ICP DAS, ZT-257x DIO Data Concentrator Quick Start Guide, v1.0
Page 16
Copyright © 2016, by ICP DAS Co., LTD. All Rights Reserved
Step2 Configure the ZT-20xx-IOG module via the ZT-2570 module
①
Set the DIP switch on the ZT-20xx-IOG module
to the “
RUN
” position (i.e., move DIP
switch 1 to the OFF position).
②
Configure the ZT-20xx-IOG module, and then adjust the hardware switches
b
ased on
the Node ID, RF Frequency and Application Mode settings indicated in the table above.
3.1.3 Hardware Settings for the ZT-20xx-IOG Module
adjust the ZT-20xx-IOG module.
③
Reboot the ZT-20xx-IOG module and wait until a connection is established.
④
3.1.4 Software Settings for the ZT-20xx-IOG Module
configure the I/O mapping for the ZT-20xx-IOG module.
Example:
Set the ZT-20xx-IOG module to
“
RUN
”
mode (i.e., move DIP switch 1 to the OFF position) to
remotely connect to the ZT-2570 module. The relevant settings are provided in the table
below.
ZT-20xx-IOG
ZT-2570
Config. Mode
DIP1
OFF
Pan ID
0x0000
Application Mode DIP2
OFF
Application Mode
Level Mode/Transparent
Mode
Encryption
DIP3
OFF
Encryption
Disabled
Node ID
DIP4
OFF
Node ID
0x0000 (ZigBee Coordinator)
DIP5
OFF
RF Channel
0x00
DIP6
OFF
Data Format
None, 8, 1
DIP7
OFF
Baud Rate
115200 bps
DIP8
ON
RF Channel
Rotary
0