VENTILATION REQUIREMENTS OF COMMERCIAL
BOILERS OVER 70kW NET INPUT
ROOM SEALED APPLIANCES, TYPE C IN PLANT ROOMS
OPEN FLUED APPLIANCES, TYPE B IN PLANT ROOMS
(ADDITIONAL RECOMMENDATIONS)
OPEN FLUED APPLIANCES, TYPE C IN PLANT ROOMS
(ADDITIONAL RECOMMENDATIONS)
FLUE TYPE
VENTILATION DIRECT TO OUTSIDE AIR
(cm
²
per kW net heat input)
HIGH
LOW
(TYPE C)
2
2
Natural Ventilation cm
²
kw (net) heat input for open flue boilers located in a boiler house
(A) Boiler House
(B) Enclosure
Summer usage*
greater than 50% up
to 75%
Summer usage*
greater than 75% up
to 100%
High
2
5
+1
+2
Low
4
10
+1
+2
*for boilers in use for more than 50% of the time during the summer months, additional ventilation needs to be
added to those in columns A and B
Natural Ventilation cm
²
kw (net) heat input for open flue boilers located in a boiler house
(A) Boiler House
(B) Enclosure
Summer usage* greater
than 50% up to 75%
Summer usage* greater
than 75% up to 100%
To a room
or internal
space
Direct to
outside air
High
2
10
5
+1
+2
Low
2
10
5
+1
+2
*for boilers in use for more than 50% of the time during the summer months, additional ventilation needs to be
added to those in columns A and B
For further information, please refer to:
• Manufacturer’s instructions
• IGEM UP10
• BS6644
Содержание EVOMAX 2 40P
Страница 1: ...EVOMAX 2 CONDENSING BOILER PRODUCT FLUE GUIDE...
Страница 5: ...5...
Страница 12: ...12 EVOMAX 2 CASCADE 30 900kW...
Страница 16: ...16 SYSTEM LAYOUT TYPICAL SYSTEM BOILER LAYOUT EVOMAX 2 FRAME HEADER KIT C W PLATE HEAT EXCHANGER LEGEND...
Страница 18: ...18 EVOMAX 2 FLUE OPTIONS...
Страница 19: ...19...
Страница 41: ...41...
Страница 43: ...43 NOTES...