Q05 : How to read HART device CMD1 data with standard format by
Modbus ?
A05:
(1) By using “HG_Tool” to add “User CMD(1)” of HART device and save settings to
HRT-710. The Modbus start address and length of the “User CMD(1)” will show in the
“Cmd In address” and “Cmd In size” field like Figure 5-1. In the example they are 0 and
7 (byte count=7 => word count=4).
HRT-710 / HRT-310 User Manual
Version 1.31