background image

 

 10

 

 

 

 

2.13.3  Air Conditioner (or Heat Pump) 

An air conditioning coil may be installed on the supply air side 
ONLY.  

 

WARNING 

 

Poisonous carbon monoxide gas hazard. 

 

Install the evaporator coil on the supply side of the 
furnace ducting ONLY. 

 

An evaporator coil installed on the return air side of the 
ducting can cause condensation to form inside the heat 
exchanger, resulting in heat exchanger failure. This in 
turn, can result in death, bodily injury and/or property 
damage. 

 

A clearance of 15 cm (6") is required between the bottom of 
the coil drain pan and the top of the heat exchanger. If a heat 
pump is installed, a “dual-energy” thermostat, or other control 
is required, in order to prevent the simultaneous operation of 
the furnace and the heat pump. It also prevents a direct 
transition from heating by way of the heat pump to heating with 
oil. Refer to the thermostat instructions or those of another 
control used for the proper wiring. 

 

If a coil blower compartment is used, install air tight, motorized 
and automatic air dampers. Cold air coming from the coil and 
passing across the furnace can cause condensation and 
shorten the life of the heat exchanger. 
 

3 OPERATION 

3.1 START-UP 

Before starting up the unit, be sure to check that the following 
items are in compliance: 

 

1. 

The electrical installation, the oil supply system, the 
venting system, combustion air supply and ventilation; 

2. 

The blower access door is in place and the blower rail 
locking screws are well tightened; 

3. 

The Blocked Vent Shut-Off (BVSO) is installed according 
to instructions (for chimney venting); 

4. 

The oil supply valve is open; 

5. 

The burner ‘’Reset’’ button is well pushed in or re-armed; 

6. 

The preliminary air adjustments on the burner comply with 
the technical specifications in this manual; 

7. 

The blower speed adjustments for heating and air 
conditioning are appropriate and according to the 
specifications in this manual; 

8. 

The blower start/stop delays are satisfactory; 

9. 

The thermostat of the room is in the heating mode and is 
set higher than the ambient temperature. 

 

To start the unit, turn the main electrical switch on.  

 

3.2 OPERATING

 

SEQUENCE 

OIL

 

HEATING

 

MODE

 

 

1. 

The W-R contact closes; 

2. 

The burner motor starts up to pre-purge the 
combustion chamber for a period of 10 to 15 
seconds. During that time a spark is established on 
the electrodes; 

3. 

The solenoid valve opens and a flame is established. 
Shortly after, the electrodes cease to spark; 

4. 

Then the blower runs up to full speed. The delay 
depends on the adjustments that were made on the 
electronic board, which controls the blower motor. 
Refer to Sections 2.11 and 2.12, p. 8 and 9 above, as 
well as the CFM table for more details. 

5. 

When the call for heat is satisfied, the solenoid valve 
closes, the flame goes out and the burner motor 
stops (after post purge delay, if applicable). 

6. 

The blower stops shortly after the burner. The delay 
depends on the adjustments that were made on the 
electronic board that controls the blower. Refer to 
Sections 2.11 and 2.12, p. 8 and 9 above, as well as 
the CFM table for more details. 

 

Note: A detailed operating sequence of the oil burner is 
outlined in the instructions provided with the burner. 

3.3 CHECKS

 

AND

 

ADJUSTMENTS 

 

3.3.1 

Purging the oil line 

 

Open the bleed port screw and start the burner. Allow the 
oil to drain into a container for at least 10 seconds. The oil 
should flow absolutely free of white streaks or air bubbles 
to indicate that no air is being drawn into the suction side 
of the oil piping and pump. Slowly close and tighten the 
bleed screw. Once closed, the flame will light up. 

 

 

3.3.2 Pressure 

adjustment 

 

The oil pressure must be adjusted according to the 
Technical Specifications of this manual. An adjustment 
screw and a connection for a pressure gauge are located 
on the oil pump for that purpose. Also refer to the burner 
instruction manual. 
 

445 01 4101 00

Содержание OMF112K14A

Страница 1: ...HE INFORMATION IN THIS MANUAL FOR THE INSTALLATION SERVICING OF THE FURNACE AND KEEP THE DOCUMENT NEAR THE UNIT FOR FUTURE REFERENCE HOMEOWNER PLEASE KEEP THIS MANUAL NEAR THE FURNACE FOR FUTURE REFER...

Страница 2: ...LE SPEED MOTORS 9 2 13 INSTALLATION OF ACCESSORIES 9 3 OPERATION 10 3 1 START UP 10 3 2 OPERATING SEQUENCE OIL HEATING MODE 10 3 3 CHECKS AND ADJUSTMENTS 10 4 MAINTENANCE 12 4 1 CLEANING THE HEAT EXCH...

Страница 3: ...on such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform to loca...

Страница 4: ...t designed for outdoor installation It must be installed in such a manner as to protect its electrical components from water Outdoor installation will lead to a hazardous electrical condition and to p...

Страница 5: ...f bodily harm if ever an electrical problem develops A green ground screw is supplied with the control box for that purpose The appliance must be installed in accordance with the current ANSI NFPA 70...

Страница 6: ...e burner for the first time adjust the air and turbulator settings to those listed in this manual Once the burner becomes operational final adjustments will be required Refer to section 3 of this manu...

Страница 7: ...Test The purpose of the following test is to check that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BVSO outle...

Страница 8: ...istance 2 10 DUCTING WARNING Poisonous carbon monoxide gas hazard DO NOT draw return air from inside a closet or utility room Return air MUST be sealed to the furnace casing Failure to properly seal d...

Страница 9: ...GPH OFF OFF A 0 68 ON OFF B 0 80 OFF ON C ALL ON ON D ALL 2 13 INSTALLATION OF ACCESSORIES WARNING Electrical shock hazard Turn OFF electrical power at the fuse box or service panel before making any...

Страница 10: ...are appropriate and according to the specifications in this manual 8 The blower start stop delays are satisfactory 9 The thermostat of the room is in the heating mode and is set higher than the ambie...

Страница 11: ...bove the burner is a measurement necessary to determine if there is a blockage in the heat exchanger or the flue pipe Refer to the Technical Specifications in this manual for overfire pressure values...

Страница 12: ...combustion chamber should be inspected to determine if replacement is required 8 After the cleaning replace the heat exchanger baffles flue collar plate and oil burner 9 Readjust the burner for proper...

Страница 13: ...ephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient te...

Страница 14: ...n 85 2 85 0 85 2 85 0 RIELLO BURNER MODEL 40 BF5 Direct vent DV Burner tube insertion length inches Nozzle Delavan 0 60 70A 0 70 70A 0 60 70A 0 70 70A Minimum and Maximum pump pressure PSIG 130 to 160...

Страница 15: ...me ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 68 13 45 sec 19 60 sec 38 3 min B 1 ON 2 OFF 0 80 13 45 sec 19 30 sec 38 3 min C 1 OFF 2 ON All 13 45 sec 100 0 sec 100 2 m...

Страница 16: ...ACE 1 5 08 cm 2 2 54 cm 1 5 08 cm 2 BOTTOM FURNACE 2 2 54 cm 1 3 5 08 cm 2 4 BACK FURNACE OPPOSITE SIDE OF THE BURNER 1 7 62 cm 3 7 62 cm 3 7 62 cm 3 PLENUM OR HORIZONTAL WARM AIR DUCT WITHIN 6 ft OF...

Страница 17: ...17 Figure 5 Furnace dimensions 445 01 4101 00...

Страница 18: ...18 Figure 6 Wiring Diagram 4 Speed Motor PSC 445 01 4101 00...

Страница 19: ...19 Figure 7 Wiring Diagram Variable Speed Motor ECM 445 01 4101 00...

Страница 20: ...20 PARTS LIST With 4 Speed motor PSC B50091B 445 01 4101 00...

Страница 21: ...MBLY Blower motor and capacitor included 24 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 25 B03118 01 ELECTRICAL KIT BVSO EXT 26 L07F003 ROCKER SWITCH DPST 27 L04I013 STRAIN RELIEF BUSHING 28 L04J001 CABLE...

Страница 22: ...22 PARTS LIST With variable speed motor ECM B50092B 445 01 4101 00...

Страница 23: ...EMBLY Blower motor and capacitor included 24 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 25 B03118 01 ELECTRICAL KIT BVSO EXT 26 L04I013 STRAIN RELIEF BUSHING 27 L04J001 CABLE CLAMP 9 16 WHITE 28 B03640 WI...

Отзывы: