Zone 1 (1+2)

Common

Zone 2 (3+4)

N.C Tamper

N.C Tamper

Zone 2

N.C Zone Contact

Zone 1

N.C Zone Contact

1K

1K

1K

1K

Z2

P1

Z1

NB

+

NA

-

 

Zone Input (1K and 1K) 

Zone 1 (1+2)

Common

Zone 2 (3+4)

N.C Tamper

N.C Tamper

Zone 3

N.C Zone Contact

Zone 1

N.C Zone Contact

Zone 2

N.C Zone Contact

1K

1K

2K4

2K4

Z2

P1

Z1

NB

+

NA

-

Zone 4

N.C Zone Contact

 

Zone Input Duplex Mode (1K and 2K4) 

To utilize the zone input duplex mode configuration shown above, 
the zone input duplex setting under the Keypad General Options 
must be enabled. 

 

6. Outputs 

The keypad has 4 programmable outputs (PGMs). These PGMs are 
used to control the 3 system status LED indicators, system beeper 
and the open collector output. The PGMs can be activated and 
deactivated based on specific events or functions within the Protege 
System. 

 

PGM 

Function 

KPXXX:01 

Open Collector Output on the Touch Sense Keypad terminal 
block (P1). 

KPXXX:02 

Disarmed Status Indicator LED (Green) 

KPXXX:03 

Armed Status Indicator LED (Red) 

KPXXX:04 

Beeper Output 

 

 

7. Trouble Inputs 

Trouble zones are used to monitor the status of the keypad and in 
most cases are not physically connected to an external zone. The 
following table details the trouble zones that are configured in the 
system. 

 

Trouble Zone 

Function 

KPXXX:01 

Module Tamper. Opens when the keypad is removed 
from the wall. 

KPXXX:02 

Reserved. 

KPXXX:03 

Keypad Panic. Keys 1 and 3 are pressed together 
generating a panic message. 

KPXXX:04 

Keypad Duress. A user code with the duress option 
enabled has entered a code on the keypad. 

KPXXX:05 

Reserved. 

KPXXX:06 

Reserved. 

KPXXX:07 

Too Many Codes. Too many incorrect codes have been 
entered at the keypad and it has been locked out for the 
set programmable lockout time. 

KPXXX:08 

Module Offline. The keypad has either been removed 
from the system or lost communications. 

 

 

8. Error Messages 

When the keypad attempts to register or communicate with the 
system controller after powering up, errors can be generated 
indicating access to the Protege System has been denied or 
unsuccessful. This is a normal part of the Protege System. 

 

Keypad Version Error 

The version of the keypad is incorrect for the system controller. This 
error cannot be corrected without updating the keypad firmware. 
The event log in the system controller will display the version of the 
keypad and the version that is required if this error has occurred. 
Please contact your distributor for information on how to update the 
firmware. 

 

Keypad Address Too High 

The address of the keypad that is programmed is beyond the 
maximum number of keypads that are allowed to connect to the 
system controller. You may also be able to adjust the controller 
profile to increase the keypad module capacity. Press the 

 key to 

restart the keypad. Refer to the 

Configuration 

section and set the 

keypad address to a lower value. 

 

Duplicate Keypad Address 

The address of the keypad is already programmed into the system 
controller. Press the 

  key to restart the keypad and refer to the 

Configuration 

section to set the keypad address to a free address. 

 

Security Violation 

The system controller has security enabled and devices cannot be 
added to the Protege System. Remove the security setting for the 
system controller then press the 

  key to restart the keypad. 

 

Invalid Serial Number 

The keypad has an invalid serial number programmed and cannot 
be registered on the Protege System. Return the keypad to your 
distributor. This error cannot be corrected without updating the 
keypad firmware. 

 

9. Technical Specifications 

 

Operating Voltage 

11.0VDC to 14VDC 

Operating Current 

60mA (95mA Max) 

User Interface Display 

Energy smart backlit LCD 16x 2 alphanumeric 
display with enhanced viewing angle 

User Interface Keypad 

Combined 23 key capacitive touch keypad with 3 
system status LEDs 

Inputs 

2 standard or 4 using Zone Input Duplex mode 

Outputs 

1 open collector (50mA Max) output. Programmable 
for all output functions. 

3 system status LEDs 

1 system beeper 

Operating Temperature 

0˚ to 49˚C (32˚ to 122˚F) 

Storage Temperature 

-10˚ to 85˚C (14˚ to 185˚F) 

Humidity 

0% to 93% non condensing, indoor use only 
(relative humidity) 

Dimensions 

125 x 125 x 18mm (4.92 x 4.92 x 0.71”) 

Weight 

192g (6.77oz) 

The size of conductor used for the supply of power to the Protege Touch Sense 
LCD Keypad should be adequate in size to prevent voltage drop at the power 
terminals of no more than 5% of the rated supply voltage. Specifications are 
subject to change without notice, please visit www.incontrol.co.nz for updated 
information. 

 

 

 

 

 

 

 

 

Integrated Control Technology Limited 

11 Canaveral Drive, Albany, North Shore City 0632, Auckland, New Zealand 

P.O. Box 302-340, North Harbour, Auckland, New Zealand 

Phone: +64 (9) 476 7124 

Fax: +64 (9) 476 7128 

Email: [email protected] 

www.incontrol.co.nz 

Designers and manufacturers of integrated electronic access control, security and building 

automation products. 

Designed and manufactured by Integrated Control Technology Limited. 

© Copyright Integrated Control Technology Limited 2003-2011. All rights reserved. 

227-4285-200

 

Отзывы: