TECHNICAL INFORMATION FOR MODEL 9300057 UPS

 

6.1 

Specifications

Input Power DC: 48VDC nominal, 55AH sealed lead-acid battery
Charging Current: 2ADC  
Input Power AC: 120VAC, +10/-15%, 60Hz, 8AAC nominal, single phase
Rated Output Power: 120VAC, 60Hz, 5.0AAC (600VA/W), single phase
Load Power Factor: 0.8 to 1.0
Output Voltage Regulation: +/-3%
Output Waveform: Sinusoidal with 5% maximum total harmonic distortion
Efficiency: Up to 85% at nominal line, battery voltage and full load
Battery Backup Times:

4 Hours at 2.5AAC Output
2 Hours at 5.0AAC Output

Operating Temperature: 10 to 40 degrees C
Operating Humidity: 0 to 85% non-condensing
Storage Temperature: 0 to 65 degrees C
Input/Output Connections: Terminal strip with provisions for conduit entry

6.2

Controls

Battery Circuit Breaker: Connects/disconnects battery to/from UPS.
Battery On/Reset Switch: Starts UPS from battery or restarts UPS after
low battery shutdown when AC input power not present.
Battery Off Switch: Shuts down UPS while operating from battery.

6.3

Indicators

AC Input LED: Indicates AC input power is present.
Battery LED: Indicates DC power is present.
AC Output LED: Indicates AC output power is available.

6.4

UL Certifications

Product Name: Fire Alarm Power Supply Unit
Category Control Number: UTRZ
Standard: UL1481Listing Mark Control No.: 2N09

10

Содержание 9300057

Страница 1: ...NINTERRUPTIBLE POWER SYSTEM MODEL M95 600 SERIES PART NO 9300057 DRAWING NO 8060180 ISSUED 5 21 07 REV B RELEASED INSTRUMENTATION AND CONTROL SYSTEMS INC 520 WEST INTERSTATE ROAD ADDISON ILLINOIS 6010...

Страница 2: ...ny situation develops that is different from what is described herein contact the factory for further assistance 1 3 Proprietary Notice This equipment was designed and manufactured under several paten...

Страница 3: ...s This UPS is provided with external batteries which must be connected to the unit Confirm that all sources of power are off and that the battery circuit breaker on the left side of the cabinet is off...

Страница 4: ...in the down position to prevent further discharge of the battery 2 6 5 If servicing of the UPS or the battery is required disconnect the battery cable at the battery before performing any maintenance...

Страница 5: ...LOAD PRESENT STATIC SWITCH CLOSED BATTERY CHARGER Figure 3 1 Commercial Power On 3 3 Operation From Battery During the loss of commercial AC power the battery provides DC current to the inverter which...

Страница 6: ...he factory However if any adjustments need to be made it is probably due to component changes in the field over a long period of time Under those circumstances it is important that the user contact th...

Страница 7: ...t when commercial power is present X No AC output when commercial power is not present X Check Battery Battery does not charge X X Check Battery Output voltage low X Reduce Load Output frequency low o...

Страница 8: ...s well as all shipping cost On repaired apparatus the warranty shall be as for new apparatus except that it shall only apply to the parts repaired or replaced by ICS Inc No separate warranty shall app...

Страница 9: ...ns and other consequential damages whether direct or indirect and whether or not resulting from or contributed to by the default or negligence of ICS Inc its agent employees and sub contractors which...

Страница 10: ...ature 10 to 40 degrees C Operating Humidity 0 to 85 non condensing Storage Temperature 0 to 65 degrees C Input Output Connections Terminal strip with provisions for conduit entry 6 2 Controls Battery...

Страница 11: ...BATTERY WIRES 8GA AWG MIN ALL OTHER WIRES 18GA AWG MIN TOTAL UPS LOAD WITH BATTERY BACKUP 5AAC MAX 2 HOURS BACKUP TIME AT 5 0 AAC OUTPUT 4 HOURS BACKUP TIME AT 2 5AAC OUTPUT CONNECT TO EARTH GROUND 11...

Страница 12: ...CABINET DIMENSIONS 12...

Страница 13: ...P INPUT OUTPUT CONNECTION ACCESS 4 DUAL CONCENTRIC CONDUIT HOLES OPERATING TEMPERATURE 10 40 DEGREES C OPERATING HUMIDITY 0 85 NON CONDENSING STORAGE TEMPERATURE 0 65 DEGREES C 4 CONTROLS BATTERY CIRC...

Страница 14: ...ted 3 3 Turn on battery circuit breaker handle up The characteristic sound of the main transformer in the UPS may change somewhat due to charging of the battery system 3 4 Connect the load s to the UP...

Отзывы: