EXAMPLE 3 (OPEN FLUE)
EXAMPLE 4 (CONCENTRIC)
OPEN FLUE FOR EVOMAX 2 30
Resistance (m)
Flue Size
80
Max permissible flue run
65
2 x 45˚ elbow
2 x 0.45 = 0.9
Total Flue Resistance
65 - 0.9 = 64.1
HORIZONTAL FLUE FOR EVOMAX 2 120
Resistance (m)
Flue Size
100/150
Max permissible flue run
9
2 x 90˚ elbow
2 x 1.9 = 3.8
Total Flue Resistance
9 - 3.8 = 5.2
b
9
5
3
5-
0
1
2
6
0
2
EXAMPLE 2 (CONCENTRIC)
VERTICAL FLUE FOR EVOMAX 2 80
Resistance (m)
Flue Size
80/125
Max permissible flue run
10
2 x 45˚
2 x 0.85 = 1.7
Total Flue Resistance
10 - 1.7 = 8.3