OPERATING INSTRUCTIONS FOR UPS PART NO. 9300057
DRAWING N0. 8060181
ISSUED 06/16/94
REV. A: RELEASED
Mount this sheet in a frame and locate it adjacent to the unit. Refer to Drawing/Manual No. 8060180, issued
06/16/94 for complete information.
1. Ratings:
Input AC Power: 120VAC, 60Hz., 8AAC nominal
Input DC Power: 48VDC, 55AH Battery
Output AC Power:120VAC, 60Hz., 5AAC
Charging Current: 2ADC
2. Intended Load: Fire Protection Signaling Systems
3. Startup Procedure
3.1 With the battery circuit breaker off (handle in down position) and the load(s) disconnected, apply AC
input power.
3.2 After UPS starts up, verify that all three LED indicators on front panel are illuminated.
3.3 Turn on battery circuit breaker (handle up). The characteristic sound of the main transformer in the
UPS may change somewhat due to charging of the battery system.
3.4 Connect the load(s) to the UPS output.
4. Shutdown Procedure
4.1 Disconnect the load(s) from the UPS.
4.2 Disconnect the commercial AC power source from the unit.
4.3 Press the BATTERY OFF pushbutton switch on the front panel to turn off the UPS.
4.4 Turn off the battery circuit breaker (handle in the down position) to prevent further discharge of the
battery.
4.5 If further servicing of the UPS or battery system is required, disconnect the battery cables at the
battery before performing any maintenance.
5. Local Service Representative:
Name:
Address:
TEL:
FAX:
INSTRUMENTATION & CONTROL SYSTEMS INC.
520 WEST INTERSTATE ROAD ADDISON, ILLINOIS 60101 USA
TEL (630) 543-6200 FAX (630) 543-6244