background image

2.2      Mounting

This unit is designed for either shelf or wall mounting. A minimum of 6” per side 
and 2” above the cabinet is necessary for the cooling and mounting purposes. 
Consideration   should  be   given  to  the   proximity   of   the   incoming   and   output 
power. 

Caution: Due to the weight of this system (up to 150 lb.) , mounting securely is 
extremely   important.   Standard   drywall   or   bookshelf     mounting   is   not 
acceptable. Mounting to the wall studs is required.

External batteries (on a rack or in a cabinet) should be located in an equipment 
room per local requirements.

2.3      Wiring

Open the door of the unit after removing the two fastening screws near the right 
edge of the door. Four dual concentric knockouts are located on the left side of 
the cabinet to install 1/2” or 3/4” conduit to the unit. Run 18 gauge (minimum) 
wires   through   the   conduit   and   connect   per   Installation   Wiring   Diagram   No. 
8022072   at   the   rear   of   this   manual.   The   input/output   terminal   strip   TS3   is 
located on the left side of the cabinet above the knockouts.

This UPS is provided with external batteries which must be connected to the 
unit.   Confirm   that   all   sources   of   power   are   off   and   that   the   battery   circuit 
breaker on the left side of the cabinet is off ( handle in the down position). 
Loosen the outside caps on the plastic feedthroughs located on the left side of 
the cabinet and pass the two battery wires (marked POS+ and NEG-) through 
the feedthroughs. Connect the wires to the terminal board on the inside rear of 
the cabinet, matching the wire markings to the terminals. Close the cabinet 
door and replace the two screws near the right hand edge of the front panel. 

With the battery system wired ( four batteries in series mounted on an open 
rack, or in a prewired battery cabinet), connect the two battery wires from the 
UPS to the battery system observing the proper polarities.

WARNING:

   The battery system is a hazardous source of power. Make all 

connections first before connecting the equipment to the batteries. Connect the 
wires at the battery terminal last. Improper polarities will damage the UPS 
and/or batteries. 

2.4      Startup Procedure

  

2.4.1 With the battery circuit breaker off ( handle in the down position) and 
the load(s) disconnected, apply AC input power.

3

Содержание Lifeline M95-600 Series

Страница 1: ...NINTERRUPTIBLE POWER SYSTEM MODEL M95 600 SERIES PART NO 9300057 DRAWING NO 8060180 ISSUED 5 21 07 REV B RELEASED INSTRUMENTATION AND CONTROL SYSTEMS INC 520 WEST INTERSTATE ROAD ADDISON ILLINOIS 6010...

Страница 2: ...ny situation develops that is different from what is described herein contact the factory for further assistance 1 3 Proprietary Notice This equipment was designed and manufactured under several paten...

Страница 3: ...s This UPS is provided with external batteries which must be connected to the unit Confirm that all sources of power are off and that the battery circuit breaker on the left side of the cabinet is off...

Страница 4: ...in the down position to prevent further discharge of the battery 2 6 5 If servicing of the UPS or the battery is required disconnect the battery cable at the battery before performing any maintenance...

Страница 5: ...LOAD PRESENT STATIC SWITCH CLOSED BATTERY CHARGER Figure 3 1 Commercial Power On 3 3 Operation From Battery During the loss of commercial AC power the battery provides DC current to the inverter which...

Страница 6: ...he factory However if any adjustments need to be made it is probably due to component changes in the field over a long period of time Under those circumstances it is important that the user contact th...

Страница 7: ...t when commercial power is present X No AC output when commercial power is not present X Check Battery Battery does not charge X X Check Battery Output voltage low X Reduce Load Output frequency low o...

Страница 8: ...s well as all shipping cost On repaired apparatus the warranty shall be as for new apparatus except that it shall only apply to the parts repaired or replaced by ICS Inc No separate warranty shall app...

Страница 9: ...ns and other consequential damages whether direct or indirect and whether or not resulting from or contributed to by the default or negligence of ICS Inc its agent employees and sub contractors which...

Страница 10: ...ature 10 to 40 degrees C Operating Humidity 0 to 85 non condensing Storage Temperature 0 to 65 degrees C Input Output Connections Terminal strip with provisions for conduit entry 6 2 Controls Battery...

Страница 11: ...BATTERY WIRES 8GA AWG MIN ALL OTHER WIRES 18GA AWG MIN TOTAL UPS LOAD WITH BATTERY BACKUP 5AAC MAX 2 HOURS BACKUP TIME AT 5 0 AAC OUTPUT 4 HOURS BACKUP TIME AT 2 5AAC OUTPUT CONNECT TO EARTH GROUND 11...

Страница 12: ...CABINET DIMENSIONS 12...

Страница 13: ...P INPUT OUTPUT CONNECTION ACCESS 4 DUAL CONCENTRIC CONDUIT HOLES OPERATING TEMPERATURE 10 40 DEGREES C OPERATING HUMIDITY 0 85 NON CONDENSING STORAGE TEMPERATURE 0 65 DEGREES C 4 CONTROLS BATTERY CIRC...

Страница 14: ...ted 3 3 Turn on battery circuit breaker handle up The characteristic sound of the main transformer in the UPS may change somewhat due to charging of the battery system 3 4 Connect the load s to the UP...

Отзывы: