The
Dial Attempts
option must be programmed. Refer to the section
Contact ID | Settings
in the
Operator Reference Manual.
⦁
DACT communication channel check-in time is not to exceed 24 hrs.
⦁
Trouble Zone Service Test Report
-
The
Test Report Time
must be programmed. Refer to the section
Controllers | Configuration
in the
Operator Reference Manual.
-
The
Generate Input Restore on Test Input
option must be enabled. Refer to the section
Controller |
Options
in the Operator Reference Manual.
-
The
Test Report Time is Periodic
option must be enabled. Refer to the section
Controller | Options
in
the Operator Reference Manual.
-
ArmorIP detects the reception of any invalid packet on the programmed port as a potential system
compromise attempt
. Each compromise attempt sends a notification to the receiver, and logs a
Compromise Attempt event under the Live Panel Events.
The event is sent with the following details:
◾
Account Code
as defined in the Serial Receiver settings
◾
Event Code
0x163
◾
Group Code
as defined in the Serial Receiver settings
◾
Point Code
as defined in the Serial Receiver settings
Refer to the section
Global Settings | Serial Receiver
in the ArmorIP Version 3 Internet Monitoring
Application User Manual.
For UL and ULC installations the Central Station Receiving software must have the Contact ID details as
specified, programmed for the
Compromise Attempt
event.
⦁
If a flexible cord is used to connect to line voltage, strain relief must be provided for the cord inside the
enclosure or at the knockout.
⦁
The power supply is not intended to be mounted on the exterior of vault, safe, or stockroom.