background image

 

WF-2051 Quick Start RevB1.0 2016/10 

8/8

 

Troubleshooting 

Item  Problem Description 

Solution 

Power Failure

 

(PWR LED Off) 

1. Please return to the ICP DAS for inspection and 

repair 

WLAN connection can not be 

established 

1. Make sure that the service set identifier device 

(SSID) settings are the same. 

2. Make sure Wi-Fi transmission Channel settings 

are the same. 

3. Make sure encryption is set, encryption keys are 

the same way 

4. Make sure antenna is connected 

5. Please confirm whether there are barriers on the 

scene. That could result in poor signal quality. 

TCP connection can not be 

established

 

 

1. Make sure WLAN connection is established 

successfully 

2. Make sure the network configuration is good 

(TCP / IP Port, Local IP, Net Mask) 

How to restore factory 
default 

 

 

 

 

 

1. Power on the WF-2000 series I/O module 

2. Change the Dip-Switch position of the WF-2000 

series and to complete the following steps in 5 

seconds. 

Step1. From “OP” to “FW” position. 

Step2. From “FW” to “OP” position. 

Step3. From “OP” to “FW” position. 

Step4. From “FW” to “OP” position. 

3. When the correct implementation of the above 

steps, the Signal Strength LEDs and PWR/Wi-Fi 

LEDS of the WF-2000 series should be turn on, 

and that should be turn off after 500 ms later. 

4. Reset the power the WF-2000 series would back 

to factory defaults. 

 

 

Technical Support 

If you have problems about using the WF-2000 series I/O mod

ule

please contact ICP DAS Product Support. 

Email:

 

[email protected]

 

Step1 

Step2 

Step3 

Step4 

Содержание WF-2051

Страница 1: ...e Antenna 2 4GHz 5 dBi ANT 124 05 Note 1 If any of these items are missed or damaged contact the local distributors for more information Save the shipping materials and cartons in case you want to ship in the future 2 This document supports the RevB version for the WF 2051 module For the previous version please refer the v1 x version quick start on the CD Appearance and pin assignments Figure 1 Ap...

Страница 2: ...nnector Pin Assignment Description F G Frame Ground Vs 10 30 VDC GND Power RS 232 GND RxD RS 232 RxD TxD RS 232 TxD Table 2 Operating Mode Selector Switch Operating Mode Selector Switch Mode Jumper Position Description FW Firmware update mode OP Firmware operation mode Hardware Connection Power and Serial port connection ...

Страница 3: ...WF 2051 Quick Start RevB1 0 2016 10 3 8 Figure 3 Power and Serial port wire connection I O connection Figure 4 DI Dry contact wire connection Figure 5 DI Wet contact wire connection ...

Страница 4: ...ng the power WF 2000 series will be in the operation mode Step 2 Serial port connection WF 2000 series supports RS 232 serial communication The circuit configuration is as shown in Figure 3 If you do not need parameter setting this step can be omitted Step 3 Power connection Connect the power supply to WF 2000 series power terminator as shown in Figure 3 WF 2000 series connection setting WF 2000 S...

Страница 5: ...y Wireless encryption Key Here does not have the setting 09 Wireless CH Wi Fi connection channel settings Here set to 2 10 Upload parameters After completing the settings above select the RS 232 interface communication Net ID and COM Num Press Write button to upload the parameters PC Wireless Network Configuration and Connection 01 TCP IP Setting a Entry the IP address as 192 168 255 x where x is ...

Страница 6: ...k the Connect button Figure 9 Modbus TCP utility Connection interface b Use the function code 0x02 and set the Reference Number as 0x00 Bit Count as 0x10 to get the 16 CHs DI value Figure 10 Digital Input reading screen c Use the function code 0x04 and set the Reference Number as 0x32 Word Count as 0x10 to get the 8 CHs Counter value 4 bytes each counter Figure 11 Counter reading screen ...

Страница 7: ...r 1 Clear W 00021 1 8 Clear Low Speed Counter 1 Clear W Table 4 1xxxx DI address Begin Address Points Descriptions Range Access Type 10001 1 16 Digital Input 0 OFF 1 ON R Table 5 3xxxx AI address Begin Address Points Descriptions Range Access Type 30051 1 16 2 points Each Channel High Speed Counter 0 4294967295 R 30071 1 16 2 points Each Channel Low Speed Counter 0 4294967295 R ...

Страница 8: ...is established successfully 2 Make sure the network configuration is good TCP IP Port Local IP Net Mask 4 How to restore factory default 1 Power on the WF 2000 series I O module 2 Change the Dip Switch position of the WF 2000 series and to complete the following steps in 5 seconds Step1 From OP to FW position Step2 From FW to OP position Step3 From OP to FW position Step4 From FW to OP position 3 ...