manualshive.com logo in svg
background image

Exalt

 

Burner Mounting Plate Replacement

4

4. Reinstall the igniter gasket, igniter, and igniter

screws. Tighten the screws to 26.5 to 31 in-lbs of

torque. Ensure the green grounding cables are

connected.

5. Reinstall the sightglass, sightglass gasket and

screws onto the mounting plate.

6. Install one new blower gasket, then metal damper,

then the second blower gasket onto the burning

mounting plate and finally reattach the blower/

venturi/gas line assembly to the burner mounting

plate. Tighten the blower bolts to 62-71 in-lbs of

torque.

WARNING

!

Ensure the gasket is in place before reassembly.  Fail-
ure to do so can result in death, serious injury or sub-
stantial property damage.

7.

 

Reconnect the gas supply piping to the venturi.

Ensure the pipe gasket is properly seated before

tightening the nut.

WARNING

!

Ensure the gasket is in place before reassembly.  Fail-
ure to do so can result in death, serious injury or sub-
stantial property damage.

8. Reattach the air inlet elbow to the venturi.

9. Re-attach all the wires to the gas valve, blower and

Igniter.

10. Turn on gas supply to the inlet of the unit at the

main manual shutoff valve to the unit. Check and

test all gas connections for leaks. Repair leaks if

found.

WARNING

!

Do not check for gas leaks with an open flame.  Use a 
bubble test.  Failure to check for gas leaks can cause 
severe personal injury, death or substantial property 
damage.

11. Turn power to the unit “ON”.  The unit is now ready

to be placed back into service.