PM
-
3133i User
’s Manual v1.02
Last Revised: Apr. 2023 Page: 20
Copyright © ICP DAS Co., Ltd. All Rights Reserved.
E-mail: [email protected]
SW7
-
SW8 setting
PM-3133i
:
For Baud Rate Setting
Baud Rate
SW 7
SW8
9600 bps
OFF
OFF
19200 bps (Default)
ON
OFF
38400 bps
OFF
ON
115200 bps
ON
ON
Add the Bias Resistor on RS-485 Network for stable signal
The RS-485 master is required to provide the bias for PM-3133i series. Otherwise, the tM-SG4
or SG-785 should be added to provide the bias. All ICP DAS controllers and converters provide
the bias.
SW9
-
SW10 setting
PM-3133i
:
Select the different wiring mode
(Please select the Software setting, if 1P2W-1CT or 1P3W-2CT is used)
Wiring
SW 9
SW 10
Software setting
OFF
OFF
3P3W-2CT
ON
OFF
3P3W-3CT
OFF
ON
3P4W-3CT
ON
ON