tWF-DA1PD2R1 User’s Manual
tWF-DA1PD2R1
User’s Manual (Rev1.0, APR./2019) ------------- 22
4.
Application
Users can use a Computer or Smart Device to communicate with the tWF devices in
the application. It can complete the purpose of I/O control to wireless network by this way.
Figure 4-1
:
tWF + PC/Laptop/Smart Device application architecture
4.1
Connection with Modbus TCP utility
a. Open Modbus TCP utility and key in the IP address , Port as "502". Finally,
click the "Connect" button.
b.
If the network settings are correct, this will immediately establish a
connection.
c.
Use the function code "0x02", and set the Reference Number as "0x00", Bit
Count as "0x08" to get the 8 CHs DI value.
Figure 4-2
:
Digital Input reading
d.
Use the function code "0x01", and set the Reference Number as "0x00", Bit
Count as "0x08" to get the 8 CHs DO value.