background image

12

icos

 - 

Installation & Servicing

GENERAL

7

SEALED SYSTEM REQUIREMENTS - continued

pressure. The cold feed pipe from the cistern should
include a non-return valve and a stop valve with an
automatic air vent connected between them, the stop
valve being located between the system and the
automatic air vent. The stop valve may remain open
during normal operation of the system if automatic
water make-up is required.

b.

Through a self-contained unit comprising a cistern,
pressure booster pump (if required) and, if necessary,
an automatic pressure reducing valve and flow
restrictor. The cistern should be supplied through a
temporary connection from a service pipe or cold
water distributing pipe.
This unit may remain permanently connected to the
heating system to provide limited automatic water
make-up.  Where the temporary connection is supplied
from a service pipe or distributing pipe which also
supplies other draw-off points at a lower level then a
double check valve shall be installed upstream of the
draw-off point.

c.

Through a temporary hose connection from a draw-off
tap supplied from a service pipe under mains
pressure. Where the mains pressure is excessive a
pressure reducing valve shall be used to facilitate
filling.

The following fittings shall form a permanent part of
the system and shall be fitted in the order stated:

A stop valve complying with the requirements of
BS. 1010, Part 2 (the hose from the draw-off tap shall
be connected to this fitting).
A test cock.
A double check valve of an approved type.

• Thoroughly flush out the whole of the system with

cold water, without the pump in position.

• With the pump fitted, fill and vent the system until the

pressure gauge registers 1.5 bar (21.5lb/in

2

).

Examine for leaks.

• Check  the operation of the safety valve by manually

raising the water pressure until the valve lifts.  This
should occur within ± 0.3 bar (± 4.3lb/in

2.

) of the

preset lift pressure.

• Release water from the system until the initial system

design pressure is reached.

• Light the boiler and heat the system to the maximum

working temperature. Examine for leaks.

• Turn off the boiler and drain the system while still hot.

• Refill and vent the system.

• Adjust the initial pressure to the required value.

4. Expansion Vessel

a.

A diaphragm type expansion vessel must be
connected to a point close to the inlet side of the
pump, the connecting pipe being not less than 15 mm
(

1/2

" nominal) size and not incorporating valves of

any sort.

b.

The vessel capacity must be adequate to accept the
expansion of the system water when heated to
110

o

C (230

o

F).

c.

The charge pressure must not be less than the
static water head above the vessel. The pressure
attained in the system when heated to 110

o

 C (230

o

F) should be at least 0.35 bar (5 Ib/in

2

) less than the

lift pressure of the safety valve.
For guidance on vessel sizing refer to the table in
Frame 8.

For further details refer to BS. 5449, BS. 7074:1 and
the British Gas Corporation publication  'Material and
Installation Specifications for Domestic Central
Heating and Hot Water'. For IE refer to the current
edition of I.S.813.

5. Cylinder

The cylinder must be either of the indirect coil type or a
direct cylinder fitted with an immersion calorifier which is
suitable for operating on a gauge pressure of 0.35 bar
(5 Ib/in

2

) in excess of the safety valve setting. Single feed

indirect cylinders are not suitable for sealed systems.

6. Make-up Water

Provision must be made for replacing water loss from the
system, either:

a.

From a manually filled make-up vessel with a readily
visible water level. The vessel should be mounted at
least 150 mm (6") above the highest point of the
system, and be connected through a non-return valve
to the system, fitted at least 300 mm (12") below the
make-up vessel on the return side of the domestic
hot water cylinder or radiators.
or

b.

Where access to a make-up vessel would be difficult
by pre-pressurisation of the system. Refer to 'Filling',
below.

7. Mains Connection

There must be no direct connection to the mains water
supply or to the water storage tank supplying domestic
water, even through a non-return valve, without the
approval of the local water authority.

8. Filling

The system may be filled by one of the following

methods:

a.

Through a cistern, used for no other purposes, via a
ball valve permanently connected directly to a service
pipe and/or a cold water distributing pipe.
The static head available from the cistern should be
adequate to provide the desired initial system design

Sizing procedure for expansion vessels:

 The volume of the expansion vessel (litres) fitted to a sealed system shall not be

less than that given by the table on the following page, multiplied by a factor of 0.8 (for flow temperatures of less than 83

o

C).

Содержание HE12

Страница 1: ...e specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers HE12 HE15 HE18 HE24 For users guide see reverse of book For the very lates...

Страница 2: ...2 icos Installation Servicing...

Страница 3: ...Notes Items 4 5 added Page 18 Frame 18 Terminal Wall Seal Assembly Position New frame added ref positioning of terminal wall seal Page 19 Frame 21 Flue Extension Ducts Item no 3 added Page 20 Frame 2...

Страница 4: ...0 37 Packaged weight kg lb 38 84 Maximum installation weight kg lb 31 68 Boiler size Height mm in 582 23 Width mm in 390 15 Depth mm in 278 11 The value is used in the UK Government s Standard Assess...

Страница 5: ...chnical Helpline on the back page Page Burner operating pressure n a Central heating flow temp measure and record Central heating return temp measure and record For combination boilers only Scale redu...

Страница 6: ...ide Installation from inside ONLY b If a core boring tool is to be used inside the building the space in which the boiler is to be installed must be at least wide enough to accommodate the tool Front...

Страница 7: ...ion Concentric Flue Screw Retaining Kit Roof Flue Kit to a maximum of 7 5m Powered Vertical Flue Kit 5 m primary and 17m secondary is a typical maximum flue length For further details refer to Powered...

Страница 8: ...erably by the gas supplier to ensure that the meter is adequate to deal with the rate of gas supply required It is the responsibility of the Gas Installer to size the gas installation pipework in acco...

Страница 9: ...bore and microbore systems BS 5449 Graph 1 Water flow rate and pressure loss WATER TREATMENT see Frame 9 The hot water storage cylinder MUST be of the indirect type and should preferably be manufactur...

Страница 10: ...a differential temperature of 20 o C across the boiler is not exceeded 4 Adjust room and cylinder thermostats and programmer to NORMAL settings The system should be vented directly off the boiler flow...

Страница 11: ...valve or discharge pipe should be positioned so that the discharge of water or steam cannot create a hazard to the occupants of the premises or cause damage to electrical components and wiring 3 Press...

Страница 12: ...ion vessel must be connected to a point close to the inlet side of the pump the connecting pipe being not less than 15 mm 1 2 nominal size and not incorporating valves of any sort b The vessel capacit...

Страница 13: ...elrad Group recommend water treatment in accordance with the Benchmark Guidance Notes on Water Treatment in Central Heating systems Ideal Stelrad Group recommend the use of FERNOX COPAL or MB1 or GE B...

Страница 14: ...assy 20 Fan bracket assy 21 Orifice plate 22 Flue thermistor LEGEND 1 Front casing panel 2 Sealing panel 3 Sump cover plate 4 Bottom casing panel 5 Flue sensing nipple 6 Return pipe 7 Flow pipe 10 BO...

Страница 15: ...4 wood screws 3 off B Wall plugs TP2B 3 off C Push in caps 6 off Refer to Frame 36 no 15 D Mains connector 1 off Pack A Contents A The boiler B Wall mounting template on cardboard C Wall mounting plat...

Страница 16: ...s stood correctly as marked on the carton 2 Cut and remove the strapping 3 Fold back the top flaps to gain access to the wall mounting plate literature and wall mounting card template 4 Remove the ins...

Страница 17: ...optional stand off kit should be used Care must be taken when cutting the ducts and marking the wall to suit this condition 4 If the boiler is to be installed with upward piping routed behind the boi...

Страница 18: ...e hole centre for standard installation Care MUST be taken to ensure the correct holes are drilled 1 Tape template into the selected position Ensure squareness by hanging a plumbline as shown 2 If fit...

Страница 19: ...not the jacking screw 3 Locate 2 No 14 x 50mm screws in the piping frame one at each side in any of the 3 holes provided at each side and screw home Note If using the stand off kit then locate the st...

Страница 20: ...e plastic inner flue 5 Fix to length using self tappers provided 6 Seal outer air duct using the tape provided Notes a If using the extension ducts go to Frame 18 b If the stand off frame is used it i...

Страница 21: ...pport cutting aid shown folded up Wall plugs 4 off Extension duct clamp 1 0m 39 long No 10 x2 wood screw 4 off nm8732 20 FITTING THE KIT Because of the flexibility of the telescopic flue terminal it i...

Страница 22: ...other materials may be used The drain outlet on the boiler is standard 21 5mm overflow pipe This size must not be reduced in any part of its length A plastic cap is fitted to the end of the condensate...

Страница 23: ...ddle BOILER External wall Ground Level Termination to Soak away cla7774 minimum 500mm BOILER External wall Ground Level Open end of pipe direct into gulley below grating but above water level DRAIN cl...

Страница 24: ...A located in the top of the flue manifold is secure and giving an effective seal 4 Secure the flue turret on top of the boiler by inserting the open ends of the turret clamp under the 2 studs and fixi...

Страница 25: ...pitched roof terminations using a concentric flue to run vertically from the top of the boiler and terminating above roof level Connection to the top of the boiler is made using both a separately sup...

Страница 26: ...so that products of combustion can safely disperse at all times Pluming may occur at the termination so where possible terminal positions where this could cause a nuisance should be avoided Minimum d...

Страница 27: ...27 icos Installation Servicing INSTALLATION FLUE OUTLET rf8737 rf8738 31 FLUE ARRANGEMENT Note The equivalent flue length resistance of the elbow kits are 90o elbow kit 1m 45o elbow kit 0 6m...

Страница 28: ...tile weather collar 1 nm8741 2 Extension Duct Vertical connector Turret clamp 3 nm8743 X 4 2 Push fit the vertical connector supplied seperately into the boiler flue connection and retain with the tur...

Страница 29: ...oiler via the gas service cock union Ensure that the gas supply pipe does not foul the boiler casing Refer to Frame 41 for details of the pressure test point position 35 ELECTRICAL CONNECTIONS WARNING...

Страница 30: ...agnostic controls to function correctly 3 Wire the switched live supply into L2 or connect L1 and L2 via external control switching as shown in Frame 32 In either case remove the wire link fitted L1 t...

Страница 31: ...br b 38 FUNCTIONAL FLOW WIRING DIAGRAM Overheat thermostat 1 2 br r r bk y pk b Mains Switch Flame detection electrode DC Fan Ignition electrode CH return thermistor not fitted Control thermistor DC G...

Страница 32: ...The fuse should be 3A Room Thermostat If the thermostat has a neutral connection use it It provides for more energy efficient operation by reducing switching temperature differentials Frost Protection...

Страница 33: ...pressure is able to obtain maximum output Refer to Table 2 1 Check that the system has been filled and that the boiler is not air locked For additional gas supply information refer to Gas Supply on pa...

Страница 34: ...d Use Regulations or rules in force 2 Explain and demonstrate the lighting and shutting down procedures 3 The operation of the boiler and the use and adjustment of ALL system controls should be fully...

Страница 35: ...l is not fitted 10 If for any reason the condensate S trap has been removed ensure the trap is refilled with water before reassembling 11 Check the gas consumption 12 Connect a suitable gas analyser t...

Страница 36: ...the 3 screws at the rear are extended to ease access 2 Lift off the burner from the combustion chamber IMPORTANT The burner head is a ceramic plaque construction Care must be taken to ensure that the...

Страница 37: ...gas service cock 10 Reconnect the electrical supply 1 Remove ignition and flame detection electrodes Refer to Frames 56 57 2 Remove the 3 screws retaining the sump cover and remove 3 Using a suitable...

Страница 38: ...els Refer to Frames 45 46 3 Pull the electrical leads off the control thermistor 4 Pull the control thermistor and spring clip off the IMPORTANT When work is complete the sealing panel must be correct...

Страница 39: ...nce of damage or deterioration is visible 9 Fit the new fan venturi assembly 10 Reassemble the boiler in reverse order taking care not to overtighten the screw on the fan mounting bracket 11 Check the...

Страница 40: ...ve the remaining screw holding the ignition electrode to the combustion chamber 6 Remove the electrode ispfu9788 5 4 5 Remove the flame detection electrode 6 Fit the new flame detection electrode usin...

Страница 41: ...nnect the earth wire 4 Remove the sensing tube from the gas control valve 5 Undo the union nut between the gas valve and the gas inlet cock 6 Undo the union nut on the outlet side of the gas control v...

Страница 42: ...the bottom panel 4 Remove the 2 control box screws 5 Carefully unplug all the electrical wiring from the control box 6 With the control box lowered pull the assembly forward to remove from the housing...

Страница 43: ...gasket supplied 8 Reassemble in reverse order 9 Check operation of the boiler Refer to Frame 52 1 Refer to Frame 52 2 Remove the boiler front and sealing panels Refer to Frames 45 46 3 Pull off the e...

Страница 44: ...should be retained and the discarded insulation should now be placed into it 10 Sweep any dampened particles and place in the plastic bag 11 Fit new insulation piece a Locate and align the insulation...

Страница 45: ...flue thermistor 13 Unscrew the M5 x 10 screw retaining the top manifold flue casing 14 Remove the top half of the flue manifold from the appliance 15 Undo the 4 M5 x 10 screws securing the bottom flu...

Страница 46: ...er Note Ensure that the boiler sealing panel is correctly seated compressing the seal to make an airtight joint 7 Check operation of boiler Refer to Frame 52 68 CONDENSATE S TRAP REPLACEMENT 1 Refer t...

Страница 47: ...RAME 71 ALTERNATING L A GO TO FRAME 72 ALTERNATING L 8 GO TO FRAME 73 ALTERNATING H 1 GO TO FRAME 74 ALTERNATING H F GO TO FRAME 75 ALTERNATING H 4 GO TO FRAME 76 ALTERNATING H n GO TO FRAME 77 ALTERN...

Страница 48: ...may measure the possible peak voltage of 339V In general terms a reading greater than 150V indicates that the correct voltage is supplied to the gas valve As an alternative to a multimeter a mains ch...

Страница 49: ...r connected across the thermistors terminal pins At 25 o C expect 9 700 10 300 Ohms At 60 o C expect 2 400 2 600 Ohms At 85 o C expect 1 000 1 100 Ohms Remove the boiler flow thermistor from the CH fl...

Страница 50: ...om PCB H9 L9 HEAT EXCHANGER OVERHEAT Is the system filled and vented and all isolation valves open including TRV s Bypass Check the pump is operating correctly in Heating DHW and check temp diffs acro...

Страница 51: ...172 625 19 E67 497 Gas control valve 1 170 913 22 E67 500 Flue thermistor 1 170 916 23 E67 501 Control thermistor 2 170 917 24 E67 502 Overheat thermostat 1 170 918 25 Ignition electrode kit 1 175 406...

Страница 52: ...52 icos Installation Servicing SHORT LIST OF PARTS nm8077d 78 SHORT LIST 79 BOILER CASING ASSEMBLY 1 Front casing panel with screws 2 Sealing panel with screws 4 Bottom casing panel with screws...

Страница 53: ...cl 1598 11 Burner assembly with screws and gasket LIST OF PARTS 80 CONTROLS ASSEMBLY 33 Controls assy with screws 34 Controls hinge bracket 35 User controls without item 38 36 PCB primary controls 38...

Страница 54: ...54 icos Installation Servicing NOTES...

Страница 55: ...55 icos Installation Servicing NOTES...

Страница 56: ......

Страница 57: ...act a government approved inspector LABC will record the data and will issue a certificate of compliance If you notify via Gas Safe Register they will then notify the relevant Local Authority Building...

Страница 58: ...Gas Safe Register ID Number...

Страница 59: ...ister ID Number Gas Safe Register ID Number Gas Safe Register ID Number Gas Safe Register ID Number Gas Safe Register ID Number Gas Safe Register ID Number Gas Safe Register ID Number Gas Safe Registe...

Страница 60: ...cification without notice The Ideal Boilers Technical Training Centre offers a series of first class training courses for domestic commercial and industrial heating installers engineers and system spe...

Отзывы: