SERVICE MANUAL
R
−
410A Ductless Split System: DLF4(A/H), DLC4(A/H)
421 08 9204 00
51
UNIT 18K & 24K, 230 Volts (Cont.)
Malfunction
Indoor Unit Display
Outdoor unit display
(LED’s have 3 modes)
OFF,
ON,
Flash
Operation Status
Malfunction
Error
Code
Display
Indicator Display
(LED Flash 0.5s
−
ON/0.5s
−
OFF
Running
LED
Cooling
LED
Heating_
LED
D40
/D5
D41
/D6
D42/
D16
D43/
D30
Overload limit,
compressor speed
reduction
F6
flash 6
times
Operation normal,
compressor speed
reduced.
Refer to
troubleshooting
section of manual.
Over current compressor
speed reduction
F8
flash 8
times
Operation normal,
compressor speed
reduced.
1. System voltage is
too low.
2. System voltage is
high.
Compressor discharge
temp high, compressor
speed reduction
F9
flash 9
times
Operation normal,
compressor speed
reduced.
1. Load is too great,
ambient temp is too
high
2. Refrigerant is low
3. Electric expansion
valve malfunction
DC voltage is too high
PH
flash 11
times
Cooling; compressor
stops, and outdoor fan
runs. Heating all stop
1. Check voltage at
terminal L and N. If
higher than 265VAC,
cut off power supply
and restart system.
2. If input voltage is
normal, check the
voltage at capacitor
on AP1. Replace AP1
if the capacitor
voltage range is
200
−
280v.
System current too high
U9
flash 13
times
Cooling, Dehumidifying;
compressor stops, and
indoor fan motor runs.
Heating all stop.
AP1 malfunction,
replace the AP1 in
outdoor unit.
Compressor current too
high
P5
flash 15
times
Cooling, Dehumidifying;
compressor stops, and
indoor fan motor runs.
Heating all stop.
Refer to service
manual (IPM
protection,
compressor speed
reduction, compressor
overcurrent
protection)
Defrost
H1
flash 1
times
Heating mode,
compressor runs,
indoor/outdoor fan motor
stop
Normal Operation
Compressor overload
protection
H3
flash 3
times
Cooling, Dehumidifying;
compressor stops, and
indoor fan motor runs.
Heating all stop.
1. Compressor
terminal loose, the
resistance should be
lower than 1 ohm.
2. Refer to service
manual.
(discharge/overload
protection)
System overload
protection
H4
flash 4
times
Cooling, Dehumidifying;
compressor stops, and
indoor fan motor runs.
Heating all stop.
Refer to
troubleshooting
section of manual.
IPM protection
H5
flash 5
times
Cooling, Dehumidifying;
compressor stops, and
indoor fan motor runs.
Heating all stop.
Refer to
troubleshooting
section of manual.