9 Supplement
WIKA Operating Instructions - Process pressure transmitter CPT-2x
Ʋ
Pressure value
-20 … 120 %
Zero/Span adjustment:
Ʋ
Zero
-20 … +95 %
Ʋ
Span
-120 … +120 %
Ʋ Difference between zero and span
max. 120 % of the nominal range
Max. permissible Turn Down
Unlimited (recommended 20 : 1)
Switch-on phase
Start-up time with operating voltage U
B
Ʋ ≥ 12 V DC
≤ 9 s
Ʋ
< 12 V DC
≤ 22 s
Staring current (for run-up time)
≤ 3.6 mA
Output variable
Output signal
4 … 20 mA - passive
Connection technology
Two-wire
Range of the output signal
3.8 … 20.5 mA (default setting)
Signal resolution
0.3 µA
Fault signal, current output (adjustable)
≤ 3.6 mA, ≥ 21 mA, last measured value
Max. output current
21.5 mA
Load
See load resistance under Power supply
Damping (63 % of the input variable),
adjustable
0 … 999 s
Dynamic behaviour output
Dynamic characteristics depending on medium and temperature
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 32: Behaviour in case of sudden change of the process variable. t
T
: dead time; t
A
: rise time; t
S
: jump response
time
1
Process variable
2
Output signal