WF-2055 Quick Start RevB1.0 2016/09 

 

7/8

 

e.  Use the function code "0x04", and set the reference number as "0x32" 

to get the Counter monitor data. 

 

 

Figure 12

:

 Counter monitor interface 

 

Table 3: 

(0xxxx) DO address

 

Begin Address 

Points 

Descriptions 

Range 

Access Type 

00001 

1~8 

Digital Output 

0=OFF, 1=ON 

R/W 

00011 

1~8 

Clear  

High Speed Counter 

1=Clear 

00021 

1~8 

Clear  

Low Speed Counter 

1=Clear 

 

Table 4: 

(1xxxx) DI address

 

Begin Address 

Points 

Descriptions 

Range 

Access Type 

10001 

1~8 

Digital Input 

0=OFF, 1=ON 

 

Table 5: 

(3xxxx) AI address

 

Begin Address 

Points 

Descriptions 

Range 

Access Type 

30051 

1~16 

(2 points/ Each 

Channel) 

High Speed Counter 

0~4294967295 

30071 

1~16 

(2 points/ Each 

Channel) 

Low Speed Counter 

0~4294967295 

 
 
 
 
 
 
 
 

Содержание WF-2055

Страница 1: ...Antenna 2 4GHz 5 dBi ANT 124 05 Note 1 If any of these items are missed or damaged contact the local distributors for more information Save the shipping materials and cartons in case you want to ship...

Страница 2: ...D 20 EXT GND Table 2 Power Signal Connector Power Signal connector Pin Assignment Description F G Frame Ground Vs 10 30 VDC GND Power RS 232 GND RxD RS 232 RxD TxD RS 232 TxD Table 3 Operating Mode Se...

Страница 3: ...WF 2055 Quick Start RevB1 0 2016 09 3 8 Figure 2 Power and Serial port wire connection I O connection Figure 3 DI DO wire connection...

Страница 4: ...g the power WF 2000 series will be in the operation mode Step 2 Serial port connection WF 2000 series supports RS 232 serial communication The circuit configuration is as shown in Figure 2 If you do n...

Страница 5: ...Wireless encryption Key Here does not have the setting 09 Wireless CH Wi Fi connection channel settings Here set to 2 10 Upload parameters After completing the settings above select the RS 232 interf...

Страница 6: ...lity Connection interface b Use the function code 0x0F and set the reference number as 0x00 to do the DO output control Figure 9 DO output control interface c Use the function code 0x01 and set the re...

Страница 7: ...0001 1 8 Digital Output 0 OFF 1 ON R W 00011 1 8 Clear High Speed Counter 1 Clear W 00021 1 8 Clear Low Speed Counter 1 Clear W Table 4 1xxxx DI address Begin Address Points Descriptions Range Access...

Страница 8: ...tion is established successfully 2 Make sure the network configuration is good TCP IP Port Local IP Net Mask 4 How to restore factory default 1 Power on the WF 2000 series I O module 2 Change the Dip...

Отзывы: