The

Report IP Service

must be enabled as the primary communication channel and the

Service Mode

must be configured to start with the operating system. The

Reporting Protocol

must be set to

ArmorIP, and the

Backup Service

must be configured to use the Contact ID Service.

-

Refer to the section

Report IP

in the Operator Reference Manual.

-

All ULC S304 P3 applications must transmit signals simultaneously over both the Contact ID Reporting
Service and the Report ID Service. This will occur automatically with the above programming.

Status Change Signal

An attempt to send a status change signal shall utilize both primary and secondary communication
channels.

Local Annunciation if Signal Reporting Failure

Failure of the primary communication channel or secondary communication channel shall result in a trouble
signal being transmitted to the signal receiving center within 240 seconds of the detection of the fault.
Failure of either communication channel shall be annunciated locally within 180 seconds of the fault.

The following options must be enabled in the Protege system:

-

The

Ethernet Link Failure

trouble input must be programmed.

-

The

Trouble Input Area

must be armed. Refer to the section

Trouble Inputs | Areas and Input Types

in

the Operator Reference Manual.

-

The

Log Modem Events to Event Buffer

option must be selected in the Contact ID Reporting Service.

Network and Domain Access

Neither the subscriber control unit nor the signal receiving center receiver shall be susceptible to security
breaches in general-purpose operating systems.

Network access policies should be set to restrict unauthorized network access and "spoofing" or "denial of
service" attacks.

Ethernet Connections

All ethernet network connections shall be installed within the same room as the equipment.

Encryption

For active communications channel security, encryption shall be enabled at all times.

The ArmorIP-E (UDP) protocol must be used and the Encryption Type must be set to AES-256.

The following options must be enabled for the Report IP service in the Protege system.

-

The

Reporting Protocol

must be set to ArmorIP (UDP) Encrypted. The AES key must be set as

specified by monitoring station.

-

Refer to the section

Report IP | General

in the Operator Reference Manual.

Server Configuration

Where a server is employed for control over network addressing, encryption or re-transmission, such shall
be designed to remain in the "on state" at all times.

Communicators are not suitable for active communication channel security and medium or high risk
applications unless such can be "online" at all times, have a minimum 128 bit encryption scheme, have
encryption enabled, network and domain security implemented.

Network access policies shall be set to restrict unauthorized network access and "spoofing" or "denial of
service" attacks.

Internet Service Provider (ISP)

The Internet Service Provider (ISP) providing service shall meet the following requirements:

-

redundant servers/systems

-

back-up power

-

routers with firewalls enabled and

-

methods to identify and protect against "Denial of Service" attacks (i.e. via "spoofing")

Information Technology Equipment, Products or Components of Products

Products or components of products, which perform communications functions only, shall comply with the
requirements applicable to communications equipment as specified in CAN/CSA-C22.2 No. 60950-1,
Information Technology Equipment Safety - Part 1: General Requirements. Where network interfaces, such

PRT-PSU-DIN-2A | Protege DIN Rail 2A Intelligent Power Supply | Installation Manual

38

Содержание PRT-PSU-DIN-2A

Страница 1: ...PRT PSU DIN 2A Protege DIN Rail 2A Intelligent Power Supply Installation Manual...

Страница 2: ...anical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Logo a...

Страница 3: ...olds 16 Encrypted Module Network 17 Module Wiring 18 End of Line EOL Resistors 18 Output Load Connection 19 Output Current Influence on Output Load Operation 19 Core Temperature on Output Load Operati...

Страница 4: ...imum Total Output Current UL and ULC Installations 32 New Zealand and Australia 33 European Standards 34 UL and ULC Installation Requirements 36 UL ULC Installation Cabinet Options 36 ULC Compliance R...

Страница 5: ...ure allows large numbers of modules to be connected to the RS 485 module network Up to 250 modules can be connected to the Protege system in any combination to the network over a distance of up to 900...

Страница 6: ...Alarm Systems CAN ULC S302 Installation and Classification of Burglar Alarm Systems for Financial and Commercial Premises Safes and Vaults CAN ULC S561 Installation and Services for Fire Signal Recei...

Страница 7: ...wire or wires of the appropriate gauge Earth Ground Connection The DIN rail enclosure and the DIN rail modules must be grounded to a suitable single point earth ground connection in the installation...

Страница 8: ...nk Connection DIN Rail Enclosure DIN Rail Enclosure DIN Rail Enclosure Module Network RS 485 N N NA and NB DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings Note th...

Страница 9: ...val A Protege DIN rail module can be removed from the DIN rail mount using the following steps 1 Insert a flat blade screwdriver into the hole in the module tab clip 2 Lever the tab outwards and rotat...

Страница 10: ...ion Terminals 1 V and 2 V 12V power connection reverse polarity protected Terminals 3 and 4 N C alarm output contacts with built in 10 ohm resistor in series 1 12V Screw terminal 1 2 0V Screw terminal...

Страница 11: ...OFF position allows adjustment in the low sensitivity area Installation Procedure 1 Select the intended position for installation ideally positioned horizontally in the vertical center of the enclosu...

Страница 12: ...rn sensitivity control anti clockwise and bang or tap the protected area Repeat this process until the unit only just responds to the desired impact 11 Replace the sensor cover tighten the fixing scre...

Страница 13: ...le Pleaserefer theSystemController InstallationManual for address programmingdetails LED Description Power Green Correctmoduleinputvoltageapplied Off Incorrectmoduleinputvoltageapplied Status Modulesu...

Страница 14: ...he electrical termination point inside the cabinet enclosure and the secondary wires of the transformer to the AC input on the power supply The earth wire shall be routed to the V terminal on the powe...

Страница 15: ...ren lock mag clamp etc An incorrect connection may cause erroneous faults or serious damage to the module and will VOID ALL WARRANTIES OR GUARANTEES The battery test procedure uses a special algorithm...

Страница 16: ...ection threshold is 8V Upon reconnection of mains power the power supply automatically detects the backup battery and begins controlled charging at 500mA typical PRT PSU DIN 2A Protege DIN Rail 2A Int...

Страница 17: ...power supply NA and NB terminals to the NA and NB terminals of the communication network Shield is frame grounded at one point Shields are connected together and Isolated Shielded Cable Network Modul...

Страница 18: ...stic impedance of 120 ohm Maximum total length of cable is 900m 3000ft CAT5e CAT6 are also supported for data transmission when using ground in the same cable to a maximum length of 100m 328ft Warning...

Страница 19: ...VDC OUTPUT 1 Power Supply Other Module 12VDC Electric Locking Device 12VDC Electric Locking Device IN4007 Diode V2 V V1 V 12VDC OUTPUT 2 12VDC OUTPUT 1 Note The 1N4007 diode shown must be installed ac...

Страница 20: ...0 C 70 80 C 80 C Outputs Enabled Mains Power Outputs Supplied by Battery Output Over Current Failure Trouble Input Activated Over Current Output Shutdown Activated PRT PSU DIN 2A Protege DIN Rail 2A I...

Страница 21: ...attery Battery Failure Power Fault General AExxx 04 Output Voltage Low Power Fault General AExxx 05 Output Over Current Failure Power Fault General AExxx 06 Core Temperature Over Temp Failure Power Fa...

Страница 22: ...k EMF voltages or large voltage induced spikes can cause the module to behave unexpectedly and should be avoided A suitable isolation circuit must be installed between the relay contacts of the module...

Страница 23: ...ge drops below 11 2V Upon reconnecting a backup battery with a voltage greater than 12 5V the output relay will revert back to its default state normally open Ensure common ground between devices Inpu...

Страница 24: ...for each power supply will monitor Channel 1 Voltage at V1 output Channel 2 Voltage at V2 output Channel 3 Battery voltage Channel 4 Total current output Each channel can be associated with a data va...

Страница 25: ...roduct Refer to the Protege system controller installation manual for address programming details The controller has a set limit on the number of modules of each type that it can support When adding a...

Страница 26: ...tor The fault indicator is lit any time the module is operating in non standard mode If the fault indicator is flashing the module requires a firmware update or is in firmware update mode When the fau...

Страница 27: ...green Mains has failed and the PSU is drawing power from the battery State is Battery Restore Temp Indicator The temp indicator will show the status of the unit s core temperature State Description On...

Страница 28: ...eature in the controller s web interface 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within the r...

Страница 29: ...m The mechanical diagram shown below outlines the essential details needed to help ensure the correct installation of the power supply PRT PSU DIN 2A Protege DIN Rail 2A Intelligent Power Supply Insta...

Страница 30: ...al details needed to help ensure correct installation and mounting All measurements are shown in millimeters 90 00 78 40 44 68 67 18 4 67 Screw Hole 39 20 39 20 78 40 17 55 35 40 Back Front PRT PSU DI...

Страница 31: ...o the 2A Combined DC Output Battery Low 11 75VDC Battery Restore 12 5VDC Electronic Disconnection 9 4VDC Communication RS 485 Isolated Module Network Inputs Tamper Dedicated Hardware Tamper Input Trou...

Страница 32: ...in Standby Maximum Charging Current Mains present Battery Rating UL 294 and CAN ULC S319 4hr backup 2000mA 240mA 350mA 2 x 12VDC 7Ah 14Ah CAN ULC S304 24hr backup 2000mA 180mA 350mA 2 x 12VDC 7Ah 14Ah...

Страница 33: ...neral Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards PRT PSU DIN 2A Protege DIN Rail 2A Intelligent Power S...

Страница 34: ...for further details of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with your national legislation For business users in the...

Страница 35: ...ontacts opening for a minimum of 1 second on detection of an alarm connected in series with the 24Hr tamper input TP on the PSU or any other system input designated programmed as a 24Hr Tamper Alarm T...

Страница 36: ...ion Listings EN DIN 12 UL294 UL1076 ULC ORD C1076 86 CAN ULC S319 EN DIN 31 EN DIN 24 EN DIN 24 ATTACK P UL ULC All cabinet installations of this type must be located inside the Protected Area Not to...

Страница 37: ...erence Manual The Poll Time must be programmed to 40 seconds Refer to the Report IP General section in the Operator Reference Manual Central Station Signal Receiver The common equipment of each signal...

Страница 38: ...attacks Ethernet Connections All ethernet network connections shall be installed within the same room as the equipment Encryption For active communications channel security encryption shall be enable...

Страница 39: ...d ULC installations the Central Station Receiving software must have the Contact ID details as specified programmed for the Compromise Attempt event Power Supply Mains Power Connection If a flexible c...

Страница 40: ...in the Operator Reference Manual In the ArmorIP Internet Monitoring Software the Poll Time must be set to 40 seconds and the Grace Time must be set to 20 seconds Refer to the section Poll Grace Time i...

Страница 41: ...outside it must be rated for outdoor use Keypad Wiring The RS 485 connection to the keypad must be wired such that the shorts and other faults on the RS 485 line connection of the keypad will not caus...

Страница 42: ...losee4Tampere4Short ofK ofK Opene4vlosee4Tampere4Short lKl lKl Opene4vlosee4Tampere4Short K lKl Opene4vlosee4Tampere4Short K K Opene4vlosee4Tampere4Short p UXq Zo vOM vOM Zl Zm Z Niv Tamper Niv4Input4...

Страница 43: ...ut Configuration uEOL4resistor4must4be4installed4at4the4Fire4 larm4vontrol4Panel4Outputi u4Fire4areas4shall4be4separated4from4burglar4areas4through4area4partitioningi u4Fire4Inputs4ZoqZm4shall4be4used...

Страница 44: ...ent both transmission lines onboard modem and IP reporting must be enabled Signals shall be sent simultaneously to both Report IP Service and Contact ID Reporting Service The Report IP and Contact ID...

Страница 45: ...promise Attempt event under the Live Panel Events The event is sent with the following details Account Code as defined in the Serial Receiver settings Event Code 0x163 Group Code as defined in the Ser...

Страница 46: ...OUT If a flexible cord is used to connect to line voltage strain relief must be provided for the cord inside the enclosure or at the knockout The power supply is not intended to be mounted on the ext...

Страница 47: ...evice may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHANGES...

Страница 48: ...S 003 This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations CAN ICES 3 A NMB 3 A PRT PSU DIN 2A Protege DIN Rail 2A Intelligent Power...

Страница 49: ...liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design and...

Страница 50: ...eserved Disclaimer Whilst every effort has been made to ensure accuracy in the representation of this product neither Integrated Control Technology Ltd nor its employees shall be liable under any circ...

Отзывы: