background image

Ideal Boilers

, P.O. Box 103, National Ave, Kingston Upon Hull, HU5 4JN. Tel.

01482 492251 Fax. 01482 448858. Registration No. London 322 137.

Ideal Stelrad Group 

pursues a policy of continuing improvement in the design and performance

of its products.  The right is therefore reserved to vary specification without notice.

Ideal Consumer Helpline

Tel: 01482 498660

www.idealboilers.com

POINTS FOR THE BOILER USER

Note.

  

In line with our current warranty policy we would ask that you check through the following guide to identify any

problems external to the boiler prior to requesting a service engineers visit.  Should the problem be found to be other than
with the appliance we reserve the right to levy a charge for the visit, or for any pre-arranged visit where access is not gained
by the engineer.

TROUBLESHOOTING - TYPICAL NON PRODUCT FAULTS

The nature of all combination boilers is to heat up water directly from the incoming mains water supply directly through the boiler
to supply domestic hot water at the stated flow rates, (as shown in the boiler installation instructions), to achieve a set
temperature rise. As the ambient temperature of the cold main varies during the summer and winter months it is likely in the
colder winter months that the flow rate will need to be reduced at the outlet taps to achieve the same temperatures achieved in the
warmer summer months. 

This is not a fault with the appliance but is relevant to the varying temperature of the incoming cold

mains water supply.

Problem

Solution

Boiler is not working for
central heating or hot water

Is there power to the boiler – check by switching the boiler 'ON/OFF' switch (A) off and then
back on.  The lights (E) should flash.  If not this is not a boiler fault - contact the installer.

Check pressure gauge on boiler (D) shows a minimum of 1 bar.  If not re-pressurise via the
filling loop to 1 bar (if unsure contact your installer), turn off the tap on the filling loop and carry
out ignition restart sequence detailed under 'Faults'.  If unable to do so or if the pressure
continues to drop then contact your installer.

Is the fault indication light (2) alight - see Reset Procedure under 'Faults'.

Fan and pump run
continuously but there is no
attempt at ignition

Check that the flue product test cap, on top of the boiler is fitted correctly.

Operating for hot water but
will not operate for central
heating.

Check that integral programmer (if fitted) is set to an 'on' period and the function switch is set
to 'auto' - If it still does not operate contact your installer.

If fitted with an external programmer check that the central heating channel is set at an 'on'
period - If it still does not operate contact your installer.

Check the room thermostat is set at the required temperature - Test the room thermostat by
turning fully up - If this does not respond contact your installer.

Check the CH thermostat knob (B) is set at the winter setting for central heating.

Boiler goes through ignition
sequence but will not fire for
either central heating or hot
water and then goes to
ignition lockout

Check gas supply (try another gas appliance – cooker/fire etc.) – If no gas supply then this is
not a boiler fault – contact gas supplier.

F a u l t s

No heating or hot water

Check that gas and electricity are available at the boiler and
that all switches are on.

Check that the system water pressure gauge (D) reads at least
0.5 bar.

Reset Procedure

Check the red fault indication light (2).  If it is illuminated turn
the main switch (B) to '0', wait until the boiler reaches standby
state, indicated by no fan or pump running.  This can take up to
10 minutes in an overheat condition.  Turn the main switch (B)
to the winter setting wait for 2 seconds then set the main switch
(B) back to the desired position to restart the ignition sequence.

Hot water but no heating 

(winter setting)

Check that the programmer and room thermostat (if fitted) are
both calling for heat.

Heating but no hot water

Check that cold water flows out of the taps at a minimum rate of
3.5 litres per minute (or 1 pint in 10 seconds or less).  If not,
look for stop valves not fully open.

If these simple checks fail to solve the problem, or the
problem recurs, consult your service engineer.

201279-6.pmd

02/11/2007, 07:42

64

Содержание excel HE C24

Страница 1: ...icing instructions When replacing any part on this appliance use only spare parts that you can be assured conform to the safety and performance specification that we require Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Boilers HE C24 C28 C32 ...

Страница 2: ...ng a 3mm 1 8 contact separation in both poles serving only the boiler and system controls Alternatively a 3 pin UNSWITCHED socket may be used The means of isolation must be accessible to the user after installation Important Notes z This appliance must not be operated without the casing correctly fitted and forming an adequate seal z If the boiler is installed in a compartment then the compartment...

Страница 3: ... Internal frost protection operates regardless of the position of the main switch and CH heating thermostat knob B Therefore when the boiler is not lit and used in cold weather with consequent risk of freezing the supply to the boiler should be left switched on If the system includes a frost thermostat then during cold weather the boiler should ONLY be turned OFF at the time switch if fitted The m...

Страница 4: ... Faults If unable to do so or if the pressure continues to drop then contact your installer Is the fault indication light 2 alight see Reset Procedure under Faults Fan and pump run continuously but there is no attempt at ignition Check that the flue product test cap on top of the boiler is fitted correctly Operating for hot water but will not operate for central heating Check that integral program...

Отзывы: