation ease of maintenance fuel flexibility and low emissions Suitable for oil or gas operation the Vanguard L range is supplied in a choice of 18 standard models rated in outputs from 130...

Страница 4: ...ACENT TO THE BOILER EN 304 Test code for heating boilers for atomizing oil burners 73 23 EEC Low voltage directive Relevant standard is EN60335 1 89336 EEC Electromagnetic Compatibility Directive Rele...

Страница 5: ...lime reduces the heat transfer from metal to water by 10 In practice the deposition of these salts is liable to cause noises from the boiler body or even premature boiler failure Corrosion and the fo...

Страница 6: ...170 630 T1 Flow connection T2 Return connection T3 Safety valve and expansion connection T4 Drain connection T5 Flue connection T6 Burner connection Boiler Size 170 240 290 340 420 510 630 Dimension A...

Страница 7: ...E T1 N O P T3 T2 I H T6 T4 T5 T1 T3 T2 1 2 3 4 41 11 16 17 30 24 12 13 21 14 15 22 23 40 van8099 Boiler Size 760 870 970 Dimension A mm 1122 1122 1122 Dimension B mm 1605 1800 1995 Dimension C mm 1432...

Страница 8: ...dimensions for boiler room access requirements Boiler Size 1100 1320 1570 1850 2200 2650 3000 3500 Dimension A mm 1352 1352 1462 1462 1622 1622 1720 1970 Dimension B mm 1952 2292 2282 2652 2692 3014 3...

Страница 9: ...oned so that there is enough space available to allow the following Access around the boiler for servicing Space to open the boiler front door Space to access the burner Recommended minimum clearances...

Страница 10: ...of the system 4 The boiler is at the highest point of the system Systems designed to rise above the flow connections will of course automatically require a minimum static head higher than shown 5 The...

Страница 11: ...g Other British Standards applicable to commercial sealed systems are BS6880 Part 2 BS 1212 BS 6281 Part 1 BS 6282 Part 1 BS 6283 Part 4 8 Ventilation Safe efficient and trouble free operation of conv...

Страница 12: ...shall be inclined upwards at 45 9 Fluing Flue Size Refer to applicable regulations while determining the size and height of the flue Please note that Vanguard L boilers have pressurised and sealed com...

Страница 13: ...ght Jacket 1 Upper Rear Central Left Jacket 1 Support for the Upper Jacket 1 Body Insulation 1 1 1 1 1 1 Front Insulation 1 1 1 1 1 1 Rear Insulation 1 1 1 1 1 1 Central Body Insulation 1 1 Rear Side...

Страница 14: ...M16 8 8 8 8 8 8 8 16 16 16 16 16 16 16 16 16 16 16 M12x60 M12x60 M16x70 M16x70 M16x70 M16x70 M16x70 M16x70 M16x70 M16x70 M20x80 M20x80 M20x80 M20x80 M20x80 M20x80 M120x80 M20x80 1 1 1 1 1 1 1 1 1 1 1...

Страница 15: ...nels 3 and 4 D Fit the rear insulation 6 fix the rear lower and upper retaining strips 7 and 8 with the self tapping screws Fit the plastic cable clamps 9 to the upper rear panel 8 E Fit the Ideal bad...

Страница 16: ...3 4 van8103 16 Position of thermometer thermostat sensor in the bulb holder Vanguard L 170 to 970 LEGEND 1 Thermometer bulb 2 Operation thermostat bulb 3 Safety thermostat bulb 4 Minimum temp thermost...

Страница 17: ...r insulation 7 fix the rear lower panels 9 with pins and springs and the upper panel 10 with the self tapping screws 8 Fit the plastic cable clamps 11 to the upper rear panel 10 E Fit the Ideal badge...

Страница 18: ...the plastic cable clamps 8 to it E Fit the Ideal badge to the front edge of the front top panel 9 and secure with the rubber fixings F Fit the control panel to front top panel 9 Remove the upper shell...

Страница 19: ...front edge of the front top panel 8 and secure with the rubber fixings F Fit the control panel to front top panel 8 Remove the upper shell of the control panel and insert the capillaries of thermomete...

Страница 20: ...ok them to the screws fitted to the upper square tube To determine which one of the front side panels is the left or the right ensure that the cable clamp plates 7 are positioned facing toward the fro...

Страница 21: ...ostat 3 Safety thermostat 4 Minimum thermostat Ensure that the sensors are inserted to the bottom of the bulb holder and then secure them with the retaining clip 5 In case some other thermostat is nec...

Страница 22: ...mber can be achieved through adjustment of the screws 23 Door Assembly Vanguard L 170 to 630 Models The combustion chamber door is fitted with four fixing points two on the left hand side which are no...

Страница 23: ...when reversing the door the bushing 9 nut 10 and washer 11 will have to be moved as shown below details 1 and 3 for hinge side details 2 and 4 for hinge side Door Adjustment 1 Vertical door adjustmen...

Страница 24: ...be and the hole in the door insulation Gas Supply The gas supply MUST be sized in accordance with British Gas recommendations and be prefabricated in compliance with CP 331 Pt 1 and any Local Gas Boar...

Страница 25: ...ur meter not supplied High low regulating thermostat Minimum thermostat Safety thermostat with manual reset N B With three phase the motor must be connected directly in this case the instrument panel...

Страница 26: ...tting Live on this lead hence on T2 allows burner to fire on low fire in a 2 stage burner No 10 S3 Burner lockout indicator Feeds signal from lockout terminal on burner control box to a remote lock ou...

Страница 27: ...FF Switch illuminated Position I ON Position OFF 12 Burner Switch Position I ON Position OFF 13 Pump Switch Position I I ON Position OFF 21 Boiler ON OFF High Low Thermostat High fire 54 C 84 C low fi...

Страница 28: ...tors will be placed inside the relevant smoke pipes at a distance from the front tube plate as shown in the picture on the right When using the boiler at minimum output the smoke temperature will not...

Страница 29: ...and drain down to complete the flushing process c Refill and vent the system clear all air locks and again check for water soundness d Balance the system 3 Finally set the controls to the User s requ...

Страница 30: ...freezing Otherwise drain the system completely 39 Safety For boilers with gas burners It is the law that any service work must be carried out by a Gas Safe Registered Engineer WARNING Always turn off...

Страница 31: ...es 4 Close off the fuel supply to the burner 5 Ensure that the boiler has been cooled to ambient temperature 6 Isolate the mains supply to the boiler and burner 7 Open the combustion chamber door afte...

Страница 32: ...Technical Helpline 01482 498 376 www idealheating com Ideal Boilers P O Box 103 National Ave Kingston upon Hull HU5 4JN Telephone 01482 492 251 Fax 01482 448 858 Registration No London 322 137 Ideal...

Отзывы: