Wiring Diagram

Wiring

AUX WIRING: Min 22AWG Max 16AWG. (Depends on 
length and Current consumption). For wire/cable size, 
a maximum of 5% voltage drop at the terminals of 
the powered device has to be observed.

MODULE NETWORK WIRING: Recommended Belden 
9842 or equivalent. (24AWG twisted pair with 
characteristic impedance of 120ohm or CAT5e / CAT6 
are also supported for Data Transmission when using 
ground in the same cable. Do not use extra wires to 
power devices.) max 900m (3000ft).

Battery Characteristics

Battery Type to be used: VRLA (valve regulated sealed 
lead acid type rechargeable battery)

Recommended Battery: Yuasa model: 
NP7-12, 12V,7Ah (www.yuasabatteries.com)

Nominal Voltage: 12V

Nominal Capacity: 7Ah

Battery Maintenance: It is recommended to replace 
the battery every 3-5 years.

NC

C

N0

C

TP

V+

V

-

Z1

C

Z2

Z3

C

Z4

Input Expander

2A Power Supply

AC Fail Connection

Ensure common ground between devices

NC

C

NO

C

TP

V+

V

-

Z1

C

Z2

Z3

C

Z4

Battery Fail Connection

Ensure common ground between devices

Input Expander

2A Power Supply

Until connection to any System Controller is established, the outputs operate in 
Offline Mode. While in offline mode, the 2 outputs function as status outputs.

AC Fail Status Output:
The output relay contacts 
disconnect (Normally Open) 
when AC power is removed 
and unit remains running on 
backup battery power. Upon 
restoring AC power, the output 
relay will revert back to its 
default state
(Normally Closed).

Outputs - Offline Mode

Battery Fail Status Output:

The output relay contacts 
connects (Normally Closed) 
when either the backup battery 
has been disconnected, or 
when the Power Supply is 
running on backup battery 
power without AC power and 
the backup battery voltage 
drops below 11.75V. Upon 
reconnecting a backup battery 
with a voltage greater than 
12.5V, the output relay will 
revert back to its default state 
(Normally Open).

The outputs are shown to be connected to a DIN Rail 16 Input Expander 
so the statuses can be externally monitored.

The address of the 2A Intelligent Power Supply is 
configured via programming and will require reference 
to the module serial number. The serial number can be 
found on the identification sticker on the side of the
module. 

Please refer the System Controller Installation Manual for 
address programming details. 

LED

Description

Power

Green

Correct module input voltage applied.

Off

Incorrect module input voltage applied.

Status

Module successfully registered with controller.

Module attempting registration with controller

Module communication activity.

Fault

Red

ON and OFF rapidly with a delay of 1.5 second between each display cycle.

Number of Flashes

Error Description

1

Unknown Error Code

2

Firmware Version

3

Address Too High

4

Address in Use

5

Controller Secured

6

Serial Number Fault

7

Locked Device

For further details, please refer to the Error Code Display section in the Installation Manual.

V1 Out /

V2 Out

Green

12VDC output operating OK.

Off

12VDC output failure.

Battery

Off

Backup battery is disconnected/failed its dynamic battery test.

Green

Last backup battery dynamic test successful.

Temp

Red

Core temperature exceeded. Over Temp Shutdown Activated.

Core temperature within 15°C of Over Temp Shutdown.

Off

Core temperature OK.

Over

Current

Red

Output current exceeded. Over Current Shutdown Activated.

Off

Maximum output current not exceeded.

Outputs - Online Mode

Upon successfully completing the initial 
registration with any System Controller, the 
outputs operate in Online Mode. While in 
online mode, the 2 outputs function as PGMs
and can be used to activate bell sirens, 
lighting circuits, door locks, relay accessory 
products and other automation points.

NC

C

NC

C

TP

1K5 OHM

LED

Output Connection

V2+

V-

V1+

V-

CAUTION: INCORRECT 
WIRING MAY RESULT 
IN DAMAGE TO THE 
UNIT

Devices connected to other Modules

Inductive devices (such as electric locking 
devices, solenoids, etc) connected to other 
modules require a 1N4007 diode to be fitted as 
close to the device as possible.

+

-

1N4007 Diode

12VDC Electric

Locking Device

NA

N+

N-

NB

System Controller

The 2A Intelligent Power Supply 
should be supplied by a dedicated 
electrical power source rated for a 
minimum 10Amp load and have a 
dedicated circuit breaker. Do not use 
a switch controlled breaker or 
switched electrical point to supply 
power.

Next 
modules 
on network

NA

N+

N-

NB

White

Blue

Black

Red

Gel Cell
Backup
Battery 
(Min 7Ah)

Tamper
Switch

B

ra

ck

et

Gel Cell
Backup
Battery 
(Min 7Ah)

Transformer 
secondary 16 
to 16.5VAC, 
50-60Hz 40VA 
and greater

ULC-LA AC 
Indicator*

Inline 
5A 3AG 
fuseholder* 

+

2A Power Supply

PRT-PSU-DIN-2A | Protege DIN Rail 2A Intelligent Power Supply | Installation Manual

13

Содержание PRT-PSU-DIN-2A

Страница 1: ...PRT PSU DIN 2A Protege DIN Rail 2A Intelligent Power Supply Installation Manual...

Страница 2: ...anical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Logo a...

Страница 3: ...olds 16 Encrypted Module Network 17 Module Wiring 18 End of Line EOL Resistors 18 Output Load Connection 19 Output Current Influence on Output Load Operation 19 Core Temperature on Output Load Operati...

Страница 4: ...imum Total Output Current UL and ULC Installations 32 New Zealand and Australia 33 European Standards 34 UL and ULC Installation Requirements 36 UL ULC Installation Cabinet Options 36 ULC Compliance R...

Страница 5: ...ure allows large numbers of modules to be connected to the RS 485 module network Up to 250 modules can be connected to the Protege system in any combination to the network over a distance of up to 900...

Страница 6: ...Alarm Systems CAN ULC S302 Installation and Classification of Burglar Alarm Systems for Financial and Commercial Premises Safes and Vaults CAN ULC S561 Installation and Services for Fire Signal Recei...

Страница 7: ...wire or wires of the appropriate gauge Earth Ground Connection The DIN rail enclosure and the DIN rail modules must be grounded to a suitable single point earth ground connection in the installation...

Страница 8: ...nk Connection DIN Rail Enclosure DIN Rail Enclosure DIN Rail Enclosure Module Network RS 485 N N NA and NB DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings Note th...

Страница 9: ...val A Protege DIN rail module can be removed from the DIN rail mount using the following steps 1 Insert a flat blade screwdriver into the hole in the module tab clip 2 Lever the tab outwards and rotat...

Страница 10: ...ion Terminals 1 V and 2 V 12V power connection reverse polarity protected Terminals 3 and 4 N C alarm output contacts with built in 10 ohm resistor in series 1 12V Screw terminal 1 2 0V Screw terminal...

Страница 11: ...OFF position allows adjustment in the low sensitivity area Installation Procedure 1 Select the intended position for installation ideally positioned horizontally in the vertical center of the enclosu...

Страница 12: ...rn sensitivity control anti clockwise and bang or tap the protected area Repeat this process until the unit only just responds to the desired impact 11 Replace the sensor cover tighten the fixing scre...

Страница 13: ...le Pleaserefer theSystemController InstallationManual for address programmingdetails LED Description Power Green Correctmoduleinputvoltageapplied Off Incorrectmoduleinputvoltageapplied Status Modulesu...

Страница 14: ...he electrical termination point inside the cabinet enclosure and the secondary wires of the transformer to the AC input on the power supply The earth wire shall be routed to the V terminal on the powe...

Страница 15: ...ren lock mag clamp etc An incorrect connection may cause erroneous faults or serious damage to the module and will VOID ALL WARRANTIES OR GUARANTEES The battery test procedure uses a special algorithm...

Страница 16: ...ection threshold is 8V Upon reconnection of mains power the power supply automatically detects the backup battery and begins controlled charging at 500mA typical PRT PSU DIN 2A Protege DIN Rail 2A Int...

Страница 17: ...power supply NA and NB terminals to the NA and NB terminals of the communication network Shield is frame grounded at one point Shields are connected together and Isolated Shielded Cable Network Modul...

Страница 18: ...stic impedance of 120 ohm Maximum total length of cable is 900m 3000ft CAT5e CAT6 are also supported for data transmission when using ground in the same cable to a maximum length of 100m 328ft Warning...

Страница 19: ...VDC OUTPUT 1 Power Supply Other Module 12VDC Electric Locking Device 12VDC Electric Locking Device IN4007 Diode V2 V V1 V 12VDC OUTPUT 2 12VDC OUTPUT 1 Note The 1N4007 diode shown must be installed ac...

Страница 20: ...0 C 70 80 C 80 C Outputs Enabled Mains Power Outputs Supplied by Battery Output Over Current Failure Trouble Input Activated Over Current Output Shutdown Activated PRT PSU DIN 2A Protege DIN Rail 2A I...

Страница 21: ...attery Battery Failure Power Fault General AExxx 04 Output Voltage Low Power Fault General AExxx 05 Output Over Current Failure Power Fault General AExxx 06 Core Temperature Over Temp Failure Power Fa...

Страница 22: ...k EMF voltages or large voltage induced spikes can cause the module to behave unexpectedly and should be avoided A suitable isolation circuit must be installed between the relay contacts of the module...

Страница 23: ...ge drops below 11 2V Upon reconnecting a backup battery with a voltage greater than 12 5V the output relay will revert back to its default state normally open Ensure common ground between devices Inpu...

Страница 24: ...for each power supply will monitor Channel 1 Voltage at V1 output Channel 2 Voltage at V2 output Channel 3 Battery voltage Channel 4 Total current output Each channel can be associated with a data va...

Страница 25: ...roduct Refer to the Protege system controller installation manual for address programming details The controller has a set limit on the number of modules of each type that it can support When adding a...

Страница 26: ...tor The fault indicator is lit any time the module is operating in non standard mode If the fault indicator is flashing the module requires a firmware update or is in firmware update mode When the fau...

Страница 27: ...green Mains has failed and the PSU is drawing power from the battery State is Battery Restore Temp Indicator The temp indicator will show the status of the unit s core temperature State Description On...

Страница 28: ...eature in the controller s web interface 3 Address Too High The module address is above the maximum number available on the system controller To clear this error change the address to one within the r...

Страница 29: ...m The mechanical diagram shown below outlines the essential details needed to help ensure the correct installation of the power supply PRT PSU DIN 2A Protege DIN Rail 2A Intelligent Power Supply Insta...

Страница 30: ...al details needed to help ensure correct installation and mounting All measurements are shown in millimeters 90 00 78 40 44 68 67 18 4 67 Screw Hole 39 20 39 20 78 40 17 55 35 40 Back Front PRT PSU DI...

Страница 31: ...o the 2A Combined DC Output Battery Low 11 75VDC Battery Restore 12 5VDC Electronic Disconnection 9 4VDC Communication RS 485 Isolated Module Network Inputs Tamper Dedicated Hardware Tamper Input Trou...

Страница 32: ...in Standby Maximum Charging Current Mains present Battery Rating UL 294 and CAN ULC S319 4hr backup 2000mA 240mA 350mA 2 x 12VDC 7Ah 14Ah CAN ULC S304 24hr backup 2000mA 180mA 350mA 2 x 12VDC 7Ah 14Ah...

Страница 33: ...neral Product Statement The RCM compliance label indicates that the supplier of the device asserts that it complies with all applicable standards PRT PSU DIN 2A Protege DIN Rail 2A Intelligent Power S...

Страница 34: ...for further details of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with your national legislation For business users in the...

Страница 35: ...ontacts opening for a minimum of 1 second on detection of an alarm connected in series with the 24Hr tamper input TP on the PSU or any other system input designated programmed as a 24Hr Tamper Alarm T...

Страница 36: ...ion Listings EN DIN 12 UL294 UL1076 ULC ORD C1076 86 CAN ULC S319 EN DIN 31 EN DIN 24 EN DIN 24 ATTACK P UL ULC All cabinet installations of this type must be located inside the Protected Area Not to...

Страница 37: ...erence Manual The Poll Time must be programmed to 40 seconds Refer to the Report IP General section in the Operator Reference Manual Central Station Signal Receiver The common equipment of each signal...

Страница 38: ...attacks Ethernet Connections All ethernet network connections shall be installed within the same room as the equipment Encryption For active communications channel security encryption shall be enable...

Страница 39: ...d ULC installations the Central Station Receiving software must have the Contact ID details as specified programmed for the Compromise Attempt event Power Supply Mains Power Connection If a flexible c...

Страница 40: ...in the Operator Reference Manual In the ArmorIP Internet Monitoring Software the Poll Time must be set to 40 seconds and the Grace Time must be set to 20 seconds Refer to the section Poll Grace Time i...

Страница 41: ...outside it must be rated for outdoor use Keypad Wiring The RS 485 connection to the keypad must be wired such that the shorts and other faults on the RS 485 line connection of the keypad will not caus...

Страница 42: ...losee4Tampere4Short ofK ofK Opene4vlosee4Tampere4Short lKl lKl Opene4vlosee4Tampere4Short K lKl Opene4vlosee4Tampere4Short K K Opene4vlosee4Tampere4Short p UXq Zo vOM vOM Zl Zm Z Niv Tamper Niv4Input4...

Страница 43: ...ut Configuration uEOL4resistor4must4be4installed4at4the4Fire4 larm4vontrol4Panel4Outputi u4Fire4areas4shall4be4separated4from4burglar4areas4through4area4partitioningi u4Fire4Inputs4ZoqZm4shall4be4used...

Страница 44: ...ent both transmission lines onboard modem and IP reporting must be enabled Signals shall be sent simultaneously to both Report IP Service and Contact ID Reporting Service The Report IP and Contact ID...

Страница 45: ...promise Attempt event under the Live Panel Events The event is sent with the following details Account Code as defined in the Serial Receiver settings Event Code 0x163 Group Code as defined in the Ser...

Страница 46: ...OUT If a flexible cord is used to connect to line voltage strain relief must be provided for the cord inside the enclosure or at the knockout The power supply is not intended to be mounted on the ext...

Страница 47: ...evice may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHANGES...

Страница 48: ...S 003 This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations CAN ICES 3 A NMB 3 A PRT PSU DIN 2A Protege DIN Rail 2A Intelligent Power...

Страница 49: ...liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design and...

Страница 50: ...eserved Disclaimer Whilst every effort has been made to ensure accuracy in the representation of this product neither Integrated Control Technology Ltd nor its employees shall be liable under any circ...

Отзывы: