40
INSTALLATION
EVOMAX
-
Installation & Servicing
INST
ALLA
TION
INST
ALLA
TION
INST
ALLA
TION
DISABLING THE ANTI-LEGIONELLA FUNCTION
Installer Mode
Normal Operation
Set Flow Temp’
Set DHW Temp’
Note that the Anti-Legionella Temperature Function is only
operational if a Domestic Hot Water Thermistor has been connected.
Care should be taken in disabling this function as an unsafe condition
could result.
Press SELECT and then hold + and - down together for more than
5s, the following screen will be displayed
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Anti-Legion Temp’
Anti-Legion Enable
BUS Address
Flame/LPG Relay
Press SELECT and the following screen will be displayed
Anti-Legion Enable
On
Off
Press + and - to change to required setting then press ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted again
and press SELECT to return to normal operation
CHANGING THE VOLT FREE BURNER ON RELAY TO OPERATE
AS AN LPG RELAY FOR BELOW GROUND LEVEL LPG
APPLICATIONS
Installer Mode
Normal Operation
Set Flow Temp’
Set DHW Temp’
If LPG is to be used in an application below ground level then an
additional valve is required to control the LPG input to the boiler
This valve should be wired from the Volt Free Burner on Relay and
enabled as follows
Press SELECT and then hold + and - down together for more than
5s, the following screen will be displayed
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
BUS Address
Flame/LPG Relay
Normal Operation
Press SELECT and the following screen will be displayed
Flame/LPG Relay
Flame On
LPG Gas Valve
Press + and - to change to the required setting and then press
ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted
again and press SELECT to return to normal operation
40 EVOMAX USER INTERFACE - ADVANCED OPERATING INSTRUCTIONS CONTINUED....
REVERTING TO FACTORY SETTINGS
Installer Mode
Normal Operation
Set Flow Temp’
Set DHW Temp’
Press SELECT, hold + and - together for more than 5s, the
following screen will be displayed
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
DHW Sensor
Factory Settings
Anti-Legion Temp’
Anti-Legion Enable
Press SELECT and the following screen will be displayed
Factory Settings
Reset?
Press ENTER and a screen similar to the following will be displayed
Factory Settings
Are you sure?
Press Enter to Reset
Press Select not to
Reset
Press ENTER and a screen similar to the following will be displayed
Factory Settings
Reset?
Press Select then Rotate the KNOB clockwise until Normal Operation
is highlighted again and press SELECT to return to normal operation
CHANGING THE ANTI-LEGIONELLA TEMPERATURE
Installer Mode
Normal Operation
Set Flow Temp’
Set DHW Temp’
Note Anti-Legionella Temp. Function is only operational if a DHW
Thermistor has been connected
Care should be taken reducing this temp. as unsafe condition could result
Press SELECT and then hold + and - down together for more than 5s,
the following screen will be displayed
Rotate the KNOB clockwise until the following screen is displayed
Installer Mode
Factory Settings
Anti-Legion Temp’
Anti-Legion Enable
BUS Address
Press SELECT and the following screen will be displayed
Anti-Legion Temp’
70°C
Press + and - to change to required setting, press ENTER to store
Rotate the KNOB clockwise until Normal Operation is highlighted again
and press SELECT to return to normal operation