GENERAL

Boiler Size

HE

9

12

15

18

Boiler

kW

 9.0

12

15

18

Output Btu/h x 1000

30.7

40.9

50.2

60.4

Water Flow

l/min

11.7

15.6

19.5

23.4

Rate

gal/h

155

206

258

309

Pressure

mbar

54.0

93.5

98.4

142.5

Loss

in wg

21.6

37.4

39.3

57

Table 5 - Water flow rate and pressure loss

TERMINAL

The terminal assembly can be adapted to accommodate various
wall thicknesses. Refer to Frame 10.

AIR SUPPLY

Detailed recommendations for air supply are given in BS.5440:2.
In IE refer to I.S. 813:2002.

The following notes are for general guidance:

1.

It is NOT necessary to have a purpose provided air vent in the
room or internal space in which the boiler is installed.

2.

If the boiler is to be installed in a cupboard or compartment,
permanent air vents are required (for cooling purposes) in
the cupboard/compartment, at both high and low levels. The
air vents must either communicate with room/internal space,
or be direct to outside air. The minimum effective areas of the
permanent air vents, required in the cupboard/compartment,
are specified in Table 4 and are related to maximum rated
heat input.

The boiler is fitted with a special drain plug, which is provided, to
drain the BOILER ONLY, in the event of the system drain plug
being unable to do so. The hydraulic resistance of the boilers, at
MAXIMUM OUTPUT with an 11

O

C (20

O

F) temperature differential,

are shown in Table 5.
Maximum boiler operating temperature should be 82

o

C (180

o

F).

Table 4 - High and low vent areas

Boiler

Air from room/internal

Air direct from

space, cm (in

2

 )

outside, cm (in

2

)

HE9

 102

(16)

 51

(8)

HE12

135

(21)

 68

(11)

HE15

170

(26)

 83

(13)

HE18

198

(31)

 102

(16)

3.

Both air vents MUST communicate with the same room or
internal space or MUST be on the same wall to outside air.

4.

In siting the air vents care must be taken to avoid the freezing
of pipework.Water circulation system.

WATER CIRCULATION SYSTEM

The boiler must NOT be used for direct hot water supply. For the
types of system and correct piping procedure refer to 'Introduction'
and Frame 1.
The central heating system should be in accordance with BS.6798
and, in addition, for Smallbore and Microbore systems, BS. 5449.
The domestic hot water system, if applicable, should be in
accordance with the relevant recommendations of BS. 5546. Copper
tubing to BS. 2871:1 is recommended for water carrying pipework.
The hot water storage cylinder MUST  be of the indirect type and
should preferably be manufactured of copper.
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating, nor
are they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of
the useful heating surface, should be lagged to prevent heat loss
and any possible freezing - particularly where pipes run through
roof spaces and ventilated under floor spaces.
Boilers not fitted to a sealed  system must be vented.

IMPORTANT

A minimum length of 1m of copper pipe MUST be fitted to both
flow and return connections from the boiler before connection to
any plastic piping.  

This applies to ALL types of installation.

Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler
and hot water storage vessel. They should be at least 

1/2" BSP

nominal size and be in accordance with BS. 2879.

WATER TREATMENT

These boilers incorporate a cast iron heat exchanger and an
aluminium heat exchanger

.

IMPORTANT. 

The application of any other treatment to this

product may render the guarantee of 

Wolseley UK

 INVALID.

Wolseley UK

 recommend Water Treatment in accordance with

the 

Benchmark

 Guidance Notes on Water Treatment in Central

Heating Systems.

Wolseley UK

 recommend the use of Fernox, GE Betz Sentinel or

Salamander water treatment products, which must be used on
accordance with the manufacturers instructions.
For further information contact:
Fernox Manufacturing Co. Ltd, Cookson Electronics, Forsyth Road,
Sheerwater, Woking, Surrey.   GU21 5RZ.  Tel. +44 (0) 1799 521133
or

Sentinel Performance Solutions
The Heath Business & Technical Park, Runcorn, Cheshire
WA7 4QX.  Tel: 0800 389 4670.  www.sentinel-solutions.net

or
Salamander Engineering Ltd, Unit 24, Reddicap Trading Estate,
Sutton Coldfield, West Midlands B75 7BU.  Tel. +44 (0) 121 378 0952

Notes.

1.

It is most important that the correct concentration of the water
treatment products is maintained in accordance with the
manufacturers' instructions.

2.

If the boiler is installed in an existing system any unsuitable
additives MUST be removed by thorough cleansing.
BS7593:1992 details the steps necessary to clean a
domestic heating system.

3.

In hard water areas, treatment to prevent limescale may be
necessary - however the use of artificially softened water is
NOT permitted.

4.

Under no circumstances should the boiler be fired before the
system has been thoroughly flushed.

BOILER CONTROL INTERLOCKS

Wolseley UK

 recommend that heating systems utilising full

thermostatic radiator valve control of temperature in individual
rooms should also be fitted with a room thermostat controlling
the temperature in a space served by radiators not fitted with
such a valve as stated in BS. 5449.
Central heating systems controls should be installed to ensure
the boiler is switched off when there is no demand for heating or
hot water.

continued . . . .

201962-6.pmd

19/02/2008, 15:10

9

Содержание Classic HE12

Страница 1: ...boiler Optia HE High Efficiency Boilers Installation Servicing Instructions See reverse for Optia HE Users Guide Manufactured exclusively for Wolseley UK by Ideal Boilers For details of document amendments refer to page 3 January 2008 UIN 201 962 A06 ...

Страница 2: ...2 Optia HE Installation Servicing ...

Страница 3: ...es 39 40 Condensate Pipe Termination Configurations BS6798 recommends that a second trap and an air break are required where the siphon trap within the boiler is less than 75mm for configuration 2 and 3 Page 27 Frame 40 Condensate Pipe Termination Configurations Statement added with ref to termination into a down pipe Page 33 Frame 54 Burner and Air Box Removal Item No 5 added Users Guide Page 2 I...

Страница 4: ...the gross C V of the gas Btu ft3 Table 1 General Data The value is used in the UK Government s Standard Assessment Procedure SAP for energy rating of dwellings The test data from which it has been calculated have been certified by a notified body Table 2 Performance Data Key to symbols GB United Kingdom IE Ireland Countries of destination PMS Maximum operating pressure of water C12 C32 A room seal...

Страница 5: ...l Helpline on the back page Page Burner operating pressure measure and record Central heating flow temp measure and record Central heating return temp measure and record For combination boilers only Scale reducer n a Hot water mode Heat input n a Max operating burner pressure n a Max operating water pressure n a Cold water inlet temp n a Hot water outlet temp n a Water flow rate at max setting n a...

Страница 6: ...istered Installer It must be carried out in accordance with the relevant requirements of the Gas Safety Installation and Use Regulations The appropriate Building Regulations either The Building Regulations The Building Standards Scotland Building Regulations Northern Ireland The Water Fittings Regulations or Water byelaws in Scotland The Current I E E Wiring Regulations Where no specific instructi...

Страница 7: ... core boring tool is to be used inside the building the space in which the boiler is to be installed must be at least wide enough to accommodate the tool Front clearance 450mm 17 3 4 from the front of the boiler casing Minimum front clearance when built behind a concealed panel is 5mm 1 4 provided that the top and bottom of the casing is not enclosed and the side clearance is 40mm 1 1 2 both sides...

Страница 8: ...accordance with the recommendations of BS 5440 1 2000 In IE refer to I S 813 2002 The following notes are intended for general guidance 1 The boiler MUST be installed so that the terminal is exposed to external air 2 It is important that the position of the terminal allows the free passage of air across it at all times 3 Minimum acceptable spacing from the terminal to obstructions and ventilation ...

Страница 9: ...ral heating nor are they suitable for the provision of gravity domestic hot water The hot water cylinder and ancillary pipework not forming part of the useful heating surface should be lagged to prevent heat loss and any possible freezing particularly where pipes run through roof spaces and ventilated under floor spaces Boilers not fitted to a sealed system must be vented IMPORTANT A minimum lengt...

Страница 10: ...air gap and a MINIMUM depth of water below the static water level cold of 75mm 2 The static water level cold must be at least 200mm above the top of the horizontal flow pipe fitted as shown The vent connection MUST NOT be made immediately off the top of the boiler as venting is made less efficient 3 The maximum practical length of 15mm cold feed pipe should be used in order to reduce the effective...

Страница 11: ...covering at least the range 0 4 bar 0 60 lb in2 must be fitted to the system The gauge should be easily seen from the filling point and should preferably be connected at the same point as the expansion vessel 4 Expansion Vessel a A diaphragm type expansion vessel must be connected at a point close to the inlet side of the pump the connecting pipe being not less than 15mm 1 2 nominal size and not i...

Страница 12: ...n automatic air vent connected between them the stop valve being located between the system and the automatic air vent The stop valve may remain open during normal operation of the system if automatic water make up is required b Through a self contained unit comprising a cistern pressure booster pump if required and if necessary an automatic pressure reducing valve and flow restrictor The cistern ...

Страница 13: ... view LEGEND 24 30 27 35 9 12 19 37 26 23 17 Data Plate Condensate siphon trap cla7880 9 Sightglass 12 Main Burner 17 Gas Valve 19 Control Box 23 PCB25E 24 Air pressure switch 26 Controls Casing 27 Flue Protection Thermostat 30 Fan 35 Front Panel 37 Controls Door INSTALLATION ...

Страница 14: ...1 off 8 UNPACKING Pack A Contents A The complete boiler B Installation Servicing User s Instructions C Hardware Pack listed below Hardware Pack 1 Contents A Pipe Flue extension 1 off B Nut Siphon 1 off C Washer siphon sealing 1 off D O ring 1 off cla7863 C E D B A F D Wall mounting template E Wall mounting plate F 1 year guarantee form E Washer M4 Form C 3 off F No 14x2 slotted woodscrew 3 off G W...

Страница 15: ...sion ducts plus the standard flue duct may be used together 2 Flue extensions of greater than 1m 39 should be supported with the bracket provided 90o Elbow kit equivalent flue length resistance 1 5m 45o Elbow kit equivalent flue length resistance 1 0m 10 DETERMINING THE FLUE LENGTH Note A roof flue kit is available as an optional extra for vertical flue installation supplied with separate fitting ...

Страница 16: ...e wall mounting plate screw positions choose one from each group Note Mark the centre of the flue hole as well as the circumference b The position of the flue duct hole c The jacking screw fixing hole 4 Remove the template from the wall IMPORTANT Ensure that during the cutting operation masonry falling outside of the building does not cause damage or personal injury 1 Cut the flue hole preferably ...

Страница 17: ...he outer flue duct Refer to Frame 16 prior to fitting the flue ring Fit the boiler sealing ring inside the terminal B pack outer flue duct Ensure the boiler sealing ring is fully engaged Ensure the notch aligns with the label on the outer flue duct This ensures correct alignment of the flue terminal 6 Drill 3 holes 3 2mm 1 8 dia through the outer flue duct and boiler sealing ring Do NOT drill the ...

Страница 18: ...e the bottom packaging protection 3 Check the boiler alignment using a spirit level and adjust as necessary with the jacking screw 4 Line up the hole in the jacking screw with the hole in the wall previously drilled and secure with the No 14 x 50mm wood screw 19 CONNECTING THE FLUE TO THE BOILER A Without Optional Flue finishing Kit 1 Insert the flue assembly through the hole 2 Ensure the notch is...

Страница 19: ...rew with an 8mm 5 16 masonry drill 21 WALL MOUNTING TEMPLATE Note The template shows the positions for the fixing holes and the flue hole centres for standard installation If the flow and return pipes are to be routed down behind the boiler the downward routing pipe bracket supplied with the Downward Piping Kit must be used This bracket is secured to the wall and it is essential to use only those ...

Страница 20: ...re the tube is cut square mark the flue all the way round 4 Cut to length and remove any burrs 24 FITTING THE FLUE ASSEMBLY 1 Insert the flue assembly through the hole 2 Ensure the flue terminal is in the correct position 23 CUTTING THE FLUE For flue lengths 270 to 775mm ONLY 1 If downward routing of pipes is required then the downward routing wall bracket supplied in the downward piping kit shoul...

Страница 21: ... switch sensing pipe and CO CO2 sensing pipe 8 Lift the boiler onto the wall mounting bracket 9 Remove the bottom packaging protection 10 Check the boiler alignment to the wall using a spirit level and adjust as necessary with the jacking screw 11 Line up the hole in the jacking screw with the hole in the wall previously drilled and secure with the No 14x50mm wood screw 26 MOUNTING THE BOILER 27 C...

Страница 22: ...k the flue all the way around 6 De burr the cut edges 29 FLUE EXTENSION DUCTS continued 28 FLUE EXTENSION DUCTS For flue lengths greater than 705mm rear flue or 775mm side flue Flue duct support Wall plugs 2 off Washers 2 off Extension duct clamp 1 0m 39 long Support fixing screws 2 off Clamp screws 2 off mxhe7656 cla7868 R or L Flue length Accessories Product No R or L Up to 775 B Pack 1 off see ...

Страница 23: ...his is achieved by using either Flat roof weather collar or Universal weather collar ACCESSORIES Flue Duct Extension Kits are available for flue lengths extending beyond 1m These packs contain 1m extension ducts and may be cut to the desired length If the offset vertical option is used an elbow Kit is required For a full accessories list refer to page 6 Optional Extras and Frame 34 Flue Arrangemen...

Страница 24: ...ON 610 mm min ex7531 610 mm min ex7532 The terminal should be positioned so that products of combustion can safely disperse at all times Pluming may occur at the termination so where possible terminal positions where this could cause a nuisance should be avoided Minimum dimensions are shown below Terminal Position Minimum Dimension Directly below an opening air brick windows etc 300 mm Below plast...

Страница 25: ...to 7 5 Push fit the vertical connector E supplied separately into the boiler flue connection and retain with the four securing screws provided 6 Push fit extension duct F if required supplied separately and the roof flue kit assembly A into the vertical connector E 7 If the last extension duct requires cutting measure the distance outer ducts between the duct and the terminal and add 100 mm to thi...

Страница 26: ... 27 The routing of the drain must be made to allow a minimum fall of 1 in 20 away from the boiler throughout its length The drainage pipework must be arranged so that obstruction e g through freezing of external drainage pipes does not give rise to spillage within the dwelling IMPORTANT If excessive external pipework cannot be avoided a condensate removal pump available as an option and insulation...

Страница 27: ...roviding it can be confirmed that the down pipe is part of a combined waste and rain water system Make connection to SVP using a solvent welded saddle BOILER External wall Ground Level Termination to Soak away cla7774 minimum 500mm BOILER External wall Ground Level Open end of pipe direct into gulley below grating but above water level DRAIN cla7775 4 TERMINATION TO SOAKAWAY 5 TERMINATIONTODRAIN G...

Страница 28: ... O heat thermostat Thermostat sensor L br br L On Off switch ALL EARTHS must be connected Not all earths are shown for clarity Air pressure switch Flue protection thermostat cla7856 Combined spark sensing electrode Potentiometer L NTC NC N C NO P C B 25 GV 1 GV 2 FAN E Main gas Pilot gas Fan b b Connect to gy bk br or pk w y g N bk bk NO NC com bk bk r r y v 41 ELECTRICAL CONNECTIONS LEGEND b blue...

Страница 29: ...ufacturer 3 This is a fully controlled system set the boiler thermostat to maximum 4 Switchmaster Midi is similar in operation but the wiring differs slightly see the manufacturer s literature 43 PICTORIAL WIRING 44 MID POSITION VALVE Pumped only LEGEND b blue bk black br brown gy grey or orange pk pink r red v violet w white y yellow y g yellow green LEGEND b blue bk black br brown gy grey or ora...

Страница 30: ...e left off for more than a day or so then a frost thermostat should be wired into the system This is usually done at the programmer in which case the programme selector switches are set to OFF and all other controls MUST be left in the running position The frost thermostat should be sited in a cold place but where it can sense heat from the system Wiring should be as shown with minimal disturbance...

Страница 31: ...t button J 7 Switch the electricity supply ON and check that all external controls are calling for heat 48 INITIAL LIGHTING 8 Set the boiler thermostat knob D to position 6 and the boiler Mains On Off switch H to ON The fan will start After the fan has run for a few seconds the pilot solenoid valve should open and the intermittent spark commence continuing until the pilot is established The main b...

Страница 32: ...02 10 Stress the importance of regular servicing by a CORGI registered installer and that a comprehensive service should be carried out AT LEAST ONCE A YEAR In IE servicing work must be carried out by a Competent Person After completing the installation and commissioning of the system the installer should hand over to the householder by the following actions 51 HANDING OVER 50 GENERAL CHECKS Make ...

Страница 33: ...below and be repeated to ensure even clamping 1 Remove the screw retaining the front burner support strap to the combustion chamber Remove the M5 pozi situated at the LH bottom rear of the burner and pull the burner downwards to disengage the retention tab Remove the burner to a safe place for inspection and cleaning 2 Remove the 2 control box fixing screws Swing the box downwards to disengage 3 P...

Страница 34: ... is correct refer to Frame 67 Clean or renew as necessary Note The pilot shield is located around the pilot assembly bracket and is located by the electrode retaining nut 57 CLEANING THE RECUPERATOR 1 Remove the 2 rubber grommets to gain screwdriver access to remove the side tie rods retaining the combustion chamber and remove the tie rods Note the combustion chamber is also retained with 2 front ...

Страница 35: ...t seal Do NOT overtighten 5 Replace the boiler front panel Refer to Frame 49 59 REASSEMBLY 62 SIGHTGLASS REPLACEMENT Reassemble the boiler in the following order 1 Refit the flue baffles 2 Inspect the collector hood rope gasket and replace if necessary ensuring that the self adhesive rope is fitted centrally on to the lip of the collector hood fan assembly The boiler efficiency will be adversely a...

Страница 36: ...changer pocket and unclip from the casing 7 Remove the strain relief bush from the back panel base 8 Remove the sensor lead through the grommet in the control box 9 Replace and reassemble in reverse order ensuring the new cable strap is fitted and securing the thermistor harness On off switch 10 Disconnect the electrical connectors from the rear of the switch 11 Press in the 2 side retaining clips...

Страница 37: ... Check the spark gap 7 Reassemble in reverse order 8 Check the operation of the boiler 9 The pilot is factory set to maximum and no further adjustment is possible Ensure there is an inlet pressure of 20 mbar available Also check burner ignition and cross lighting 1 Refer to Frame 61 2 Remove the limit thermostat assembly from the boiler flow pipe 3 Disconnect the electrical connectors 4 Clip new t...

Страница 38: ...djustment sealing 1 Refer to Frame 61 2 Remove the burner and air box assembly Refer to Frame 54 3 Remove the electrode retaining nut 4 Remove the pilot shield 5 Remove the ignition electrode and integral lead 6 Refit the new electrode and lead in reverse order Ensure that the pilot shield is replaced 7 Check the spark gap Refer to Frame 67 8 Reassemble in reverse order 9 Check the operation of th...

Страница 39: ... electrical connections from the APS 5 Fit the new APS and reassemble in reverse order 6 Check the operation of the boiler 73 PRINTED CIRCUIT BOARD PCB REPLACEMENT 1 Refer to Frame 61 2 Remove the control box fixing screws and swing the control box down into the servicing position 3 Disconnect the detection lead from the PCB 4 Unplug all the Molex connectors from the PCB 74 COMBUSTION CHAMBER INSU...

Страница 40: ...Remove the fan collector hood assembly refer to Frame 55 Pull off the electrical connections from the overheat thermostat and pull off the white rubber tube from the siphon blockage sensing pipe 6 a Rear Flue Outlet Remove the two screws retaining the recuperator top section Pull the recuperator top section to release the flue pipe connection b Side Flue Outlet Remove the 3 screws retaining the to...

Страница 41: ...r sump connecting pipe and the blockage sensing pipe 5 Unscrew the siphon union connection 6 Remove the two siphon retaining screws and remove siphon 7 Re fit the new siphon and gasket and reassemble in reverse order ensuring the rubber sump connecting pipe and blockage sensing pipe are correctly replaced 8 Ensure the siphon is charged with water and the heat shield is replaced 4 6 5 3 SERVICING ...

Страница 42: ...y on the fan connector at PCB Molex marked FAN YES YES NO NO Check the polarity of the mains supply Check the continuity of the ignition lead from connector to electrode Does the spark now cease when gas is lit Ensure pilot and main gas valve leads are not crossed over Is there a supply voltage at pilot gas valve Is there a live supply on the red lead to the pressure switch NO Is there a regular s...

Страница 43: ...66 HE15 1 174 067 HE18 1 174 068 35 Front Panel Assembly Kit 1 174 069 37 Control Door Kit 1 173 572 39 Casing Seal and Screws Kit 1 174 070 45 E83 682 Overheat Thermostat LM7 Kit 1 171 950 59 E97 310 Limit Thermostat Kit 1 173 353 The following are parts commonly required due to damage or expendability Their failure or absence is likely to affect safety or performance of this appliance The list i...

Страница 44: ...44 Optia HE Installation Servicing SHORT LIST OF PARTS 78 SHORT PARTS LIST 12 30 35 19 9 24 17 18 23 FUSE 37 39 26 27 15 14 13 13 A 45 59 cla7873 ...

Страница 45: ...Local Authority Building Control LABC who will arrange an inspection or contact a government approved inspector LABC will record the data and will issue a certificate of compliance If you notify via CORGI Scheme CORGI will then notify the relevant Local Authority Building Control LABC scheme on members behalf Scheme members only Call CORGI on 0870 88 88 777 or log onto www corgi notify com within ...

Страница 46: ...WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED FOR THE DOMESTIC HOT WATER MODE MEASURE RECORD GAS RATE ft3 hr MAXIMUM BURNER OPERATING PRESSURE IF APPLICABLE mbar COLD WATER INLET TEMPERATURE o C HOT WATER OUTLET TEMPERATURE o C WATER FLOW RATE lts min FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH THE MANUFACTURER S INSTRUCTIONS YES FOR AL...

Страница 47: ...CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 5 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 6 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATUR...

Страница 48: ...Optia HE Installer Technical Helpline 0870 8498057 The code of practice for the installation commissioning servicing of central heating systems ...

Отзывы: