5.3.4.7 Through Mode
Figure 46: The window of through mode
It is used to send / receive HART command directly.
EX: Send a short frame HART command 0 and receive the response.
(1) In “Send” field, fill in the data - “0xFF 0xFF 0xFF 0xFF 0xFF 0x02 0x80 0x00 0x00” and
then click “Send” button to send HART Cmd.
(2) Click “Update” button to show the response of HART device.
Warning: Before using through mode function, please check the below items:
(1) The “RUN” LED is always on.
(2) The “auto polling” function is disabled. (Refer to section 5.3.4.2 – “The Basic Operation
of System item”)
HRT-710 / HRT-310 User Manual
Version 1.31
Page
:
65
Copyright © 2017 ICP DAS Co., Ltd. All Rights Reserved E-mail: [email protected]