Valid from: 11/2013 – Rev.: UKW & BAKERY (13A)
Subject to technical changes
Page 4 from 4
Pre-defined parameter sets
Para-
meter
Description of function
Setting range
UKW
BAKERY
BAKERY
H
BAKERY
S
Parameter set (type of application)
0 … 5
0 0 0
0
Parameters of the
Level
Control circuit1
Para-
meter
Description of function
Setting range
UKW
BAKERY
BAKERY
H
BAKERY
S
Hysteresis 0,1...15,0°C
3,0°C 3,0°C
3,0°C
3,0°C
Fan control circuit 1
Para-
meter
Description of function
Setting range
UKW
BAKERY
BAKERY
H
BAKERY
S
Defrosting interval
0: no defrost
1...99 hours
3 hours
3 hours
3 hours
3 hours
Type of defrosting
0: no defrost
1:compressor of, air only
2: electrical
3: with hot gas
1
1
1
1
Stop at defrosting temperature
0 ... +30,0°C
7,0°C 7,0°C 7,0°C
7,0°C
Fan control circuit 1
Para-
meter
Description of function
Setting range
UKW
BAKERY
BAKERY
H
BAKERY
S
Fan speed control mode, Set1
0 ... 100%
65,0 45,0 55,0
55,0
Fan speed defrosting, Set1
0 ... 100%
80,0 45,0 80,0
80,0
Temperature sensors
Para-
meter
Description of function
Setting range
UKW
BAKERY
BAKERY
H
BAKERY
S
Calibration sensor F1
(act. value correction)
-20...+20,0°C
- 2,0°C
5,0°C
0,0°C
2,0°C
Actual value sensor F2 (sensor coil)
Measured value, not adjustable
Networking and display (password-protected)
Para-
meter
Description of function
Setting range
UKW
BAKERY
BAKERY
H
BAKERY
S
Display in standby mode
0: OFF
1: AUS
2: right
decimal
point
3: right
decimal
point
flashing
1
1
1
1