Communication 

3.1. 

RS-485 & CAN setting 

 

Default setting for RS-485: 

19200, n, 8, 1

 ,

for CAN:

 125K bps

 

 

DIP switch (SW1-SW6) is used for Modbus address(or 

CANopen Node ID) setting, default is 1, i.e. all OFF

 

For example:

 Modbus address(or CANopen Node ID) is 10

find the table of DIP switch 1-6 is 

ON, OFF, OFF, ON, OFF, OFF

 

 

SW1

SW6 setting 

Setting Modbus-RTU address for communication (1-64) 

Modbus Address 

SW 1 

  SW 2 

SW 3 

SW 4 

SW 5 

SW 6 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON

 

OFF 

OFF 

OFF 

OFF 

ON

 

ON

 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON

 

OFF 

OFF 

OFF 

ON

 

OFF 

ON

 

OFF 

OFF 

OFF 

OFF 

ON

 

ON

 

OFF 

OFF 

OFF 

ON

 

ON

 

ON

 

OFF 

OFF 

OFF 

OFF 

OFF 

OFF 

ON

 

OFF 

OFF 

10 

ON

 

OFF 

OFF 

ON

 

OFF 

OFF 

 

 

SW7

SW8 For Baud Rate Setting 

 

RS-485 

CAN 

  SW 7 

SW8 

9600 bps 

125k(Default) 

 

OFF 

OFF 

19200 (Default) 

 

250k bps 

ON 

OFF 

38400 bps 

500k bps 

OFF 

ON

 

115200 bps 

1M bps 

ON 

ON

 

 

PM-3133

Select the different wiring mode   

(Please select the Software setting, if 1P2W-1CT or 1P3W-2CT is used) 

Models 

PM-3133

 

PM-3133-MTCP

 

Wiring 

SW 9 

SW 10 

SW 1 

SW 2 

Software setting 

OFF 

OFF 

OFF 

OFF 

3P3W-2CT 

ON

 

OFF 

ON

 

OFF 

3P3W-3CT 

OFF 

ON

 

OFF 

ON

 

3P4W-3CT 

ON

 

ON

 

ON

 

ON

 

Ethernet default settings

 

For recovering to default settings, dip 
Init/Run Switch (SW 4) to Init  position for 
10 seconds after power on, the settings 
will be changed as default values. Must dip 
back to Run position and repower on after settings changed. User also can 
recover settings to default value by Modbus command. 

 

IP Address 

192.168.255.1 

Subnet mask 

255.255.0.0 

Gateway 

192.168.0.1 

Port 

502 