OSDP Reader Connection
OSDP reader mode is only available for card readers with firmware version 1.04.277 or higher. Readers that only
support 125kHz reading and readers with PSK hardware
do not
support OSDP.
Connecting a card reader in OSDP mode is the same as the connection for standard RS-485 configuration.
Shield wires
connected
at the splice
Reader shield is
not terminated
inside the reader
Shield is frame
grounded at
one point
V+
V-
C
BZ
L2
L1
D1/
D0/
NB
NA
1
2
3
4
5
6
7
8
9
0
X
RED
BLACK
SHIELD
GREEN
WHITE
ORANGE
BROWN
BLUE
YELLOW
VIOLET
Shielded Cable
Readers must also be programmed to operate in OSDP mode. For more information, see
For more information about OSDP support on ICT card readers, including configuring readers for secure channel
communications, see
Application Note 321: Configuring ICT Readers for OSDP Communication
.
OSDP Baud Rate Requirement
For a card reader operating in OSDP mode to communicate with an OSDP server, the reader must have the same
baud rate setting as the reader port it is connected to. The default reader baud rate is 38400.
ICT card readers support the following baud rates:
Supported Baud Rates
4800 baud
9600 baud
19200 baud
38400 baud (default)
57600 baud
115200 baud
The card reader baud rate can be programmed using:
⦁
A mobile device running the Protege Config App
⦁
A correctly encoded MIFARE config card
A suitably configured MIFARE config card can be ordered from the ICT customer services team.
For detailed information on programming ICT card readers, see the
ICT Card Reader Configuration Guide
,
available from the ICT website.