Lightening and Surge Protection 17
Lightening and Surge Protection
This series speed dome adopts TVS lighting protection technology. It can effectively prevent
damages from various pulse signals below 6000V, such as sudden lighting and surge. While
maintaining your local electrical safety code, you still need to take necessary precaution
measures when installing the speed dome in the outdoor environment.
The distance between the signal transmission cable and high-voltage device (or
high-voltage cable) shall be at least 50 meters.
Outdoor cable layout shall go under the penthouse if possible.
For vast land, use sealing steel tube under the land to implement cable layout and
connects one point to the earth. Open floor cable layout is forbidden.
For vast land, install a 10KA lightning rod near the Camera’s power input port and Ethernet
port. For Camera with AC to DC power adapter, install a 10KA lightning rod near the
adapter’s input port.
For Camera installed on the iron tower, if there is a wire connected properly into the ground,
connect the Camera’s ground wire to the tower’s ground wire. And:
Make sure that the Camera is over 3 m away from the tower lightning rod’s top point.
Use several strands of copper wire whose total diameter is up to 16 mm
2
.
Make sure the Camera is installed within both arcs of circles whose radius is 60m. See
Appendix figure 1-1.
If there is no ground wire on the tower, connect the Camera’s ground wire into the ground.
In area of strong thunderstorm hit or near high sensitive voltage (such as near high-voltage
transformer substation), you need to install additional high-power thunder protection
device or lightning rod.
The thunder protection and earth of the outdoor device and cable shall be considered in
the building whole thunder protection and conform to your local national or industry
standard.
System shall adopt equal-potential wiring. The earth device shall meet anti-jamming and at
the same time conforms to your local electrical safety code. The earth device shall not
short circuit to N (neutral) line of high voltage power grid or mixed with other wires. When
you connect the system to the earth alone, the earth resistance shall not be more than 4Ω
and earth cable cross-sectional area shall be no less than 25 mm
²
. See Appendix figure
Содержание THIP-P2078FM-IR
Страница 1: ...Thermal Hybrid Speed Dome Quick Start Guide V1 0 0 ...
Страница 14: ...Design 3 Pole mount bracket mm inch Corner mount bracket mm inch ...
Страница 22: ...Installation 11 Wall mount installation ...
Страница 23: ...Installation 12 Pole mount installation ...
Страница 24: ...Installation 13 Corner mount installation Ceiling mount installation ...
Страница 29: ...Lightening and Surge Protection 18 Appendix figure 1 1 Lightening protection ...