Overview 

The EBDSPIR-AT-AD is a passive infrared (PIR) motion 

sensor combined with two output channels capable of 

controlling incandescent, fluorescent and compact 

fluorescent lighting. 

 

Output Channel 1 comprises a mains voltage relay capable 

of simple on/off switching, while Output Channel 2 provides 

dimmable control of 1-10V ballasts. 

 

Functioning as a presence detector, the unit can turn lights 

on when a room is occupied and off when the room is 

empty. Optional settings allow lights to be turned off in 

response to ambient daylight, or to implement a maintained 

illuminance (constant light) system.  The unit also includes 

stored scenes for versatile manual control of lighting levels. 

 

The EBDSPIR-AT-AD can be used as a standalone unit or 

integrated with other devices as part of a system. The  

built-in RF transceiver allows wireless communication with 

all other 

An-10

®

 compatible products, e.g. the AT-BB-IN 

Input Unit, useful for push-button scene selection and 

absence detection. 

 

All functionality is fully programmable. 

Features 

PIR Sensor 

Detects movement within the unit’s detection range, 
allowing load control in response to changes in occupancy. 
 

IR Receiver 

Receives control and programming commands from an  
IR (infrared) handset. 
 

Light Level Sensor 

Monitors the ambient light level, allowing load control 
based on minimum and maximum Lux Level and also for 
providing Maintained Illuminance (constant light) control. 
 

Status LEDs 

These flash 

R

ed and/or 

G

reen to indicate the following: 

Power Input & Switched Output Connector 

(Channel 1)

 

Used to connect mains power to the unit and to connect a 
switched load. 

 
Dimmable Control Output Connector 

(Channel 2)

 

Used to connect 1-10V controllable ballasts and 
transformers for dimmable loads. 

Front features 

Back features 

Walk Test LED active 

        

when movement is detected

 

Valid setting received 

 

Invalid setting received 

 

Software reset received 

 

Factory reset received 

 

RF ceiling PIR presence detector – 1-10V dimming 

EBDSPIR-AT-AD 

Product Guide 

Содержание EBDSPIR-AT-AD

Страница 1: ...ts e g the AT BB IN Input Unit useful for push button scene selection and absence detection All functionality is fully programmable Features PIR Sensor Detects movement within the unit s detection range allowing load control in response to changes in occupancy IR Receiver Receives control and programming commands from an IR infrared handset Light Level Sensor Monitors the ambient light level allow...

Страница 2: ... forced air heating or ventilation Do not fix the sensor to an unstable or vibrating surface Position the sensor so that the occupants of the room fall inside the detection zone shown in below Note that the detection zone illustrated is based on a recommended mounting height of 2 8m A lower height will decrease the overall size of the detection zone Installation Area of lower sensitivity Area of h...

Страница 3: ...ed by a qualified electrician in accordance with the latest edition of the IEE Wiring Regulations and any applicable Building Regulations Mounting procedures WARNING Be careful bending springs when mounting unit Installation Mounting Methods The EBDSPIR AT AD is designed to be mounted using either Flush fixing or Surface fixing using the optional Surface Mounting Box part no DBB Both methods are i...

Страница 4: ... switched output of the EBDSPIR AT AD can either be used to switch a separate channel of standard non dimming luminaires or to isolate the mains supply to dimming ballasts saving on the standby current of the ballasts Multiple luminaires may be connected in parallel to Channel 1 via the N and L Out terminals as long as the maximum total load is not exceeded Channel 2 dimmable output of the EBDSPIR...

Страница 5: ...dressed see Step 1 Set channel addresses and channel load type on page 7 If the detection range is smaller than expected check the diagrams in page 2 Rotating the sensor slightly may improve the detection range HINT The Walk Test LED function can be used to check that the unit is detecting movement in the required area see page 8 for further details What if the load does not turn OFF Ensure that t...

Страница 6: ... Handset UNLCDHS Infrared Handset with LCD For most basic programming operations the UHS4 handset is recommended and the following procedures are based on using this device Point the handset at the Sensor and send the required programming commands to the unit as shown in Steps 1 2 and 3 Valid commands will be indicated by a green LED flash See page 1 for details of other LED responses ...

Страница 7: ... that also have a Local Code of 1 To program the settings for a specific channel on the Sensor you must specify the appropriate channel number i e 1 to 3 using the programming device If no channel number or channel 0 is specified all channels will be set to the same address The output channels also have Circuit numbers This allows different physical channels to be linked and controlled as a single...

Страница 8: ...sh red when movement is detected By default when the detector turns on Local Scene 1 is selected When the detector turns off Local Scene 20 is selected See Scenes Used for Occupancy Detection in Step 3 for further details Switch Level On Off Occupancy detection can be made dependant on the ambient light level using the Lux On Level and Lux Off Level parameters Maintained Illuminance The detector m...

Страница 9: ... has a Fade Rate which is the time taken for the existing output channel levels to fade to the levels defined in the selected Scene By default this is set to 3 seconds for all Scenes Each Scene also has a Maintained Illuminance Level setting By default this is set to 0 i e disabled for all Scenes Scenes Used for Occupancy Detection If movement is detected in Presence mode Local On Scene 1 is selec...

Страница 10: ...d Similarly the corridor lights are controlled by two sensors such that if either sensor detects movement all of the corridor lights turn on Note that only one sensor is physically wired to the lighting circuit In this arrangement the devices in each room need to be programmed with a unique Local Code although the two devices in the corridor share the same code so that they can both control the co...

Страница 11: ... lights via Channel 2 dimmed output Fully independent control of all four circuits can be provided with suitable scene programming Scene selection and manual control of all circuit levels can be achieved via an IR Handset In addition this example shows two AT BB IN input units used in conjunction with wall mounted button plates to provide manual selection of scenes Since the detectors are in Absen...

Страница 12: ... channel Detection Mode Presence Presence or Absence Presence mode allows the output to turn on when movement is detected and off when movement ceases Absence mode allows the output to turn off when movement ceases but must be manually turned on first Output State Set by Scene 0 100 0 off The current output state of the channel for example as set by a Scene Select command Light Level maintained il...

Страница 13: ...0 0 to 100 Maximum dimming output level Min Value 0 0 to 100 Minimum dimming output level Maintained Illuminance Level Set by Scene 0 disabled or 1 to 999 The maintained illuminance target level of the channel when under manual control for example as set by a Scene Select command Max Maintained Illuminance output level 100 0 to 100 Set the maximum maintained illuminance level for the channel Min M...

Страница 14: ...ment Lux off level Switch level off 700 0 disabled or 1 to 999 Sets a maximum light level above which the PIR sensor is disabled preventing lights from being turned on by movement Light Level maintained illuminance 550 0 disabled or 1 to 999 Sets a target light level to be maintained by the lighting system Power Up State On On or Off When power is applied to the unit the PIR sensor goes through a ...

Страница 15: ... If a Local and or Area Step Scene is specified this will be requested first when the Sensor switches off If a Step Scene is not specified or if it times out the Local and or Area Off Scene will be implemented NOTE Area Step and Off Scenes are ignored unless one or more Area Codes are set for the corresponding input channel and they match the Area Codes set in any output channel The values of the ...

Страница 16: ...ming IR handset UNLCDHS Universal LCD IR handset C P Electronics Ltd Brent Crescent London NW10 7XR United Kingdom Tel 44 0 333 900 0671 Fax 44 0 333 900 0674 www cpelectronics co uk enquiry cpelectronics co uk Ref WD382 Issue 2 FM 45789 EMS 534520 Receiver Class 2 Transmitter Duty Cycle 10 on g3 band default band 0 1 on g2 band 1 on g1 band Range The maximum RF range between An 10 devices is 100m...

Отзывы: