PM
-
3133i User
’s Manual v1.02
Last Revised: Apr. 2023 Page: 63
Copyright © ICP DAS Co., Ltd. All Rights Reserved.
E-mail: [email protected]
2
read Freq_avg data
INTEGER 32
RO
3209 0420h
8.3.2 Manufacturer Specific Profile Area
In the following table, there is information about some special functions for the
PM-3133i-CPS. The index from 0x3200 to 0x3209 records the power meter
measurement parameters. The number of these entries will be automatically updated
when the PM-3133i-CPS boot up. 0x320A is meter parameters information. 0x320B
stores three meter parameters including Meter Ratio, PT Ratio and RT Ratio. PT Ratio
means potential transformer ratio, the default value is 100 and the unit is 0.1. RT Ratio
means current transformer ratio, the default value is 1 and the unit is 1.
Idx
Sidx Description
Type
Attr
Default
3200h
0
largest sub-index supported for
“kW”
UNSIGNED 8
RO
4
1
kW(Kw_a)
INTEGER32
RO
0
2
kW(Kw_b)
INTEGER32
RO
0
3
kW(Kw_c)
INTEGER32
RO
0
4
kW(Kw_tot)
INTEGER32
RO
0
3201h
0
largest sub-index supported for
“kWh”
UNSIGNED 8
RO
4
1
kWh_a
INTEGER32
RO
0
2
kWh_b
INTEGER32
RO
0
3
kWh_c
INTEGER32
RO
0
4
kWh_tot
INTEGER32
RO
0
3202h
0
largest sub-index supported for
“Volt”
UNSIGNED 8
RO
4
1
Volt(V_a)
INTEGER32
RO
0
2
Volt(V_b)
INTEGER32
RO
0
3
Volt(V_c)
INTEGER32
RO
0
4
Volt(V_avg)
INTEGER32
RO
0
3203h
0
largest sub-index supported for
“Amp”
UNSIGNED 8
RO
4
1
Amp(I_a)
INTEGER32
RO
0
2
Amp(I_b)
INTEGER32
RO
0