COMMISSIONING CHECKLIST

When the Halo is set up use this commissioning checklist to check and complete the install.

Description

Confirmed

Use the “Identify” function to confirm successful pairing has 

taken place. Short press on the Pair button on the Smart 

Interface. Press Pair button again to exit “Identify” function. 

Zigbee LED on Smart Interface 

flashes green

Halo home screen flashes to 

indicate successful pairing

Halo is positioned in the homeowners chosen location if desk mounted. 

Check RSSI (Received Signal Strength Indication) of the 

Zigbee wireless connection via support page on the PRT 

(access via the menu).

Target RSSI between 0 and -65 

and text green

Check RSSI (Received Signal Strength Indication) of the 

Zigbee wireless connection and the Wi-Fi connection via the 

support information in the Halo app.

Target RSSI between 0 and -65 

and text green

On the Halo set the mode to AUTO then increase the 

temperature to 30°C (repeat using Halo app).

Flame ON

Boiler ON

Boiler LED on Smart Interface 

ON (Green)

On the Halo set the mode to AUTO then decrease the 

temperature to 5°C (repeat using Halo app).

Flame OFF

Boiler OFF

Boiler LED on Smart Interface 

OFF

Check the Smart Interface indication is correct.

Power LED green
Zigbee LED green
Connectivity LED green

Full battery level indication on Halo home screen.

Содержание Halo Combi Wi-Fi

Страница 1: ...w w w i d e a l b o i l e rs com Halo Combi W i Fi I n s t a l l a t i o n G u i d e...

Страница 2: ...he Halo unit is powered by 4 AA batteries and communicates with the Smart Interface through Zigbee a local RF protocol The Smart Interface is Wi Fi enabled and can be linked to the home Wi Fi network...

Страница 3: ...Name Halo Combi Wi Fi Model Qualifier ErP Class VI I certify that the boiler is connected to an enhanced load compensator and weather compensator Class VI provided via the internet This product is com...

Страница 4: ...ider using the Ideal Zigbee Booster Product Code 221132 or mounting the Smart Interface externally to the boiler using a bracket Product Code 220366 Further details on this at www idealboilers com The...

Страница 5: ...sing and clip into place 2 If no trim plate is required use the rear housing of the Halo to position the unit on the wall alternatively secure rear housing to trim plate Take care not to overtighten t...

Страница 6: ...d rear housing and desk stand 2 Insert the 4 AA batteries provided into the front housing of the Halo Pay close attention that the orientation of the batteries is as indicated in the housing 3 Clip th...

Страница 7: ...m connection see diagram On brand new boilers the link should already be in place 2 Locate the wiring terminals 230V connections are on the left and low voltage on the right 3 If existing 230V device...

Страница 8: ...the aperture 8 Push fit the Halo Smart Interface into the boiler aperture 5 Locate the blanking plate on the front of the boiler and remove carefully with a small flat bladed screwdriver 6 Remove lin...

Страница 9: ...ch off the boiler the Override LED should now go out 11 Press and hold the Pair button on the Smart Interface until the Zigbee LED starts flashing red to begin the pairing process with the Halo 9 Swit...

Страница 10: ...ete when the Halo has successfully connected to the Smart Interface 5 The device will automatically prompt set up of the time and date 6 There is the opportunity to add an installer contact phone numb...

Страница 11: ...unt has been set up the app will automatically guide the user through connection of the Halo This will involve using the app to link the Halo Smart Interface to the home Wi Fi network by following the...

Страница 12: ...ent person Landlord settings Specific settings for landlords Override and Failsafe only active when communication is lost between Halo and Halo Smart Interface See Halo User Guide for more information...

Страница 13: ...erature at the time specified OFF Delayed start If the room temperature is close to target temperature the heating start time is delayed to save energy OFF Display tolerance Select the display toleran...

Страница 14: ...s connection via support page on the PRT access via the menu Target RSSI between 0 and 65 and text green Check RSSI Received Signal Strength Indication of the Zigbee wireless connection and the Wi Fi...

Страница 15: ...the target temperature is above current temperature Check Smart Interface power LED is green Check Smart Interface is securely plugged into boiler aperture Halo screen shows failed to pair Check Smart...

Страница 16: ...ing a Wi Fi Booster or mounting the Smart Interface externally to the boiler using a bracket further details on www idealboilers com Deleting Halo from the Zigbee Network On the Halo press the dial an...

Отзывы: