InStALLAtIon

Ideal airtherm - Air Source Heat Pump - 

Installation

oPtIonAL WeAtHeR CoMPenSAtIon

Coding switches (item     )

Setting potentiometers (items     ,      ,     )

FUNCTION

SWITCH POSITION ON LEFT SYMBOL SYMBOL SWITCH POSITION ON LEFT

SUGGESTED 

SETTING

Base point of heating 
curve

Base point at 20ºC flow 
temperature

20ºC

35ºC

Base point at 35ºC flow 
temperature

Set to Left

Frost protection, yes/no

Yes, frost protection

No, no frost protection

Set to Right

Changeover of 
compensating variable, 
yes/no

No changeover: always 
weather compensated control 
and room temperature 
authority according to setting 
potentiometer E

Changeover to  room 
temperature compensated 
control at reduced level

Set to Left

Pump overrun, yes/no

Six minute pump overrun

6 Min

0 Min

0 minutes, no pump overrun

Set to Right

 

 

 

 

WEATHER COMPENSATOR UNIT

 

 

 

ITEM

POTENTIOMETER

FUNCTION

SETTING RANGE

GUIDE VALUE

SUGGESTED SETTING

1

Switching differential 

of heat pump 

temperature control

1…20 K

6 K

Set to 5 K

4

Authority of room 

temperature on heat 

pump temperature 

control

0…100 % authority 

OFF = quick 

setback is inactive

50 % (quick 

setback is active)

Set to OFF

5

Heating limit for 

ECO automatic 

energy saver

 –10…+8 °C 

(referred to the room 

temperature 

setpoint)

–3 K (gives a 

heating limit of 16 

°C at a room 

temperature 

setpoint of 20 °C)

Function disabled: OFF

1. Setting potentiometer for switching differential.

2. Setting knob for heating curve slope.

3. Coding switches

4. Setting potentiometer for authority of room
    temperature for quick setback active/inactive.

5. Setting potentiometer for ECO heating limit.

6. Heating curve chart.

LEGEND

1

2

3

3

1

4

5

4

5

6

The use of a weather compensator with Ideal airtherm heat pumps achieves greater efficiency benefits.
An example of using the Siemens model RVP102 follows.

Содержание AIRTHERM 12

Страница 1: ...ured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal For the very latest copy of literature fo...

Страница 2: ...2 Ideal airtherm Air Source Heat Pump Installation...

Страница 3: ...al wiring 8 Electrical Diagrams 9 10 Internal Machine Circuit Diagrams 11 12 Frost protection 13 Control Panel 13 Commissioning 14 Handing Over 14 Fault finding 15 16 Data sheet 17 Machine dimensions...

Страница 4: ...SER where it is surrounded by water from the heating system The heat is given up to the cooler water and the now cooler refrigerant returns to its former liquid state but still under high pressure fro...

Страница 5: ...lone basis monovalent system to satisfy the full heating and hot water demand of the property or in parallel with an existing boiler bivalent system In the case of a bivalent installation the heat pum...

Страница 6: ...d entering the unit may impede the normal airflow and result in a malfunction e Allow for the minimum clearances around the machine as shown below required for unobstructed air flow and access to serv...

Страница 7: ...run in front of service panels f All pipe work must be adequately supported with allowance for expansion contraction and should be insulated to avoid unnecessary heat loss a The Ideal air source heat...

Страница 8: ...s 9 and 10 of this manual b The wiring junction box is located behind the access panel below the unit s control panel c For the heat pump to operate you must have a live signal into terminal 9 space h...

Страница 9: ...EARTH CONNECTION HERE Connect to Connect to Heat Pump Terminal Connections S Plan Connections AW45002 AW9002 External Wiring Connections W Plan Connections AW45002 AW9002 External Wiring Connections...

Страница 10: ...e in fromProgrammer Programmer Live Lamp 2 2 31 Internal Connection Defrost Terminals Add link if Required Mains Pow er Supply LIVE GO SIGNAL FOR HEATING PUMP W AND Y PLAN ONLY OUT COMPRESSOR 1 C MAIN...

Страница 11: ...ALVE FROM PROGRAMMER 4 7 1 3 9 6 PF CAP RESISTOR 100 OHM R9 R9 2 1 4 3 DEFROST THERMOSTAT R1 7 4 3 5 OUT1 C H HP SWITCH 430PSI FAULT LAMP AMBER PROBE 10 12 R4 8 5 TECNOLOGIC N O N O N C COM COM COM N...

Страница 12: ...PROGRAMMED TIMED WATER PERIOD FROM STAT DEMAND 7 4 R9 A1 A2 SOPAC JAEGER 1 2 TECASA R5 8 5 ELEC BOX EARTH STUD TB 24 LIVE GO SIGNAL FOR HEATING PUMP ON Y AND W PLAN ONLY 9 6 TB 29 TB 30 R9 R9 PROGRAM...

Страница 13: ...the water flow and pressure drop should be set to the values shown in the data sheet on page 17 of this manual LEGEND A Space Heating Temperature Controller B Mains Lamp red C Defrost Lamp Green D Pro...

Страница 14: ...s will confirm that the system is working h Central heating system tests i Set the programmer to central heating ii Turn the room thermostat up to 30o C at which point the water circulating pump shoul...

Страница 15: ...air flows are not restricted Check Heating pump s FAN OFF COMPRESSOR ON NO ROOM HEATING OR HOT WATER UNIT NOT OPERATING POWER FAULT DEFROST PROGRAMMER LIVE RED AMBER GREEN RED ON OFF ON ON Unit on def...

Страница 16: ...etting Both HEATING DHW OPEN TB10 TB13 TB1 TB14 TB9 TB15 TB30 TB10 TB5 TB13 Buffer Tank heated to setting Heating only HEATING OPEN TB10 TB9 TB15 TB30 TB10 Buffer Tank already being heated Programmer...

Страница 17: ...2 93 Air on 7o C 87 RH TO EN 14511 2 2007 OUTPUT TO WATER 35o c kW 4 40 8 40 11 70 ELECTRICAL INPUT kW 1 18 2 27 3 13 C O P SEE NOTE 6 3 72 3 70 3 70 Air on 2o C 60 RH DESIGN WATER FLOW OUTPUT TO WAT...

Страница 18: ...S 3 4 BSPM STUBS CONDENSATE CONNECTION 3 4 BSPM STUB ALLOW 500mm FOR ACCESS TO SERVICE PANELS SEE WIRING DIAGRAMS CUSTOMERS ELECTRICAL CONNECTIONS AIR ON EVAPORATOR PANEL REMOVABLE FAN PANEL REMOVABLE...

Страница 19: ...3 4 BSPM STUBS CONDENSATE CONNECTION 3 4 BSPM STUB ALLOW 500mm FOR ACCESS TO SERVICE PANELS SEE WIRING DIAGRAMS CUSTOMERS ELECTRICAL CONNECTIONS AIR ON EVAPORATOR PANEL REMOVABLE TOP PANEL REMOVABLE F...

Страница 20: ...CONDENSATE CONNECTION 3 4 BSPM STUB ALLOW 500mm FOR ACCESS TO SERVICE PANELS SEE WIRING DIAGRAMS CUSTOMERS ELECTRICAL CONNECTIONS AIR ON EVAPORATOR PANEL REMOVABLE TOP PANEL REMOVABLE 36 95 5 958 FAN...

Страница 21: ...50 LITRES AIRTHERM 9 100 LITRES AIRTHERM 12 150 LITRES IF FITTED OPTIONAL 2 PORT SAFETY CUT OUT VALVE FITTED IN INDIRECT PRESSURISED CYLINDERS PROGRAMMER e g DANFOSS FP175 OUTSIDE SENSOR PART OF WEATH...

Страница 22: ...LL V4043 ROOM HEATING ROOM THERMOSTAT DOMESTIC HOT WATER THERMOSTAT PROGRAMMER TERMINAL JUNCTION BOX AIR SOURCE HEAT PUMP INTERNAL TERMINALS N E N L E N L N E L L L L L HW CH L N E L L N E L L L N E L...

Страница 23: ...T VALVE FITTED IN INDIRECT PRESSURISED CYLINDERS PROGRAMMER e g DANFOSS FP175 OUTSIDE SENSOR PART OF WEATHER COMPENSATION UNIT IF FITTED JUNCTION BOX FROST STAT WEATHER COMPENSATION UNIT IF FITTED DWE...

Страница 24: ...UMP INTERNAL TERMINALS N E N L E N L N E L L L L L HW CH L N E L L N E L L L N E L N HIGH LEVEL MANUAL RESET THERMOSTAT HIGH PRESSURE CYLINDER ONLY REQUIRED ONLY IF HIGH LEVEL STAT NOT FITTED 12 11 L...

Страница 25: ...e open 60 deg C DHW TANK BUFFER TANK 55 deg C DHW Supply Defrost By pass Valve 55 deg C 70 deg C 55 deg C NRV 50 deg C 50 deg C Return Temp Thermostat sensor Ambient Thermostat sensor 20 l min Boiler...

Страница 26: ...AL E D C M THERMOSTAT CONSOLE HEATING RETURN WATER REVERSING VALVE COIL COMP HP SCHRADER SERVICE HP SUCTION ACCUMULATOR TEV PHIAL TEV DRIP TRAY HEATER DRIER RECEIVER CONDENSER NRV PORT PROCESS CAPILLA...

Страница 27: ...V PHIAL TEV PHIAL PROCESS PORT LP SERVICE SCHRADER TEV RECEIVER REVERSING VALVE COIL SUCTION ACCUMULATOR DRIER DRIP TRAY HEATER NRV NRV CAPILLARY 1 4 DIA X 300mm LONG SOL VALVE TEV COMP 2 LP SERVICE S...

Страница 28: ...ht WEATHER COMPENSATOR UNIT ITEM POTENTIOMETER FUNCTION SETTING RANGE GUIDE VALUE SUGGESTED SETTING 1 Switching differential of heat pump temperature control 1 20 K 6 K Set to 5 K 4 Authority of room...

Страница 29: ...coldest wall of the house normally wall facing north The sensor must never be exposed to the morning sun Mounting Height Preferably in middle of dwelling to be heated but at least 2 5m above the groun...

Страница 30: ...er 15 0 litre 150 litre 180 litre 15 50 1 S or W Plan 4 5kW underfloor n a 7 5 n a Yes 50 litres separate cylinder buffer 150 litre 150 litre 180 litre 15 50 2 2 pump system 9 0kW radiators no 15 abov...

Страница 31: ...lves must comply with BS6759 All system components must comply with the required local water regulations Thermostore Cylinders Pressure Data Thermstore Coil Pressure Data 1 Inlet control to 2 1 bars b...

Страница 32: ...undish Cold Feed c w Baffle and Check Valve Fitted female for High Limit Stat Pocket Control Thermostat Buffer Vessel for Heating 3 kW Immersion heater integrated stat 1 Flow Return Connections for Bu...

Страница 33: ...w Heat Pump Stat Boss for Control Stat Boss for High Limit Stat 1 Returns 1 Flow Heating Thermstore Unvented direct Buffer Cylinder Cylinder Type Shell size mm Finished Size Ideal No 50L Direct 450 x...

Страница 34: ...strated to the customer Yes The manufacturer s literature including Benchmark Checklist and Service Record has been explained and left with the customer Yes CENTRAL HEATING MODE Heating Flow Temperatu...

Страница 35: ...rative ID No Comments Signature Date Engineer Name Company Name Telephone No Operative ID No Comments Signature Date Engineer Name Company Name Telephone No Operative ID No Comments Signature Date Eng...

Страница 36: ...36 Ideal airtherm Air Source Heat Pump Installation...

Страница 37: ...37 Ideal airtherm Air Source Heat Pump Installation...

Страница 38: ...n and performance of its products The right is therefore reserved to vary specification without notice The Ideal Boilers Technical Training Centre offers a series of first class training courses for d...

Отзывы: