PART 1 

INSTALLATION 

 

 

 

3

SAFETY CONSIDERATIONS 

 
INSTALLATION OF OIL FIRED HEATING UNITS 
SHALL BE IN STRICT ACCORDANCE WITH THE 
REGULATIONS OF THE AUTHORITIES HAVING 
JURISDICTION. IN CANADA CSA B139 AND IN THE 
UNITED STATES NFPA NO.31-1992 INSTALLATION 
CODES FOR OIL BURNING EQUIPMENT APPLY. 
 
DO NOT OPERATE FURNACE IN A CORROSIVE 
ATMOSPHERE CONTAINING CHLORINE, FLUORINE 
OR ANY OTHER DAMAGING CHEMICALS. 
 
DO NOT STORE OR USE GASOLINE, OR OTHER 
FLAMMABLE VAPOURS AND LIQUIDS IN THE 
VICINITY OF THIS OR ANY OTHER APPLIANCE. 

 
 

1.1) 

SAFETY LABELING AND WARNING SIGNS 

 

DANGER, WARNING AND CAUTION 

 

The words DANGER, WARNING and CAUTION are used to identify 
the levels of seriousness of certain hazards. It is important that you 
understand their meaning. You will notice these words in the manual 
as follows: 

 
 

DANGER 

Immediate hazards that 

WILL

 result in death or 

serious damage to body and/or property.

 

 
 

WARNING 

Hazards or unsafe practices that CAN result in 
death or damage to body and/or property. 

 

 

CAUTION 

Hazards or unsafe practices which 

CAN

 result in 

damage to body and/or property.

 

 
 

1.2) SAFE 

INSTALLATION 

REQUIREMENTS

 

 

 

WARNING 

 

Installation or repairs performed by unqualified 
persons can result in hazards to them and others. 
Installation MUST conform to local codes or, in the 
absence of same, to codes of the country having 
jurisdiction. 

 

The information contained in this manual is 
intended for use by a qualified service technician 
familiar with safety procedures and equipped with 
the proper tools and test instruments. 

 

Failure to carefully read and follow all instructions 
in this manual can result in death and/or personal 
injury, property damage, furnace malfunction.

 

 
 

WARNING 

 

Fire hazard 

 

The furnace must be installed in a level position, 
never where it will slope toward the front. If the 
furnace is installed in the latter position, oil will 
drain into the furnace vestibule and create a fire 
hazard.

 

 
 

NOTE:

 It is the personal responsibility and obligation of the 

homeowner to contact a qualified technician to ensure that the 
installation conforms to applicable local and/or national codes and 
ordinances. 
 
a.  This furnace is NOT approved for installation in mobile homes, 

trailers or recreational vehicles; 

b. Do 

NOT

 use this furnace as a construction heater or to heat a 

building under construction; 

c. 

There must be a sufficient supply of fresh air for combustion as 
well as ventilation in the area where the furnace is located; 

d.  Use only the Type of fuel oil approved for this furnace (see 

Rating Plate

 on unit). Overfiring will result in heat exchanger 

failure and cause dangerous operating conditions; 

e.  Visually check all oil line joints for signs of wetness, which would 

indicate a leak; 

f. 

Connect furnace to the chimney; 

g.  The points in Part 2 “Operation” are vital to the proper and safe 

operation of the heating system. Take the time to ensure that all 
steps were followed; 

h. 

Follow the regulations of the ANSI/NFPA No.31 (in the USA) and 
CSA B-139 (in Canada) or local codes for placing and installing 
the oil storage tank; 

445 01 4054 06

Содержание FLO115DABR-C

Страница 1: ...5DABR D OLF140C12C OLR182A16C D N S 0 5 9 4 R v A D N S 0 6 6 5 R v A D N S 0 5 7 5 R v A Manufactured by UTC Canada Corporation ICP Division 3400 Industrial Boulevard Sherbrooke Quebec Canada J1L 1V8...

Страница 2: ...ician familiar with safety procedures and equipped with the proper tools and test instruments Failure to carefully read and follow all instructions in this manual can result in death and or personal i...

Страница 3: ...mber Normal servicing of this unit does not require cleaning of the combustion chamber Use extreme care if for any reason you have to work in the area of the combustion chamber 1 2 2 Freezing temperat...

Страница 4: ...r size and adequate chimney base temperature as specified in the Installation Code The relevant excerpt from the code is found in this section Use it as a guide when local or national codes do not exi...

Страница 5: ...o provide adequate combustion and ventilation air can result in death and or personal injury 1 5 1 General Oil furnaces must have an adequate supply of combustion air It is common practice to assume t...

Страница 6: ...vinyl vapour barrier CAUTION The CAS 2B does not turn the furnace installation into a direct vent system Therefore the building structure must provide for adequate combustion air to be delivered to t...

Страница 7: ...heat exchanger warranty intact WARNING Fire and explosion hazard Use only approved heating type oil in this furnace DO NOT USE waste oil used motor oil gasoline or kerosene Use of these will result in...

Страница 8: ...here the furnace is located Install the air conditioning cooling coil evaporator downstream from the supply air plenum of the furnace If a separate evaporator and blower unit is used install appropria...

Страница 9: ...off the disconnect switch and CALL A QUALIFIED SERVICE TECHNICIAN CAUTION Do not attempt to start the burner when excess oil has accumulated when the furnace is full of vapour or when the combustion c...

Страница 10: ...nd blower regulator Modification of the FAN ON and HI Limit settings on the Fan Limit and blower regulator can cause a malfunction of the furnace and carry to premature wear of the heat exchanger CAUT...

Страница 11: ...inder with a stiff brush and vacuum cleaner 7 The heat exchanger and combustion chamber should be inspected to determine if replacement is required before re assembling the unit 8 After cleaning repla...

Страница 12: ...ntion head 3 1 5 Nozzle Replace the nozzle with the one specified in Tables 3 1 to 3 4 p 15 to 18 3 1 6 Oil filter Tank filter The tank filter should be replaced as required Secondary filter The 10 mi...

Страница 13: ...e Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure Lb psi Burner adjustments Primary air Fine air Draw Assembly CO2 Smoke scale Bacharach Gross stack temperature F Ambient tempe...

Страница 14: ...5 1 2 75 2 3 75 AERO BURNER 1725 RPM Nozzle 100 PSIG pump pressure Delavan 0 65 70W 0 75 70W 0 85 70W Volts Hertz Phase Operating voltage range Rated voltage Amps Minimum ampacity for wiring sizing Ma...

Страница 15: ...Nozzle Delavan 060 60W 075 60W 0 85 60W 0 85 60W Pump pressure PSIG 155 130 140 170 Combustion air adjustment turbulator damper 2 3 25 2 5 4 2 2 5 3 2 5 AERO BURNER 1725 RPM Nozzle 100 PSIG pump press...

Страница 16: ...6 6 RIELLO BURNER MODEL 40 Nozzle Delavan 0 85 60W 0 85 60W 1 00 60W 1 10 60W Pump pressure PSIG 140 170 145 140 Combustion air adjustment turbulator damper 2 5 2 5 3 2 75 3 3 3 5 3 25 AERO BURNER 172...

Страница 17: ...er 1 5 2 75 2 5 3 25 3 4 25 AERO BURNER 1725 RPM Nozzle 100 PSIG pump pressure Delavan 0 75 70W 0 85 70W 1 00 70W ELECTRICAL SYSTEM Volts Hertz Phase Operating voltage range Rated voltage Amps Minimum...

Страница 18: ...19 DNS 0596 Rev D FIGURE 4 2 Model MBOV115DABR D FIGURE 4 1 Model MBO115DABR D DNS 0590 Rev D 445 01 4054 06...

Страница 19: ...20 FIGURE 4 3 Models LBO125DABR13 D LBO145DABR34 D OLR182A16C FIGURE 4 4 Model FLO115DABR C OLF140C12C DNS 0666 Rev C DNS 0576 Rev F 445 01 4054 06...

Страница 20: ...21 FIGURE 5 Wiring diagram MBO115DABR D MBOV115DABR D LBO125DABR13 D LBO145DABR34 D OLR182A16C FLO115DABR C OLF140C12C DNS 1014 Rev A 445 01 4054 06...

Страница 21: ...22 PARTS LIST Model MBO115DABR D B50040B 445 01 4054 06...

Страница 22: ...B40492 Top rear panel 30 B40032 Gasket smoke outlet 31 B40046 Smoke outlet assembly 32 B40054 01 Baffle assembly 5 required 33 B40043 Plenum divider 34 B40076 Top division panel 35 B40410 Filter rack...

Страница 23: ...PARTS LIST Model MBOV115DABR D B50041B 445 01 4054 06...

Страница 24: ...ntral support rear baffle and item 32 included 32 B01291 02 Seal strip 3 required 33 B40131 02 Left side panel assembly Item 34 included 34 B40125 02 Left side panel insulation 35 L04G005 Bushing 1 3...

Страница 25: ...26 PARTS LIST Model LBO125DABR13 D B50038C 445 01 4054 06...

Страница 26: ...32 B40032 Gasket smoke outlet 33 B40046 Smoke outlet assembly 34 B40071 Inlet baffle 2 required 35 B40043 Plenum divider 36 B40054 01 Baffle assembly 5 required 37 B40108 Division panel assembly Centr...

Страница 27: ...PARTS LIST Models LBO145DABR34 D OLR182A16C B50039F 445 01 4054 06...

Страница 28: ...B40107 01 Blower door assembly Item 29 included 29 Z99F050 Door handle 30 B40497 Top rear panel 31 B40031 Gasket smoke outlet 32 B40047 Smoke outlet 33 B40054 02 Baffle assembly 7 required 34 B40043...

Страница 29: ...PARTS LIST Model FLO115DABR C OLF140C12C B50042A 445 01 4054 06...

Страница 30: ...rack 29 Z04F004 Paper filter 20 x 20 x 1 1 required 30 B40381 Blower door assembly Item 31 included 31 Z99F050 Acces door 32 B40356 Top back panel assembly 33 Z04F001 Paper filter 10 x 20 x 1 1 requir...

Отзывы: