Installation requirements
Take the following requirements into consideration when installing the ICU
EVe:
The cable route of the main distributor to the ICU EVe must be
protected against power surges and short-circuits by using a B
characteristic circuit breaker or a screw gG tag fuse.
The cable route must be protected against accidental touching by a
type A or B 30 mA earth-leakage circuit breaker.
The cable route and charging point are a part of a TN-S system and
the earthing is provided from the main distributor.
The cable route must be laid in accordance with the applicable
standards such as, for example, IEC-60364.
The cable route consists of copper cable where 90°C is at least the
highest allowed conductive temperature.
Type
Protection
Option 1
Protection
Option 2
Min. Core
cross
section
2 x 16
A 1-
phase
3 x 35 A gG fuses + 40 A-
30 mA earth-leakage circuit
breaker
40 B
– 30 mA 2p earth-
leakage fuse
5 x 6mm
2
1 x 16
A 3-
phase
3 x 20 A gG fuses + 20 A-
30 mA earth-leakage circuit
breaker
20 B
– 30 mA 4p earth-
leakage fuse
5 x 4 mm
2
2 x 16
A 3-
phase
3 x 35 A gG fuses + 40 A-
30 mA earth-leakage circuit
breaker
40 B
– 30 mA 4p earth-
leakage fuse
5 x 6mm
2
1 x 32
A 3-
phase
3 x 35 A gG fuses + 40 A-
30 mA earth-leakage circuit
breaker
40 B
– 30 mA 4p earth-
leakage fuse
5 x 6mm
2
2 x 32
A 3-
phase
3 x 80 A gG fuses + 80 A-
30 mA earth-leakage circuit
breaker
3 x 80 B system fuse +
80 A-30 mA earth-
leakage circuit breaker
5 x 16 mm
2