background image

SERVICE AND TECHNICAL SUPPORT MANUAL

Gas Furnace: N9MSB

Specifications  subject to change without notice.

16

440 04 4413 00

2. Remove blower door.
3. All factory wires can be left connected, but field

thermostat and accessory wiring may need to be

disconnected depending on their length and routing.

4. If the vent and combustion air pipe passes through the

blower compartment, it will be necessary to remove the

pipes from the blower compartment.

Disconnect the vent  and  combustion air pipe by:

a. Loosen the clamps on the vent couplings and

combustion air pipe external to the furnace.

b. Separate the pipes from the couplings and move

them aside.

c. Loosen the clamps on the vent couplings and

combustion air pipe located on the blower shelf.

d. Separate the pipes from the blower compartment and

set aside.

e. Remove the couplings from the pipe adapters and set

aside.

f. After servicing the blower, reverse steps a through e.

g. Tighten all clamps 15 lb

in.

See 

Figure 8

 for steps 5 through 14.

5. Remove screws securing blower assembly to blower

shelf and slide blower assembly out of furnace. Detach

ground wire and disconnect blower motor harness plugs

from blower motor.

NOTE

:  Blower wheel is fragile. Use care.

6. Clean blower wheel and motor by using a vacuum with

soft brush attachment. Be careful not to disturb balance

weights (clips) on blower wheel vanes. Do not bend

wheel or blades as balance will be affected.

7. If greasy residue is present on blower wheel, remove

wheel from the blower housing and wash it with an

appropriate degreaser. To remove wheel:
a. Mark blower wheel location on shaft before

disassembly to ensure proper reassembly.

b. Loosen setscrew holding blower wheel on motor

shaft.

NOTE

:  Mark blower mounting arms and blower housing so

each arm is positioned at the same hole location during
reassembly.

c. Mark blower wheel orientation and cutoff plate

location to ensure proper reassembly.

d. Remove screws securing cutoff plate and remove

cutoff plate from housing.

e. Remove bolts holding motor mounts to blower

housing and slide motor and mounts out of housing.

f. Remove blower wheel from housing.

g. Clean wheel per instructions on degreaser cleaner.

Do not get degreaser in motor.

8. Reassemble motor and blower wheel by reversing items

7b through 7f. Ensure wheel is positioned for proper

rotation.

9. Torque motor mounting bolts to 40 +/

 10 lb

in. when

reassembling.

10. Torque blower wheel set screw to 160 +/

 20 lb

in. when

reassembling.

11. Verify that blower wheel is centered in blower housing

and set screw contacts the flat portion of the motor shaft.

Loosen set screw on blower wheel and reposition if

necessary.

12. Spin the blower wheel by hand to verify that the wheel

does not rub on the housing.

13. Reinstall blower assembly in furnace.

Figure 8

Blower Assembly

A11584A

SET SCREW

MOTOR WHEEL HUB

MOTOR SHAFT FLAT

A11584B

SCREW

MOTOR ARM

GROMMET

A11584C

SCREW LOCATION

BLO HSG ASSY

BRACKET

BRACKET

ENGAGEMENT

DETAIL

 

A

A11584D

SEE DETAIL 

A

POWER CHOKE

BRACKET

SCREW

(GND)

BLOWER HSG ASSY

MOTOR, BLOWER

WHEEL, BLOWER

CUTOFF, BLOWER

A11584E

OR CAPACITOR

WHEN REQUIRED

Содержание N9MSB0401410C

Страница 1: ...The signal word WARNING is used throughout this manual in the following manner Safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for pe...

Страница 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Страница 3: ...am of Furnace Drip Leg Gas Valve turned ON Type of Gas Natural Propane Filter Type and Size Check in box the Blower OFF Delay Jumper Heating Position for Fan Time OFF Setting 1 and 2 2 and 3 3 and 4 5...

Страница 4: ...is energized whenever blower operates HUM 24vac terminal is only energized the draft inducer is energized in heating Prime Condensate Trap with Water CARBON MONOXIDE POISONING HAZARD Failure to follo...

Страница 5: ...has the correct orifice installed At higher altitudes or different gas heat contents it may be necessary to change the factory orifice to a different orifice Tables have been provided in the furnace S...

Страница 6: ...rewdriver counterclockwise out to decrease input rate or clockwise in to increase input rate NOTICE DO NOT set low heat manifold pressure less than 2 8 in w c 697 Pa or more than 3 8 in w c 947 Pa for...

Страница 7: ...24 VAC CONNECTIONS P2 HOT SURFACE IGNITOR HSI INDUCER MOTOR IND CONNECTOR 115 VAC L1 LINE VOLTAGE CONNECTION SPARE1 COM BLUE 115 VAC L2 NEUTRAL CONNECTIONS 24 V THERMOSTAT TERMINALS HUMIDIFIER TERMINA...

Страница 8: ...300 21 171 343 857 62 58 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 9...

Страница 9: ...42 3 4 42 3 5 42 3 6 3001 800 43 3 8 42 3 2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219...

Страница 10: ...ding Leaving blower door off will result in incorrect temperature measurements due to possible changes in duct static pressure and airflow FURNACE DAMAGE HAZARD Failure to follow this caution may resu...

Страница 11: ...e terminals R and W The thermostat anticipator should NOT be in the circuit while measuring current 1 Remove thermostat from sub base or from wall 2 Connect an amp meter across the R and W sub base te...

Страница 12: ...2 5 394 1030 1025 1030 1010 985 940 905 855 805 735 801716C SIDE BOTTOM Black 4 0 389 1650 1620 1640 1605 1555 1495 1425 1345 1255 1165 Yellow 3 5 381 1420 1425 1400 1370 1335 1290 1230 1170 1095 1015...

Страница 13: ...nominal break point of each switch is shown on the label below the reference location in inches of water column W C The maximum and minimum break point of the switch is 0 05 inches of water column fro...

Страница 14: ...LED 6 A component test sequence will follow 7 Reinstall the Main Control door Component Self Test NOTE The furnace control component test allows all components to run for a short time except the gas v...

Страница 15: ...rvice as necessary 4 Inspect burner compartment before each heating season for rust corrosion soot or excessive dust If necessary have furnace and burner serviced by a qualified service agency 5 Inspe...

Страница 16: ...t on blower wheel remove wheel from the blower housing and wash it with an appropriate degreaser To remove wheel a Mark blower wheel location on shaft before disassembly to ensure proper reassembly b...

Страница 17: ...old or damaging the mounting to the burner assembly ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and el...

Страница 18: ...ck for proper operation 18 Install control door when complete Servicing Hot Surface Igniter The igniter does NOT require annual inspection Check igniter resistance before removal Refer to Figure 9 Fig...

Страница 19: ...6 Connect condensate drain elbow or drain extension elbow to the condensate trap 7 Connect the leads of the condensate heat pad if used 8 Connect external drain piping to the condensate drain elbow or...

Страница 20: ...ratures may be 32_ F 0_ C or lower freeze protection measures must be taken to prevent property or product damage CAUTION Since the furnace uses a condensing heat exchanger some water will accumulate...

Страница 21: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace N9MSB Specifications subject to change without notice 440 04 4413 00 21 Figure 14 Service Label 338310 2 Rev F...

Страница 22: ...SERVICE AND TECHNICAL SUPPORT MANUAL Gas Furnace N9MSB Specifications subject to change without notice 22 440 04 4413 00 Figure 15 Wiring Diagram 339241 2 Rev A...

Страница 23: ...quence Gas valve and humidifier will not be turned on Inducer motor will start and remain on until the end of the blower test then off The following components are on for 10 15 seconds each individual...

Страница 24: ...onent test Does the igniter glow orange white by the end of the 15 second warm up period Unplug igniter harness from control and repeat component test Check for 115V between connector P2 HSI and NEUTR...

Страница 25: ...ds after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC is energized and remains energized as long as the blower motor BLWM is energized f Heat Off Delay When the...

Страница 26: ...ctor box Condensate trap Condensate trap elbow Gaskets WARNING FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in dangerous operation p...

Страница 27: ...ble Speed X ECM S Single stage T Two stage FEATURE B Base AFUE Efficiency E Extra AFUE Efficiency C Communicating D Dual Certified 2 pipe or 1 pipe R 2 pipe only S Single stage T Two stage N Standard...

Отзывы: