SECTION 4 - FAULT FINDING
4.16 NO HW BUT CH ON
Does the display show “dH” when a tap is on?
NO
YES
Are the flow rates correct as per Section 1.16.
Is the wiring between the PCB and the diverter
valve actuator connected?
YES
YES
Check diverter head fully engaged onto
waterset body
YES
Is diverter stuck in the CH position
YES
Check and replace diverter valve actuator head.
Is Boiler DHW OK?
NO
Change diverter valve assembly.
NO
Adjust flow rates to achieve 35º
temp rise and check filter fitted in
turbine is not blocked with debris.
NO
Reconnect wiring or
replace wiring harness if
no continuity.
NO
Re-engage diverter
head.
NO
Replace PCB
Is hot and cold pipework crossed?
NO
Is the wiring connected
between PCB and DHW
sensor?
Remove the turbine, and
check for debris in the
turbine. Replace turbine
if necessary. Is DHW
OK?
YES
NO
Re-connect wiring
NO
Replace turbine sensor
4.17 NO DISPLAY
Is there 230Vac to the boiler at L and N?
Replace PCB
YES
NO
Supply power to the boiler
Is the wiring from the terminal block to the Main PCB
connected securely?
YES
NO
Connect the wiring from the terminal block to the
Main PCB securely.
L
N