ICP HC4H3 Скачать руководство пользователя страница 10

10

428 01 9700 03

START

UP

Step 1

 —

Preliminary Checks

1. Check that all internal wiring connections are tight

and that all barriers, covers, and panels are in place.

2. Field electrical power source must agree with unit

nameplate rating.

3. All service valves must be open.
4. Belly

band crankcase heater must be tight on

compressor crankcase for those units with belly

band

heaters.

Step 2

 —

Leak Test

Field piping and fan coil must be leak tested by pressure

method. Use R

410A refrigerant at approximately 25 psig

backed up with an inert gas to a total pressure not to

exceed 245 psig.

NOTE

:  Leak detectors should be designed to detect HFC

(hydroflourocarbon) refrigerant.

Step 3

 —

Evacuate and Dehydrate

Field piping and fan coil must be evacuated and

dehydrated.

Step 4

 —

Charge System

Release charge into system by opening (backseating) liquid

and suction line service valves. F

Step 5

 —

To Start Unit

Be sure that the field disconnect is closed. Set room

thermostat below ambient temperature. Operate unit for 15

minutes, then check system refrigerant charge. See

Refrigerant Charging section.

NOTE

:  When using in conjunction with underceiling fan

coils, refer to start

up instructions included with fan coil for

correct start

up procedures.

SERVICE

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in

personal injury or death.
Before installing, modifying, or servicing system,

main electrical disconnect switch must be in the

OFF position. There may be more than 1

disconnect switch. Lock out and tag switch with a

suitable warning label.

Outdoor Fan

A reinforced wire mount holds the outdoor fan assembly in

position. See Figure 10 for proper mounting position.

HC4H3 Unit Size, in. (mm)

18,24

30,36

48,60

0.433 (11.00)

0

0

A07401

Figure 10

 - 

Condenser Fan Mounting Positions

High

Pressure Relief Valve

The high

pressure relief valve is located in the compressor.

The relief valve opens at a pressure differential of

approximately 550 to 625 

±

 50 psig between suction (low

side) and discharge (high side) to allow pressure

equalization.

Internal Current and Temperature Sensitive Overload

The control resets automatically when internal compressor

motor temperature drops to a safe level (overloads may

require up to 45 minutes to reset). When an internal

overload is suspected of being open, check by using an

ohmmeter or continuity tester.

Pumpdown Procedure

The system may be pumped down in order to make repairs

on the low side without losing complete refrigerant charge.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never open system to atmosphere while it is under a

vacuum.

When system must be opened for service, recover

refrigerant, break vacuum with dry nitrogen before opening

system.

1. Attach pressure gage to suction service valve gage

port.

2. Frontseat the liquid/mixed phase line valve.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
The unit coils hold only the factorydesignated amount

of refrigerant. Additional refrigerant may cause units

to relieve pressure through the compressor internal

pressure relief valve (indicated by a sudden rise of

suction pressure) before suction pressure reaches 20

psig. If this occurs, shut off unit immediately then

frontseat the suction valve and remove and recover

excess refrigerant following accepted practices

3. Start unit and run until suction pressure reaches 20

psig.

4. Shut unit off and frontseat suction valve.

5. De

pressurize low side of unit and recover refrigerant

following accepted practices.

High

Pressure Switch

The high

pressure switch, located on discharge line,

protects against high discharge pressures caused by such

events as overcharge, condenser

fan motor failure, system

restriction, etc. It opens on pressure rise at about 650 

±

 10

psig. If system pressures go above this setting during

abnormal conditions, the switch opens.

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this warning could result in

personal injury or death.

DO NOT

 attempt to simulate these system

abnormalities 

 high pressures pose a serious

safety hazard.

The high

pressure switch is checked with an ohmmeter. If

system pressure is below 625 psig  switch shows continuity.

Содержание HC4H3

Страница 1: ...s Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit Consult local building codes and National Electrical Code NEC for special requirements Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instruction...

Страница 2: ...ints See Figure 3 for center of gravity Matching the Heat Pump to an Indoor Unit The HC4H3 ducted heat pump units can be matched to corresponding indoor units The HC4H3 unit can be matched with underceiling and residential fan coils and evaporator coils Refer to separate indoor unit literature for more information Expansion Device Cooling Mode A hard shutoff thermostatic expansion valve TXV is req...

Страница 3: ...30 1 60 208 230 3 60 460 3 60 1 1 2 FIELD CONTROL SUPPLY WIRE ENTRY 7 8 HOLE W GROMMET 1 REQUIRED CLEARANCES WITH COIL FACING WALL ALLOW 6 MIN CLEARANCE ON COIL SIDE AND COIL END AND 36 MIN CLEARANCE ON COMPRESSOR END AND FAN SIDE WITH FAN FACING WALL ALLOW 8 MIN CLEARANCE ON FAN SIDE AND COIL END AND 36 MIN CLEARANCE ON COMPRESSOR END AND COIL SIDE WITH MULTI UNIT APPLICATION ARRANGE UNITS SO DIS...

Страница 4: ...3 774 7 498 5 893 8 1017 6 368 3 215 9 479 4 22 2 87 3 165 1 139 0 150 4 1282 7 X 520 7 X 1173 1 UNIT SIZE DIMENSIONS 208 230 1 60 230 1 60 208 230 3 60 460 3 60 FIELD CONTROL SUPPLY WIRE ENTRY 22 22 HOLE W GROMMET FIELD POWER SUPPLY CONN HOLE SIZES PROVIDED 22 22 12 70 TRADE 30 16 19 05 TRADE 34 92 25 40 TRADE MEASUREMENT METR X YES O NO 1 REQUIRED CLEARANCES WITH COIL FACING WALL ALLOW 152 4 MIN...

Страница 5: ... 2 3 3 3 FPI 20 20 20 20 20 20 HIGH PRESSURE SWITCH Cut In psig Cutout psig 420 25 650 10 420 25 650 10 420 25 650 10 420 25 650 10 420 25 650 10 420 25 650 10 LOW PRESSURE SWITCH Low Cutout psig Low Cut in psig 20 5 45 25 20 5 45 25 20 5 45 25 20 5 45 25 20 5 45 25 20 5 45 25 REFRIGERANT LINES Connection Type Sweat Liquid Line in OD 3 8 Vapor Line in OD 5 8 3 4 7 8 7 8 Max Length ft m 200 60 96 M...

Страница 6: ... line sizes Do not use less than 10 ft 3 05 m of interconnecting tubing CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation If any section of pipe is buried there must be a 6 in 152 4 mm vertical rise to the valve connections on the outdoor unit If more than the recommended length is buried refrigerant may migrate to cooler buried section ...

Страница 7: ...HOCK HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintenance be sure indoor unit main power switch is turned OFF and indoor blower has stopped Power Wiring Unit is factory wired for voltage shown on nameplate Provide adequate fused disconnect switch within sight from unit readily accessible but out of reach of children Provision for l...

Страница 8: ...sor control G energizes fan relay at outdoor unit and outdoor fan motor runs 4 24 v from microprocessor control Y energizes the contactor coil and the compressor will run 5 Demand defrost is controlled by the indoor unit microprocessor control 6 The indoor unit microprocessor control continuously monitors both outdoor coil temperature and outdoor ambient temperature determining the optimum defrost...

Страница 9: ...nd requires external power source Copper wire must be used from service disconnect to unit 2 All motors compressors contain internal overload protection 3 In compliance with NEC U S A Standard requirements for multimotor and combination load equipment refer to NEC Articles 430 and 440 the overcurrent protective device for the unit shall be fuse 4 Motor RLA values are established in accordance with...

Страница 10: ...re equalization Internal Current and Temperature Sensitive Overload The control resets automatically when internal compressor motor temperature drops to a safe level overloads may require up to 45 minutes to reset When an internal overload is suspected of being open check by using an ohmmeter or continuity tester Pumpdown Procedure The system may be pumped down in order to make repairs on the low ...

Страница 11: ...reas and defrost demands Control board has additional feature that allows unit to restart in defrost cycle if room thermostat is satisfied during defrost Defrost control simultaneously tops outdoor fan energizes reversing valve solenoid to return system to cooling cycle outdoor unit as condenser indoor unit as evaporator and activates accessory electric heater The defrost timer limits defrosting p...

Страница 12: ...ant R 410A refrigerant cylinders are rose colored Recovery cylinder service pressure rating must be 400 psig DOT Department of Transportation 4BA400 or DOT BW400 R 410A systems should be charged with liquid refrigerant Use a commercial type metering device in the manifold hose when charging into suction line with compressor operating Manifold sets should be 700 psig high side and 180 psig low side...

Страница 13: ...47 9 64 39 58 7 3 13 72 160 56 2 13 44 262 86 9 30 50 364 110 0 43 33 466 128 7 53 72 596 148 4 64 67 60 8 6 13 00 162 57 0 13 89 264 87 4 30 78 366 110 4 43 56 468 129 0 53 89 600 149 0 65 00 62 10 0 12 22 164 57 7 14 28 266 87 9 31 06 368 110 8 43 78 470 129 3 54 06 604 149 5 65 28 64 11 3 11 50 166 58 4 14 67 268 88 4 31 33 370 111 2 44 00 472 129 7 54 28 608 150 1 65 61 66 12 6 10 78 168 59 0 ...

Страница 14: ...ce of 3 F 1 67 C Table 4 Subcooling Charging Table LIQUID PRES SURE AT SERVICE VALVE REQUIRED LIQUID LINE TEMPERATURE Required Subcooling Temperature _F 5C 8 4 4 10 5 5 12 6 6 14 7 7 16 8 8 18 9 9 psig _F 5C _F 5C _F 5C _F 5C _F 5C _F 5C 189 58 32 56 31 54 30 52 29 50 28 48 27 195 60 33 58 32 56 31 54 30 52 29 50 28 202 62 34 60 33 58 32 56 31 54 30 52 29 208 64 36 62 34 60 33 58 32 56 31 54 30 21...

Страница 15: ...ut with compressor air Note that the blow thru design causes dirt and debris to build up on the inside of the coils Clean coil annually or as required by location and outdoor air conditions Inspect coil monthly and clean as required Fins are not continuous through coil sections Dirt and debris may pass through first section become trapped between the row of fins and restrict condenser airflow Use ...

Страница 16: ...ING LEGEND NOTE For systems with indoor units equipped with microprocessor control see separate controls service and troubleshooting manual NC Normally Closed ODT Outdoor Thermostat A07435 Figure 13 Troubleshooting the Cooling Cycle ...

Страница 17: ...428 01 9700 03 17 TROUBLESHOOTING CONT A07436 Figure 14 Troubleshooting the Heating Cycle International Comfort Products LLC Lewisburg TN 37091 USA ...

Отзывы: