: the state of the NMT Slave
4: STOPPED
5: OPERATIONAL
127: PRE_OPERATIONAL
8.2.4 Special Functions for PM-3133i-CPS
8.2.4.1 Power Meter Data Table
The PM-3133i-CPS Manufacturer in the Specific Profile Area defines some entries,
which are used for the power meter data. The objects with index 0x3200~0x3208 will
map to the PDOs as below table. The D0 to D7 represent the CANopen message from
Data0 to Data7.
No.(PDO)
COB-ID
Data
Length
D0~D3
D4~D7
1
0x180+Node-ID
8
kW(Kw_a)
kWh_a
2
0x280+Node-ID
8
kW(Kw_b)
kWh_b
3
0x380+Node-ID
8
kW(Kw_c)
kWh_c
4
0x480+Node-ID
8
kW(Kw_tot)
kWh_tot
5
---
8
Volt(V_a)
Amp(I_a)
6
---
8
Volt(V_b)
Amp(I_b)
7
---
8
Volt(V_c)
Amp(I_c)
8
---
8
Volt(V_avg)
Amp(I_avg)
9
---
8
kvar(kvar_a)
kVA(Kva_a)
10
---
8
kvar(kvar_b)
kVA(Kva_b)
11
---
8
kvar(kvar_c)
kVA(Kva_c)
12
---
8
kvar(kvar_tot)
kVA(Kva_tot)
13
---
8
PF_a
kVAh_a
14
---
8
PF_b
kVAh_d
15
---
8
PF_c
kVAh_c
16
---
8
PF_tot
kVAh_tot
17
---
8
kvarh_a
Freq_a
18
---
8
kvarh_b
Freq_b
19
---
8
kvarh_c
Freq_c
20
---
8
kvarh_tot
Freq_avg