TECHNICAL INFORMATION FOR MODEL 9300057 UPS
6.1
Specifications
Input Power DC: 48VDC nominal, 55AH sealed lead-acid battery
Charging Current: 2ADC
Input Power AC: 120VAC, +10/-15%, 60Hz, 8AAC nominal, single phase
Rated Output Power: 120VAC, 60Hz, 5.0AAC (600VA/W), single phase
Load Power Factor: 0.8 to 1.0
Output Voltage Regulation: +/-3%
Output Waveform: Sinusoidal with 5% maximum total harmonic distortion
Efficiency: Up to 85% at nominal line, battery voltage and full load
Battery Backup Times:
4 Hours at 2.5AAC Output
2 Hours at 5.0AAC Output
Operating Temperature: 10 to 40 degrees C
Operating Humidity: 0 to 85% non-condensing
Storage Temperature: 0 to 65 degrees C
Input/Output Connections: Terminal strip with provisions for conduit entry
6.2
Controls
Battery Circuit Breaker: Connects/disconnects battery to/from UPS.
Battery On/Reset Switch: Starts UPS from battery or restarts UPS after
low battery shutdown when AC input power not present.
Battery Off Switch: Shuts down UPS while operating from battery.
6.3
Indicators
AC Input LED: Indicates AC input power is present.
Battery LED: Indicates DC power is present.
AC Output LED: Indicates AC output power is available.
6.4
UL Certifications
Product Name: Fire Alarm Power Supply Unit
Category Control Number: UTRZ
Standard: UL1481Listing Mark Control No.: 2N09