26
BOXER
combination boiler -
Installation and Servicing
INSTALLATION
36 GENERAL CHECKS
Make the following checks for correct operation in:
CENTRAL HEATING (CH) & DOMESTIC HOT WATER (DHW)
MODE.
1.
Ensure that the CH external controls are calling for heat,
and the CH adjustor is in middle position, the CH and flame
leds are On.
The display should read:
2.
Fully open a DHW tap and check that hot water is
delivered.
The CH led is Off,
and flame led is On.
3. Gas Rate
Check the boiler gas rate when the boiler is at full DHW
output.
The gas rate will normally be between:
22.2 to 46.8 litres per minute
0.8 to 1.6
cu/ft per minute
25.2 to 54.6 litres per minute
0.9 to 1.9
cu/ft per minute
checked at the gas meter, with no other appliance in use.
4.
Close the DHW tap. The burner should go off and the
pump continue to run.
The CH led is On.
After few seconds the burner should relight, to supply
central heating, if there is a request for it.
Make the following checks for correct operation in:
DOMESTIC HOT WATER (DHW) MODE
1.
With no call for CH or DHW the boiler is in stand-by mode.
Only the mains led is On.
2.
Fully open all DHW taps in turn and ensure that water
flows freely from them.
The flame led is On.
3.
Close all taps except the furthest one from the boiler and
check that the boiler is firing at maximum rate.
This is factory set to give a DHW temperature rise of
approximately 35
o
C at the following flow rate:
- 11.5 l/min for
BOXER C 28
- 10.0 l/min for
BOXER C 24
4.
Reduce the DHW draw-off rate to about 3 l/min (0.7 gpm)
and check that the boiler modulates to deliver DHW at
approximately 62
o
C.
5.
Close the DHW tap and check that the main burner
extinguishes.
The pump should overrun for a few seconds but the flame
led is Off immediately.
Note.
On systems in excess of 2 bar inlet pressure a water
pressure governor may be required to prevent water
noise.
BOXER C 24
BOXER C 28
INST
ALLA
TION