PRT-CTRL-DIN-1D

Protege GX DIN Rail Single Door Controller

Installation Manual

Содержание Protege GX PRT-CTRL-DIN

Страница 1: ...PRT CTRL DIN 1D Protege GX DIN Rail Single Door Controller Installation Manual...

Страница 2: ...anical for any purpose without the express written permission of Integrated Control Technology Limited Designed and manufactured by Integrated Control Technology Limited Protege and the Protege Logo a...

Страница 3: ...tors 15 Backup Battery 15 Ethernet 10 100 Network Interface 16 Configuration 17 Configuring a Controller via the Web Interface 17 Home Page 17 System Settings 17 Operators 19 Application Software 19 C...

Страница 4: ...32 Hardware Configuration 33 Temporarily Defaulting the IP Address 33 Defaulting a Controller 34 LED Indicators 36 Power Indicator 36 Status Indicator 36 Fault Indicator 36 PoE Power Indicator 36 Batt...

Страница 5: ...y 43 Recommended Routine Maintenance Procedures 44 European Standards 48 FCC Compliance Statements 50 Industry Canada Statement 51 Disclaimer and Warranty 52 PRT CTRL DIN 1D Protege GX DIN Rail Single...

Страница 6: ...cted to the Protege system in any combination to the network over a distance of up to 900M 3000ft Further span can be achieved with the use of a network repeater module The current features of the Con...

Страница 7: ...t is to be installed in accordance with The product installation instructions AS NZS 2201 1 Intruder alarm systems The Local Authority Having Jurisdiction AHJ PRT CTRL DIN 1D Protege GX DIN Rail Singl...

Страница 8: ...r wire or wires of the appropriate gauge Earth Ground Connection The DIN Rail enclosure and the DIN Rail modules must be grounded to a suitable single point earth ground connection in the installation...

Страница 9: ...nk Connection DIN Rail Enclosure DIN Rail Enclosure DIN Rail Enclosure Module Network RS 485 N N NA and NB DIN Rail Ground Connections multiple cabinets in different rooms sectors or buildings Note th...

Страница 10: ...n electrical room communication equipment room closet or in an accessible area of the ceiling 1 Position the DIN Rail module in the correct orientation with the writing on the face the right way up 2...

Страница 11: ...tery is connected may cause serious damage to the unit and will VOID ALL WARRANTIES OR GUARANTEES Power the unit only after all wiring configuration and jumper settings are completed A battery backup...

Страница 12: ...n several supplies To comply with EN 50131 1 only one battery can be connected and monitored per system If more capacity is required a single larger battery must be used Example Multiple PSU Connectio...

Страница 13: ...EE 802 3at 25 5W Deliverable When using a PoE Router as the power source to the controller the N and N terminals become the network outputs that can be used for powering the module network The auxilia...

Страница 14: ...at only one end of the cable DO NOT connect a shield at both ends The 12V N and N Communication input must be supplied from only ONE point Connections from more than one 12V supply may cause failure...

Страница 15: ...resettable fuse to open requiring resetting by removal of all connections to the B and B plugs for approximately 30 seconds Single Door Controller with PoE BatteryConnection Warning Only attach stand...

Страница 16: ...ured using an LCD Keypad terminal or via the built in web interface The default IP address is set to a static IP address of 192 168 1 2 with a subnet mask of 255 255 255 0 These IP address settings ar...

Страница 17: ...s Health Displays the Health Status of the controller This is the same as the information displayed by the Get Health Status function in the Protege GX software Voltage Shows the voltage passing throu...

Страница 18: ...ccessible via an external hostname it can be entered here This is only required if the DDNS or HTTPS options below are being used Dynamic DNS Enable DDNS The controller has an in built DDNS Dynamic Do...

Страница 19: ...Version Displays the current firmware version of this controller Click on this field to display further version information Update Application Software BIN File This section is used to update the fir...

Страница 20: ...keypad 1 Connect the keypad to the module network 2 Log in to the keypad using any valid Installer code The default Installer code is 000000 If the default code has been overridden and you do not know...

Страница 21: ...er hardware have 16 onboard inputs Outputs The Single Door 1D Controller has 1 onboard output By default the number of outputs is set to 4 for compatibility with older Controller hardware and should b...

Страница 22: ...name containing all doors and an access level containing this door group Copy Global Records When enabled copies the global records that are relevant to the original Controller Configuring a Controll...

Страница 23: ...tor frequently This setting is only relevant to older hardware which is supplied by an AC power source Module UDP Port This is the UDP port that all Ethernet enabled modules will communicate with the...

Страница 24: ...these things will result in the time being inaccurate Controllers Custom Reader Format Settings Custom Reader Configuration Custom Reader Type Defines the reader type The data can be output as Wiegand...

Страница 25: ...sful or not open the Auto addressing window in the software by right clicking on the Controller and selecting Module Addressing 5 If the address can be changed electronically this is indicated in the...

Страница 26: ...th the Protege system such as tSec Standard Readers tSec Mini Readers etc RS 485 Reader Locations As two RS 485 readers can be connected to the same RS 485 reader port the configuration of the green a...

Страница 27: ...hield not connected SB SA S S Z2 V Z1 NC C NO RS 485 NETWORK 12VDC OUT INPUT 2 INPUT 1 RELAY 1 VIOLET VIOLET ENTRY EXIT 1 2 3 4 5 6 7 8 9 0 X The exit reader has the green and orange wires connected t...

Страница 28: ...EX Input Port 1 When connected the REX input can be programmed to operate regardless of the door contact state The REX input can also be programmed to recycle the door alarm time to prevent nuisance a...

Страница 29: ...X respectively Any inputs that are not configured for used with the onboard reader may be used as general purpose inputs If the onboard reader is enabled and you wish to use one as a general input you...

Страница 30: ...put Configuration Inputs 1 and 2 can operate as either general purpose inputs or as onboard reader inputs If used as general purpose inputs you must ensure that they are not defined in the onboard rea...

Страница 31: ...d by the trouble input when it is activated Input Number Description Type Group CP001 02 12V supply failure Power Fault General CP001 04 Real Time Clock Not Set RTC Clock Loss General CP001 05 Service...

Страница 32: ...y closed contacts This output can be used to activate larger relays sounders lights locks etc Example Relay Connection Warning The Relay outputs can switch to a maximum capacity of 7A Exceeding this a...

Страница 33: ...1 Remove power to the Controller by disconnecting the 12V DC input 2 Wait until the power indicator is off 3 Connect a wire link between NA of the module network and SA of the reader network and betw...

Страница 34: ...be set back to the factory default which resets all internal data and event information This allows you to remove all programming and start afresh Defaulting a One Door Controller 1 Remove power to t...

Страница 35: ...ith all programming and settings returned to factory configuration Defaulting the Controller does not reset the IP address Refer to Configuring the IP Address for instructions on how to reset the addr...

Страница 36: ...plied Status Indicator The Status indicator displays the status of the Controller State Description Flashing green at 1 second intervals The Controller is operating normally Fault Indicator The Fault...

Страница 37: ...he status of the Ethernet connection State Description On green Valid link with a hub switch or direct connection to a personal computer detected Flashing green Data is being received or transmitted O...

Страница 38: ...erification of inputs without the need to view the inputs from the keypad or the Protege software State Description Constantly off Input is not programmed Constantly on red Input is in an OPEN state C...

Страница 39: ...am The mechanical diagram shown below outlines the essential details needed to help ensure the correct installation of the Controller PRT CTRL DIN 1D Protege GX DIN Rail Single Door Controller Install...

Страница 40: ...ut The mechanical layout shown below outlines the essential details needed to help ensure the correct installation of the Controller PRT CTRL DIN 1D Protege GX DIN Rail Single Door Controller Installa...

Страница 41: ...attery charging PoE Electronic Disconnection 9 0VDC Battery Battery Charging 300mA typical Battery Low 11 2VDC Battery Restore 12 5VDC Communications Communication Ethernet 10 100Mbps Ethernet communi...

Страница 42: ...uses The ICT implementation of OSDP conforms to a subset of the OSDP functionality For specifications and reader configuration refer to AN 254 Configuring OSDP Readers available from the Integrated Co...

Страница 43: ...s described below this may not meet the routine maintenance procedures recommended for those devices As a minimum we recommend that you follow the AS NZS 2201 1 2007 standards relating to Detection de...

Страница 44: ...ies Check wiring and cable protection Once per year Visually inspect all wiring and cable protection systems conduits trunking etc Record any damage or deterioration Check for dust moisture and vermin...

Страница 45: ...keypad display Once per year Check the operation of the keypad display to ensure that all characters display correctly on the screen and that the backlight is operational and at the correct brightness...

Страница 46: ...n monitoring company and client but not less than once per year May be performed alongside Input Testing above Note This procedure must be pre arranged in consultation with the monitoring station Test...

Страница 47: ...tem resulting from the maintenance procedures Record these in the maintenance sheets and report Obtain client sign off At the conclusion of each maintenance visit Obtain the signature of the client or...

Страница 48: ...handling Please contact your local authority for further details of your nearest designated collection point Penalties may be applicable for incorrect disposal of this waste in accordance with your na...

Страница 49: ...or per input Do not mix unpowered detectors and non latching powered detectors on an input To comply with EN 50131 1 the Entry Timer should not be programmed to more than 45 seconds To comply with EN...

Страница 50: ...device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation NOTE THE GRANTEE IS NOT RESPONSIBLE FOR ANY CHANGE...

Страница 51: ...S 003 This is a Class A digital device that meets all requirements of the Canadian Interference Causing Equipment Regulations CAN ICES 3 A NMB 3 A PRT CTRL DIN 1D Protege GX DIN Rail Single Door Contr...

Страница 52: ...liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information In accordance with the ICT policy of enhanced development design and...

Страница 53: ...igners manufacturers of integrated electronic access control security and automation products Designed manufactured by Integrated Control Technology Ltd Copyright Integrated Control Technology Limited...