Innovative Circuit Technology Ltd.
Reverse Sequence Order
: Checking this box will cause the power on
sequence to run in reverse order with output channel 4 on first, ending with
output 1, when the
Enable Bus
button is clicked on the
Status and Control
page.
Network Watchdog:
Watchdog Enabled
: Checking this box will enable the watchdog feature,
which will cause the unit to periodically ping up to two remote IP addresses
to verify the network connection status. If there is no response from either
address the unit will cycle the power on all outputs that have the
Power
Cycling
option enabled on the
Output Setup
page. This feature is useful for
re-booting a modem or other network device that is powered by one of the
distribution panel outputs, to help recover the network IP connection when
one of these devices has locked up. At least one channel must have the
Power Cycle
option enabled, and a delay time entered in the
Sequence/Cycle Delay
field for this function to work. Power for a cycled
channel will be held in the off state for the duration set by the
Sequence/Cycle delay time, then will be turned back on.
Primary IP Address
: Enter the remote IP address you would like the panel to
monitor. If left blank the unit will monitor the Gateway IP address listed in
the Network Setup page.
Secondary IP Address
: Enter an optional second IP address that the unit can
monitor to verify network status. The Network Watchdog will only trigger if
both the Primary and Secondary IP addresses fail to respond.
Watchdog Timeout
: Enter the time (1 to 80 minutes) for which the remote
IP address must stop responding to ping requests from the panel, before the
Network Watchdog will trigger an output power cycle. Ensure this time is
greater than the normal start-up time for the network hardware to prevent
nuisance power cycle events at system start up.
Data Logging:
Data Logging rate:
Enable this feature by selecting the sample rate. The data
logger will record the bus voltage, bus current, channel output currents,
breaker status, and alarm inputs at a rate of up to 1 sample per minute. View
this Comma Separated Values (CSV) format log by clicking the
Download Log
button, and open in any Spreadsheet software, such as Microsoft Excel. The
log will store up to 30days of data, with the oldest entries at the top of the
file, newest at the bottom.
Log Start Date
: Shows the date/time the most recent log began.