Solar Thermal -
Installation and Servicing
55 faulT finDing
no floW solar primary circuiT
possible causes
acTion
System in “stagnation”
Check
st. limit
at max
Airlock in circuit
Purge air
Manometer on low pressure
Refill and manually operate Differential Temperature Controller (DTC)
Faulty check valve
Check open and if necessary, replace
Steam escaped from AAV
Manual isolate AAV and refill. Check expansion vessel
Fluid exhaust from SRV
Check expansion vessel, SRV and refill
Faulty or blocked pump
Free, clean and if necessary, replace
Frost damage to collector
Replace collector and re-commission circuit
Blocked circuit
Check for degraded old antifreeze blockage or limescale blockage
PT1000 sensors loose
Relocate sensors
Faulty DTC
See below
loW performance of solar sysTem
possi
BLE CAUSES
ACTION
Faulty DTC/system settings
Check delta T
on
and delta T
off
settings, flowrate and pump speed control. Also check
functions ON/OFF and DTC on auto.
Faulty PT1000 sensors
Check sensor location and check electrical resistance to temperature
(see table in Frame 50).
Faulty pump
Check pump is rotating. Check valves open and pump speed correctly set.
Restriction in circuit
Check circuit components and for old antifreeze/limescale restriction in pipes.
Inadequate air removal
Purge air.
Loss insulation
Re-attach insulation.
Boiler primary circuit providing too
much heat
Reset central heating timeclock to give solar system more cylinder water to heat
WaTer Too HoT aT poinTs of use
possible causes
acTion
Incorrectly set DTC
Check
st. limit
on DTC
Incorrectly set TMV
Check output temperature from TMV
Faulty boiler primary circuit
Check out boiler primary circuit for faults
faulTy DTc
possible causes
acTion
No LCD display
No power supply, check fuse and 230 V
LCD says
short circuit T1/T2
Check relevant sensor for short circuit
LCD says
interruption T1/T2
Check relevant sensor for circuit break